| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.6 LAccepted-AOC A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹28.5 L+₹87,868 (3.18%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L2 | Rejected-Finance Being Not Lowest | |
| 3 | L3₹28.6 L+₹1.0 L (3.68%)Rejected-Finance | L3 | Rejected-Finance Being Not Lowest | |
| 4 | L4₹30.8 L+₹3.2 L (11.5%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L4 | Rejected-Finance Being Not Lowest | |
| 5 | L5₹31.0 L+₹3.4 L (12.3%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L5 | Rejected-Finance Being Not Lowest |
Tender Value
₹43.7 L
EMD Value
₹43,700
Closing Date
6 Feb 2021, 6:00 pmClosed
ARJUN PATRO IDSE
GE U ELECTRIC SUPPLY DELHI CANTT
SPL REPAIR TO REPLACEMENT OF LT PANEL LT CABLE AT BLDG NO. P5 P6 P15 P27 P28 AND P47 SPECIAL REPAIR TO TRANSFORMER AND ALLIED WORKS IN NOM VARUNA and PROVISION OF BORING HOLES UNDER N8 BY TECHNOLOGY INCLUDING REROUTING HT CABLE FOR NOM VARUNA IN TH
2020_MES_398427_1
GE ELECT/D-101/2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC SUPPLY DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹43,700
Yes
17 Feb 2021
16 Jan 2021
8 Feb 2021
17 Jan 2021
6 Feb 2021
1 Feb 2021
Amount
Supply, install, test and commissioning in replacement of factory made tested Out door LT panel board cubical double door compartment outdoor type plate maounted suitable for 440 Volt 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bar of rating 1260 Amp installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-65 class protection and complete made of 3.15mm CRCA MS Sheet and inner compartment/Partition sheet 2 mm, 50x50x6 mm thick MS angle iron frame work,painting of 7 tank processed powder coated of outdoor specified and rare opening type with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cabel IS-694-marked, 1100 Volts grade of appropriate size (but not less than 4 Sqmm), earth bus strip with earthing terminals and comprising of the following including necessary brick work and PCC in 1:2:4 type B1 using 20 mm graded stone aggregate for platform of suitable size.
Accessories for Pillar Box : - Multi function meter point PS 485/232, 5 display, class 0.5/1. 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 630 A, 04 pole,50 KA,MCCB Microprocessor based type along with sprader terminals-01 no, (b)Outgoing:- (i) 315/320 A, 03 Pole, 50 KA,MCCB Microprocessor based type along with sprader terminals-01 no -(ii) 125 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-01 no -(iii) 100 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-03 no
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through extended links. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.
Supply, install, test and commissioning in replacement of factory made tested Out door LT panel board cubical double door compartment outdoor type plate maounted suitable for 440 Volt 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bar of rating 650 Amp installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-65 class protection and complete made of 3.15mm CRCA MS Sheet and compartment sheet 1.6 mm, 50x50x6 mm thick MS angle iron frame work, powder coated finished over one coat of red oxide on out side surface and painted inside with 02 coat of red oxide primer and rare opening type with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cabel IS-694-marked, 1100 Volts grade of appropriate size (but not less than 4 Sqmm), earth bus strip with earthing terminals and comprising of the following including necessary brick work and PCC in 1:2:4 type B1 using 20 mm graded stone aggregate for platform of suitable size.
Accessories for Pillar Box : - Multi function meter point PS 485/232, 5 display, class 0.5/1. 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 320/315 A, 04 pole,50 KA,MCCB Microprocessor based type along with sprader terminals-01 no, (b)Outgoing:- (i) 100 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-05 no -(ii) 63 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-01 no
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through extended links. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.
Supply, install, test and commissioning in replacement of factory made tested Out door LT panel board cubical double door compartment outdoor type plate maounted suitable for 440 Volt 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bar of rating 500 Amp installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-65 class protection and complete made of 3.15mm CRCA MS Sheet and inner compartment/Partition sheet 2 mm, 50x50x6 mm thick MS angle iron frame work,painting of 7 tank processed powder coated of outdoor specified and rare opening type with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cabel IS-694-marked, 1100 Volts grade of appropriate size (but not less than 4 Sqmm), earth bus strip with earthing terminals and comprising of the following including necessary brick work and PCC in 1:2:4 type B1 using 20 mm graded stone aggregate for platform of suitable size.
Accessories for Pillar Box : - Multi function meter point PS 485/232, 5 display, class 0.5/1. 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 250 A, 04 pole,35 KA,MCCB Microprocessor based type along with sprader terminals-01 no, (b)Outgoing:- (i) 160 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-02 no -(ii) 100 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-02 no (iii) 63 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-02 no
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through extended links. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.
Supply, install, test and commissioning in replacement of factory made tested Out door LT panel board cubical double door compartment outdoor type plate maounted suitable for 440 Volt 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bar of rating 350 Amp installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-65 class protection and complete made of 3.15mm CRCA MS Sheet and inner compartment/Partition sheet 2 mm, 50x50x6 mm thick MS angle iron frame work,painting of 7 tank processed powder coated of outdoor specified and rare opening type with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cabel IS-694-marked, 1100 Volts grade of appropriate size (but not less than 4 Sqmm), earth bus strip with earthing terminals and comprising of the following including necessary brick work and PCC in 1:2:4 type B1 using 20 mm graded stone aggregate for platform of suitable size.
Accessories for Pillar Box : - Multi function meter point PS 485/232, 5 display, class 0.5/1. 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 160 A, 04 pole,35 KA,MCCB Microprocessor based type along with sprader terminals-01 no, (b)Outgoing:- (i) 63 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-05 no
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through extended links. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.
Supply, install, test and commissioning in replacement of factory made tested Out door LT panel board cubical double door compartment outdoor type plate maounted suitable for 440 Volt 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bar of rating 500 Amp installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-65 class protection and complete made of 3.15mm CRCA MS Sheet and inner compartment/Partition sheet 2 mm, 50x50x6 mm thick MS angle iron frame work,painting of 7 tank processed powder coated of outdoor specified and rare opening type with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cabel IS-694-marked, 1100 Volts grade of appropriate size (but not less than 4 Sqmm), earth bus strip with earthing terminals and comprising of the following including necessary brick work and PCC in 1:2:4 type B1 using 20 mm graded stone aggregate for platform of suitable size.
Accessories for Pillar Box : - Multi function meter point PS 485/232, 5 display, class 0.5/1. 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 250 A, 04 pole,35 KA,MCCB Microprocessor based type along with sprader terminals-01 no, (b)Outgoing:- (i) 63 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-08 no
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through extended links. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.
Supply, install, test and commissioning in replacement of factory made tested Out door LT panel board cubical double door compartment outdoor type plate maounted suitable for 440 Volt 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bar of rating 1260 Amp installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-65 class protection and complete made of 3.15mm CRCA MS Sheet and inner compartment/Partition sheet 2 mm, 40x40x6 mm thick MS angle iron frame work,painting of 7 tank processed powder coated of outdoor specified and rare opening type with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cabel IS-694-marked, 1100 Volts grade of appropriate size (but not less than 4 Sqmm), earth bus strip with earthing terminals and comprising of the following including necessary brick work and PCC in 1:2:4 type B1 using 20 mm graded stone aggregate for platform of suitable size.
Accessories for Pillar Box : - Multi function meter point PS 485/232, 5 display, class 0.5/1. 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 630 A, 04 pole,50 KA,MCCB Microprocessor based type along with sprader terminals-01 no, (b)Outgoing:- (i) 250 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-02 no (ii) 200 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-04 no (iii) 100 A, 03 Pole, 35 KA,MCCB Microprocessor based type along with sprader terminals-01 no
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through extended links. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture.
Earthing complete in replacement with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in soft/loose soil and testing complete all as specified and directed and shown in electrical plate number 3 of MES SSR part-I(1991) (a) Excavation and earth work for drilling hole for electrode in soft/loose Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 40 mm nominal bore medium grade GI protection pipe for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
Supply & Fix in replacement Junction/loop in - loop out box weather proof incluiding made out of one piece mounted SMC base and door pole mounted hinged door size 333x233x120 mm out side and 300x200x105 mm inside dimensions comprising of aluminium bus bar 4 strip for 3 phase and neutral 63 Amps and 02 Amps MCB SP with base incluiding embossing/ painting of danger notice of size not less than 10cm x 7.5 cm with letters,figures band conventional skull and bones in signal red colour on front face of junction box body complete all as specified and directed.
