Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.3 LAccepted-AOC FLAT 7 SRADHANJALI APARTMENT 393 3F 6 PRINCE ANWAR SHAH ROAD PODDAR NAGAR KOLKATA WEST BENGAL 700068 | KOLKATA | WEST BENGAL | 700068 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹19.2 L+₹1.9 L (10.7%)Rejected-Finance MOSAT HARIPUR RD VILL P O HARIPUR DIST HOOGHLY PIN 712701 | HARIPUR | HOOGHLY | WEST BENGAL | 712701 | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹20.4 L+₹3.1 L (17.6%)Rejected-Finance 4 28 VIVEK NAGAR KOLKATA 700075 | KOLKATA | KOLKATA | WEST BENGAL | 700075 | L3 | Rejected-Finance 3rd lowest bidder |
| Sl No | Description | Qty | Unit | MEGHJIT POWER SOLUTIONS LLP L1 | GHANASHYAM ELECTRIC STORES L2 | DB Enterprise L3 |
|---|---|---|---|---|---|---|
| 1.00 | SITC of 10 KVA UPS including Battery Bank of 18720 VAH for each UPS with SMF Battery of 12 Volt. Three phase Input / Single phase Output, Inbuilt/External Isolation Transformer, static by pass arrangement, compatible with D.G. Set, DSP controlled IGBT based rectifier with minimum 95% efficiency on 100% Load. The UPS shall be provided with active input P.F. Correction system to obtain 0.99 lag to unity at 100% resistive Load, Wave form - Pure Sine wave. It Should be capable of operating in 50 deg C above ambient temperature, Built in Solid State float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least 15% of the total battery current. The UPS Should have current limiting protection, built in over load / Short circuit protection with snubber circuits for current limit. Soft start arrangement, Over voltage / under voltage protection, mains ON, Inverter ON/ OFF/ FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low, Static by-pass ON, Over temperature. Battery set Complete with self-standing cubicle or cabinet. The UPS should have external automatic load transfer switch for parallel operation.(3 nos in parallel)/ paralleing kit and suitable size battery rack made of MS /SS. The UPS connection have to be made with suitable size of 1.1 KV gradeed FRLS 'Cu' wire as per direction of EIC. | 6 | Sets | 2,89,100 ₹17,34,600 Lowest | 3,20,000 ₹19,20,000 | 3,40,000 ₹20,40,000 |
| 1.01Regulated Sealed Lead Acid Battery, Construction type : AGM or VRSLAB in ABS Flame & Fire Retardant Rating, 18720 VAH (for each UPS) (12V, SMF Battery) Back up time 30 Min at full load.. Certificate : ISO 9001:2015, ISO 14001:2015, IOS 18001,OHSAS 18001. CE Certification: IEC/ EN 62040-1-1, IEC/ EN50091- 1,IEC/EN 60950(Safety),IEC/ EN 5009 I-2,IEC/ EN 62040-2(EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/ EN 60146 (Design & Manufacture) [Battery Make(Fire and Flame Retardent type): Amararaja Quntra/ Exide ] (UPS Make: APC-Schneider Electric / NUMERIC/ VERTIV/ Delta) | ||||||
| 1.02Terms and Condition: | ||||||
| 1.03The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. | ||||||
| 1.04Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. | ||||||
| 1.05If any refurbished material is supplied and installed, penal action will be taken as per existing rules | ||||||
| 1.06Warranty - 2years (On site) 2. Defect Liability Period -2 Years . | ||||||
| 1.07Make & model of each and every material to be approved by EIC | ||||||
Tender Value
₹17 L
EMD Value
₹34,000
Closing Date
31 Oct 2025, 12:00 pmClosed
Exe. Engr.-I, Kol. South Health El. Divn., PWDte
75 D H Road Kidderpore Kol_23
Electrical works for construction of 2 Storied Building for 50 bedded Critical Care Block at Kolkata Police Hospital, Annex-VI of IPGMER - SSKM (Centre of Excellence), Kolkata-SITC of 10 KVA UPS
2025_WBPWD_919329_1
WBPWD/EE-I/KSHED/Q67/25-26
Open Tender
Electrical Work/ Equipment
Item Rate
30 days
Kolkata
Please refer Tender documents.
4 documents required · 4 mandatory
₹34,000
O/o Exe. Engr., Kol. South Health El. Divn., PWDte
2 Sept 2026
10 Oct 2025
3 Nov 2025
10 Oct 2025
31 Oct 2025
17 Oct 2025
16 Oct 2025
Amount
SITC of 10 KVA UPS including Battery Bank of 18720 VAH for each UPS with SMF Battery of 12 Volt. Three phase Input / Single phase Output, Inbuilt/External Isolation Transformer, static by pass arrangement, compatible with D.G. Set, DSP controlled IGBT based rectifier with minimum 95% efficiency on 100% Load. The UPS shall be provided with active input P.F. Correction system to obtain 0.99 lag to unity at 100% resistive Load, Wave form - Pure Sine wave. It Should be capable of operating in 50 deg C above ambient temperature, Built in Solid State float cum boost charger with automatic boost / trickel charge mode with current Limiting features. The charger should be designed for at least 15% of the total battery current. The UPS Should have current limiting protection, built in over load / Short circuit protection with snubber circuits for current limit. Soft start arrangement, Over voltage / under voltage protection, mains ON, Inverter ON/ OFF/ FAULTY/ TRIP (Reason), Charger ON/ FAULTY or TRIP, Battery Low, Static by-pass ON, Over temperature. Battery set Complete with self-standing cubicle or cabinet. The UPS should have external automatic load transfer switch for parallel operation.(3 nos in parallel)/ paralleing kit and suitable size battery rack made of MS /SS. The UPS connection have to be made with suitable size of 1.1 KV gradeed FRLS 'Cu' wire as per direction of EIC.
Regulated Sealed Lead Acid Battery, Construction type : AGM or VRSLAB in ABS Flame & Fire Retardant Rating, 18720 VAH (for each UPS) (12V, SMF Battery) Back up time 30 Min at full load.. Certificate : ISO 9001:2015, ISO 14001:2015, IOS 18001,OHSAS 18001. CE Certification: IEC/ EN 62040-1-1, IEC/ EN50091- 1,IEC/EN 60950(Safety),IEC/ EN 5009 I-2,IEC/ EN 62040-2(EMC Emmission), IEC/EN 62040-3 (Performance & Design), IEC/EN 61000-4(EMC Emmunity) & IEC/ EN 60146 (Design & Manufacture) [Battery Make(Fire and Flame Retardent type): Amararaja Quntra/ Exide ] (UPS Make: APC-Schneider Electric / NUMERIC/ VERTIV/ Delta)
Terms and Condition:
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Warranty - 2years (On site) 2. Defect Liability Period -2 Years .
Make & model of each and every material to be approved by EIC
GHANASHYAM ELECTRIC STORES (BID ID -7196916)
DB Enterprise (BID ID -7242064)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .