Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.5 LAccepted-Finance | L1 | Accepted-Finance Lowest | |
| 2 | L2₹36.0 L+₹2.5 L (7.42%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹38.9 L+₹5.4 L (16.1%)Rejected-Finance S NO 50 8 MAMTA SOCIETY VADGAONSHERI BEHIND AYYAPPA TEMPLE PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹44.0 L+₹10.5 L (31.3%)Rejected-Finance | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹44.1 L+₹10.6 L (31.6%)Rejected-Finance 1 NEAR AKBARIYA MASJID WIMBERLYGUNJ SOUTH ANDAMAN ANDAMAN NICOBAR 744206 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744206 | L5 | Rejected-Finance Not Lowest |
| Sl No | Description | Qty | Unit | PARAMOUNT ELECTRICALS L3 | purva engineears and contracters L4 | Chaulya Enterprises L6 | Adinath Technical Services L7 | TRINSIYA ASSOCIATE L1 | TULAJA ENTERPRISES L2 | SBS Enterprises L5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI (TTA Panels complying to IEC 61439) approved double door floor mounted outdoor type, as per IP-55 grade,Single front, fixed, Compartmentalised, floor mounted, cable entry, paint shade RAL 7032 Siemens Grey made out of CRCA sheet 3.15 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: | 1 | Each | 3,99,000 ₹3,99,000 | 2,00,000 ₹2,00,000 Lowest | 7,25,000 ₹7,25,000 | 7,42,500 ₹7,42,500 | 5,75,000 ₹5,75,000 | 5,75,000 ₹5,75,000 | 6,32,000 ₹6,32,000 |
| 1.01Incoming | ||||||||||
| 1.02(a) 630A, 4P, 50kA, Manual Drawout, ACB with Universal Termination, Micropro3- 3.1 Release with LSING Protection, Type: Winmaster with breaking capacity 50 KA at 415 volts Ics=100% Icu With on/off/trip indicator -01 No. (CAT No WX306N4P1MDOA (S) of C &S) | ||||||||||
| 1.03(b) Copper bus bar of suitable size 1000 Amps TPN -01 Set | ||||||||||
| 1.04(c) Digital Voltemeter 0-500 volts with selector switch - 01 No (Secure) | ||||||||||
| 1.05(d) Digital Amp meter 0-200 Amp with selector switch - 01 No (Secure) | ||||||||||
| 1.06(e) Amber, Green , Yellow,blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC (C &S RCB7-IVL75, RCB7-IVL73,RCB7-IVL78,RCB7-IVL76)-01 Nos Each | ||||||||||
| 1.07Red Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC (C &S RCB7-IVL74)02 Nos | ||||||||||
| 1.08(f) 3 PH Digital Ammter 230V, AC AuX Supply -01 Nos (Secure) | ||||||||||
| 1.09(g) Amp selector Switch 6A (61325)-01 (L &K) | ||||||||||
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
26 Mar 2026, 6:00 pmClosed
GE NORTH PUNE
Garrison Engineer North General Cariappa Marg Camp Pune - 411001
GE (N) P/TOKEN- 95 OF 2025-2026 REPAIR MAINT OF DG SETS AND CERTAIN E/M EQUIPMENTS AND LT INFRASTRUCTURE, LT FEEDER PILLAR BOXES IN GHORPADI AREA AND NEAR MILKHA SINGH COMPLEX UNDER AOR OF GE (N) PUNE
2026_MES_754328_1
GE (N) P/TOKEN- 95 OF 2025-2026
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹98,000
Yes
2 Apr 2026
26 Feb 2026
28 Mar 2026
26 Feb 2026
26 Mar 2026
12 Mar 2026
27 Feb 2026 - 5 Mar 2026
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI (TTA Panels complying to IEC 61439) approved double door floor mounted outdoor type, as per IP-55 grade,Single front, fixed, Compartmentalised, floor mounted, cable entry, paint shade RAL 7032 Siemens Grey made out of CRCA sheet 3.15 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including:
Incoming
(a) 630A, 4P, 50kA, Manual Drawout, ACB with Universal Termination, Micropro3- 3.1 Release with LSING Protection, Type: Winmaster with breaking capacity 50 KA at 415 volts Ics=100% Icu With on/off/trip indicator -01 No. (CAT No WX306N4P1MDOA (S) of C &S)
(b) Copper bus bar of suitable size 1000 Amps TPN -01 Set
(e) Amber, Green , Yellow,blue Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC (C &S RCB7-IVL75, RCB7-IVL73,RCB7-IVL78,RCB7-IVL76)-01 Nos Each
Red Indicating lamp with integral LED metallic suaitable for operating at 110V, 240V, 220V, 48V, 24V, 12V AC/DC (C &S RCB7-IVL74)02 Nos
(f) 3 PH Digital Ammter 230V, AC AuX Supply -01 Nos (Secure)
(h) Digital Voltmeter 3 PH - 01 Nos(secure)
(j) Wire Wound CT 600/5A, CL 1.0, 5VA-03 Nos
(k) CT Short Link-04 Nos (Connectwel)
(l) 6 A SP 'c' MCB (BB10060C)-08 Nos
Outgoing
(a) MCCB 3 pole, 250 Amp, (DN1-250C) (CM90638OOPO) (01 Nos) adjustable type Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN1 (CM98041OOOO), Spreaders, DN2-3 Pole (set of 06)-01 Nos), Auxiliary1 C/O+TAC 1 C/O DN0, DN1-Right (CM97890OOO)-01 Nos Phase Barrier - 01 Nos. 6A SP 'C' MCB-02 Nos (LK)
(b) MCCB 3 pole, 100 Amp (04 Nos), adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0-04 Nos (CM9786OOOO) , Spreaders Terminal DN0-03 Pole (set of 6)-04, Phase Barrier - 04 Nos, Auxiliary 1 c/o+TAC 1 c/o DN0, DN1-Right-04 Nos (CM97890OOOO)-04Nos, RGO indication Lamp-04 Nos, 6A SP 'C' MCB-08 Nos
(c) MCCB 3 pole, 63 Amp (CM91612OOHO)-04 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu- With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0 (CM97896OOO)-04 Nos, Spreaders Terminal DN0-3 Pole (et of 6)-04 Nos, Phase Barrier 04 Nos, RGO Indication LAmp-01 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel ((TTA Panels complying to IEC 61439)) CPRI approved double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Ghorpadi Pump house No. 01 ).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 250 Amp (01 Nos), adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN2 (CM99830OOOO)-01 Nos, Spreaders Terminal DN1, DN2-04 Pole (set of 8) (CM92007OOOO)-01 Nos), Phase Barrier -01 Nos, Auxiliary 1 C/o+TAC 1 C/O DN2, DN3B, DN3, DN4-Right 01 (nos) -01 Nos, 250/5 DIN Type Cl-1 VA-5CT-03 Nos
(b) Copper bus bar of suitable size 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B &R-G-O)) complete - 01 Set
Outgoing
(a) MCCB 3 pole, 100 Amp (DN0-100C) (CM91162OOKO)-01 Nos,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0 (CM97896OOOO)-01 Nos, Spreaders Terminal DN0-3 Pole (Set of 6) (CM97785OOO)-01 Nos, Phase Barrier- 01 Nos, Auxiliary 1 c/o +TAC 1 C/O DN0, Dn1-Right-01 (R-G-O Indication Lamp-01 Nos), 6A SP 'c' MCB -LK BB10060C-02 Nos
(b) MCCB 3 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 18 KA (DU100D) (04 Nos) CM90517OOHO)at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle, Spreaders Terminal DU100D/DU100H-3 Pole (set of 6)-04 Nos (CM97785OOO), Phase Barrier- 04 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI ((TTA Panels complying to IEC 61439)) approved double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Copper bus bar 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Vishwamithra Marg Near Main Gate ).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp (DN3B-400D) (CM98403OORO of L &K) 01 Nos, adjustable type Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN3B, DN3-01 Nos, Spreaders terminal DN3B/DN3-400- 4 Pole (set of 08)-01 Nos (ST98066OOOO), Phase Barrier01 No, Auxiliary 1 c/o +TAC1 C/O DN2, DN3, DN4,-Right
(b) Copper bus bar of suitable size 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B &R-G-O) complete with bakalite fuse fitting - 01 Set
(f) 400/5 Ring Type Cl-1 VA-15 CT-03 Nos
(g) 6A SP'C' MCB (Lk) (BB10060C)-08 Nos
Outgoing
(a) MCCB 3P, 200 Amp (DN1-250C) (CM90638OONO)-03 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle Dn1--03 Nos, Spreaders terminal DN1, DN2-3 Pole (set of 6) (ST98053OOOOO)-03 nos), Phase Barrier 03 Nos, Auxiliary 1 c/o +TAC1 C/O DN2, DN3, DN4,-Right, R-G-O indication Lamp-03 nos, 6A SP'C' MCB (LK)-06 nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
(d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz - 01 No.