Disconnecting of all HT/LT connection electrically and machanically of Indoor transformers 400 KVA capacity, taking out from Sub- Station carefully including transportation to MES yard, complete all as directed.
Supply & install ,testing and commissioning of transformer step down, indoor type copper wound 11KV/433 Volts (at no load) AC 3 phase 50 Hz 500 KVA capacity, core type, oil immersed naturally air cooled, oil natural air natural (ON/AN) , with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11 with neutral brought out on secondry side (LV) and having taping at +5% to 10% in steps of 2.5% on HV side to be changed by means of hand operated off load tap changergear. The maximum temperature rise should not exceed 50 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree celsius transformer shall be of BOLTLESS core design. Transformer shall be double wound, core type with low loss, non ageing, high permeability prime grade crgo with M4 grade or better, perfectly insulated and clamped to minimize noise and vibrations. The transformer shall be IS/IEC 60076and as per IS-1180 part - I of 2014 marked and shall comprise of the following :-
(a) One cable box on HT side (Primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washer , with cable glands suitable for reception/taking out 3 core 120 Sqmm, HT 11000 volts grade, XLPE insulated and PVC sheathed, heavy duty , armoured cables including jointing materials complete. (b) One cable box on LT side(secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands suitable for reception/taking out single core 1000 sqmm, LT 1100 volts grade, PVC/XLPE insulated and PVC sheathed, heavy duty, armoured cables including jointing materials complete. (c ) conservator with filter type drain valve and oil level guage. (d) De-hydrating breather with first fill of dehydrating agent (Silica Gel). (e) Explosive vent, Thermometer pocket on tank cover, oil level guage, Oil drain filter valve, Lifting ligs,oil filling hole with cap/plug with connection plate complete, Air release valve plug and four nos plain solid cast steel detachable roller (f) One no 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminals on tank cover to facilitate fixing of 50x6mm galvanised iron earth strip for earthing of body. (h) Rating plate and terminal marking plate. (j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral. (k) First fill of new and unused transformer oil, IS-335 of 1986 marked, filtered and tested upto 50 KV dielectric strength at 2.5 mm air gap between testing electrodes, specific resistance at 27 Degree celsius Ohm-om 500 x 10 the power12, water content 50 PPM, Dielectric dissipation factor (tan Deta at 90 degree celsius) 0.005, Neutralisation value mg of KOH/gm of oil 0.03, Inter facial tension N/M at 27 Degree celsius - 0.04, flash point 140 Degree celsius and sluge 0.1 % by weight.
(l) Providing adequate size and nos of channels, embeded in floor, for movement of transformer. (m) Tranformer losses shall not exceed the loses mentioned in Table 6 of IS: 1180 of 2014 Part - I with energy Effeciency level - II. (n) Oil temperator indicator , winding temperature indicator, marshlig box single window, double flit buchhols relay with alarm and trip contact including connection to existing RMU relay with PVC insulated PVC sheathed cable galvanized steel strip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm 10 core 1100 volts grade.
Supply and fix cable end jointing kit for 11 KV earth grade cable for indoor terminal heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 185 sqmm.
Taking out old damaged LT XLPE underground cable 10 sqmm 4 core from trenches complete all as specified and directed.
Taking out old damaged HT 11000 V underground cable 185 to 300 sqmm 3.0 core from trenches/duct complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 Sqmm 4 core
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 volts grade with stranded aluminium conductor of size 300 Sqmm 3.0 core
Supply and fix in replacement suspension type decorative street light fitting, made of spun aluminium housing, polycarbonate diffuser protector with IP 65 protection for optical compartment with 60 W LED systemas per sample, duly pre wired 230 volts AC , 50 Hz
Supply and fix PVC insulated copper cable Three core of size 2.5 sqmm
Excavation in trenches in soft and loose soil n.exc 1.5 mtr wide and n.exc. 1.5 mtr depth for laying and taking out of electric power cable and getting out all as specified and directed by engineer -in-charge.