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved ((TTA Panels complying to IEC 61439)) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 300 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Near bldg No T7 Ghorpadi )
Incoming
(a) MCCB, 4 Pole, 415 Volts, 200 Amp (CM90642OONO)-01 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN2 (CM99830OOOO)-01 Nos, Spreaders terminal DN1, DN2-4 Pole (Set of 8) (CM92007OOOO)-01 Nos, Phase Barrier-02 No, Auxiliary 1 c/o +TAC1 C/O DN2, DN3, DN4,-Right (CM99804OOOO)-01 Nos
(b) Copper bus bar of suitable size 300 Amp TPN -01 Set
(e) Indicator lamp LED type (R,Y,B &R-G-O) complete with bakalite fuse fitting - 01 Set
(f) 200/5 DIN TypeCl-1 VA-5 CT -03 Nos
(g) 6A SP 'C' MCB-LK (BB10060C)-08 Nos
Outgoing
(a) MCCB 3 pole, 100 Amp (DN0-100C) (CM91612OOKO)-02 Nos , adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0 (CM97896OOO)-02 Nos, Spreaders terminal DN0-3 Pole (set of 6) (CM97785OOOO)-02 Nos, Phase Barrier- 02 Nos, Auxiliary 1 c/o +TAC1 C/O DN0, DN1-Right (CM97890OOOO)-02 Nos, R-G-O Indication Lamp-02 Nos, 6A SP'C' MCB (BB10060C)-04 Nos
(e) MCB DP 32 Amps - 02 Nos
(b) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved ((TTA Panels complying to IEC 61439)) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg NP-09 Ghorpadi)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp (DN3B-400D), (CM98403OOQO)-02 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN3B, DN3 (CM99861OOOO)-02 Nos, Spreaders Terminal DN3B/DN3-400-4 Pole (set of 8)-02 Nos, Phase Barrier-02 No Auxiliary 1 c/o +TAC1 C/O DN2, DN3B, DN3, DN4-Right -04 Nos (CM99804OOOO)
(b) Copper bus bar of suitable size 500 Amps, TPN -01 Set
(e) Indicator lamp LED type (R,Y,B &R-G-O) complete with bakalite fuse fitting - 01 Set
(f) 6A SP 'C' MCB-LK (BB10060C)-08 Nos
Outgoing
(a) MCCB 3 pole, 63 Amp (DN0-100C) (04 Nos) (CM9161200HO of LK), adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0 (CM97896OOOO)-04 Nos, Spreaders terminal DN0-3 Pole (set of 6) (CM97785OOOO)-04 Nos, Phase Barrier 04 Nos, Auxiliary 1 c/o +TAC1 C/O DN0, DN1-Right -04 Nos (CM97890OOOO), R-G-O Indication Lamp-04 Nos, 6A SP 'C' MCB-LK (BB10060C)-08 Nos, 63A TP 'C' MCB-L&K- (BB30630C-02 Nos)
(b) MCB TP 63 Amp, 16 KA, 415 V AC - 02 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved ((TTA Panels complying to IEC 61439)) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No. 148 Ghorpadi)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp (CM98403OOQO)-01 Nos , adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN3B, DN3 (CM99861OOOO)-01, Spreaders terminals DN3B/DN3-400-4 Pole (Set of 8) (ST98066OOOO), Phase Barrier02 No
(b) Copper bus bar of suitable size 500 Amps, TPN -01 Set
(e) Indicator lamp LED type (R,Y,B & R-G-O) complete with bakalite fuse fitting - 01 Set
(f) 300/5 DIN Type Cl-1 VA-5CT-03 Nos
(g) 6A SP 'C' MCB -L &K -08 nos (BB10060C)
Outgoing
(a) MCCB 3P, 63 Amp,(04 Nos) (CM91612OOHO) adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle, Spreaders terminal DN0-3 Pole (Set of 6)-04 Nos (CM97785OOOO), Phase Barrier-04 Nos,Auxiliary 1 c/o +TAC1 C/O DN0, DN1-Right -04 Nos (CM97890OOOO), 6AMCB SP 'C' (LK-BB10060C)-08 Nos, 63A TP 'C' MCB (LK BB30630C)-03 Nos
(b) MCB TP 63 Amp, 16 KA, 415 V AC - 03 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved double ((TTA Panels complying to IEC 61439)) door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with Copper bus bar 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No. E2 Ghorpadi).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp (01 Nos) (CM98403OOQO), adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN3B, DN3 (CM99861OOOO)-01 Nos, Spreaders terminal DN3B/DN3-400-4 Pole (set of 08)-01 Nos (ST98066OOOO), Phase Barrier 02 Nos, Auxiliary 1 c/o +TAC1 C/O DN2, DN3B, DN3, DN4-Right -01 Nos (CM99804OOOO)
(b) Copper bus bar of suitable size 500 Amps, TPN -01 Set
(e) Indicator lamp LED type (R,Y,B & R-G-O) complete with bakalite fuse fitting - 01 Set
(f) 300/5 DIN Type CL-1 VA-5 CT -03 Nos
(g) 6A SP 'C' MCB -LK (08 Nos)
Outgoing
(a) MCCB 3P, 63 Amp (05 Nos), adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0-05 Nos, Spreaders terminal DN0-3 Pole (set of 6) -05 Nos (CM97785OOOO) , Phase Barrier- 05 Nos, Auxiliary 1 c/o +TAC1 C/O DN0, DN1, Right -01 Nos (CM97890OOOO)-05 Nos
(b) MCB TP 40 Amp, 16 KA, 415 V AC - 02 Nos
(b) MCB 6A 'C' Amp- 10 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved (TTA Panels complying to IEC 61439) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body and inner compartments/ Protective door of 2.00 mm of suitable size with aluminium bus ba 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No. 157 Ghorpadi).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp (CM98403OORO) (01 Nos), adjustable type Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN3B, DN3, Spreaders Terminal DN3B/DN3-400 -4 Pole (set of 8) (ST98066OOOO)-01 Nos, Phase Barrier-01 No (Make ABB,L&T,LEGRAND)
(b) Copper bus bar of suitable size 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B & R-G-O) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 250 Amp,(01 Nos) (CM90638OOPO) adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN1-01 Nos, Spreaders terminal DN1, DN2-3 Pole (set of 6) (ST98053OOOOO)-01 Nos, Phase Barrier-01 Nos, Auxiliary 1 c/o +TAC1 C/O DN0, DN2-Right -01 Nos (CM97890OOOO), 6A SP 'C' MCB-02 Nos (BB10060C)
(b) MCCB 3P, 63 Amp (04 Nos)(CM91612OOHO) adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN1 (CM98041OOOO)-04Nos, Spreaders terminal DN0-3 Pole(set of 6)-04 Nos, Phase Barrier 04 Nos,6A SP 'C' MCB (BB10060C)-08 Nos, R-G-O Indication Lamp-04 Nos, Auxiliary 1 c/o +TAC1 C/O DN0, DN1-Right -04 Nos (CM97890OOOO)
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI approved d (TTA Panels complying to IEC 61439) double door floor mounted outdoor type, as per IP-55 grade, made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Copper bus bar 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (752 TPT Coy).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 160Amp, (CM90642OOMO)-01 Nos adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN1 (CM98041OOOO)-01 Nos, Spreaders terminal DN1, DN2, -04 Pole (set of 8)-(CM92007OOOO)-01 Nos, Phase Barrier01 No, Auxiliary 1 c/o +TAC1 C/O DN0, DN1-Right -01 Nos
(b) Copper bus bar of suitable size 250 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B & R-G-O) complete with bakalite fuse fitting - 01 Set
(f) 6A SP 'C' MCB (CM91612OOKO)-01 Nos
(f) 150/5 DIN Type CL-1 VA 5CT-03 Nos
Outgoing
(a) MCCB 3P, 100 Amp (CM91612OOKO)-01 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle Extended DN0-01 Nos, Spreaders Terminal DN0-3 Pole (set of 06) (CM97785OOOO)-01 Nos , Phase Barrier 01 Nos, Auxiliary 1 C/o+TAC1 c/o DN0, Dn1-Right (CM97890OOOO)-01 Nos, R-GO-Indication Lamp-01 Nos, 6A SP 'C' MCB LK (BB10060C)-02 Nos
(b) MCCB 3P, 63 Amp (DN0-100C)(CM91612OOHO)-02 Nos, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 With on/off/trip indicator ,Mcb.and Standard Extended Rotary Handle DN0-02 Nos, Spreaders Terminal DN0-3 Pole (set of 6) (CM97785OOOO)-02 Nos, Phase Barrier 02 Nos,Auxiliary 1 C/o+TAC1 c/o DN0, Dn1-Right (CM97890OOOO)-02 Nos, R-G-