M&L for returing filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil.
M&L for removing of excavated material n exc. 50m and depostiting where directed at a level n exc. 1.5m in soils
M & L for sand as in sand cushioning to underground PVC cable incl punning down of sand layer all as specified
Supply and laying burnt brick sub class 'B' 22 X 10 X 7.5 cm locally available laid in length of brick perpendicular to the length of cable
Supply and lay unreinforced precast concrete cable covers class HVP Type -1 with peak of size 300 x 180 x 40 mm. compete all as specified and directed
Supply and fix cable jointing kit for 11 KV earth grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 300 sqmm.
Taking out old damaged HT XLPE underground cable Three core 185 sqmm from trenches complete all as specified and directed.
M&L for boring of holes under road/pavement/hard standing by trenchless technology using ultra sound technique and necessary machine including material and labour for HDPE pipe of 160 mm dia suitable for 04 Kg/cm working pressure. Wall thickness of pipe not less than 6.5 mm. NOTE : The obtaining of permision for trenchless boring under NH -8 and IGL will be responsibility of the contractor.
Labour and T&P only for relaying the HT cables in same/any position all as directed by engr - in - charge after dressing the soil complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded,galvinised steel strip or wire armoured, electric power cables (heavy duty) 11000 Volt grade with stranded aluminium conductor of size 185 Sqmm 3 core
Supply and fix cable end jointing kit for 11 KV grade cable for indoor terminal heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 185 sqmm.
Supply, jointing and testing, straight through joint, heat shrinkable type, suitable for HT, 11 KV (E) XLPE cables, aluminium stranded conductors cable of size 185 Sqmm ,3 core.
S &F fire retardant/extinguishing electric insulated synthetic mat Insulatica - 2000 of 2.5 mm thick + 10% confirming to BIS : DOC No ET-02(5440) dated 30 Apr 2004, meeting requirement of IS-3043,IS-5216 (Part -I,II &II), IS-8437 and IEC-479 pub-I,tested for breakdiwn strength, tensile/Elongation ageing properties,insulation resistance , effect of acid, alkaline, diesel and transformer oil leakage current test, fire test etc, having minimum width of 1000mm + 20mm including all allied materials such as PU-Resin, chemical bound (Hasdornor) special PVC adhesive liquid primer etc of required quantity to complete the job as per site requirement of all voltages not exceeding 11 KV system without HT trolley movement.
Supply and fix cable route indicator made of RCC with 8 mm TMT size 1.5 M height x 60 cm wide x 10 cm thick tapered on top visible above ground duly painted with synthetic enamel paint of yellow colour base and letters with black paint complete all as specified and directed.
Supply, installation & commissioning and testing in replacement of SHF/VRLA Battery, Battery charge panel comprising 12 Nos. 2 Volts 100 AH tubular cell, self contained floor mounted sheet steel cabinet with two tiers for housing the batteries. The charging equipment will be operated from 240Volt +/- 10%, 50 c/s supply. The cabinet should be complete and internally wired auto/mannual switch. The charger unit should house, resstance control DC ammeter , Voltmeter and fuses, AC supply failure alarm. Complete accessories required for commissioning is included in the scope of work. DC distribution board comprising of 63 Amps DPMCB as incomer and 2 nos of 15 A DP MCB as O/G Battery Charger with batteries Automatic Float cum Bboost charger of 16 A to give 24 V DC output at 60 Ah capacity
M&L in replacement mild steel chequered plate 10 mm thick incliding cutting of suitable size for duct cover at site complete all as specified and directed by Engr-in-Charge.
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge
MV Engineers And Contractors
Water Power Engg. Enterprises
M/s Adhikari construction co.
Vijay Electricals
Rajindera Enterprises
mayur enterprises
M/s ELECTROSHINE ENGINEERS
Buddham Builders
stage.html
html • 0.07 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .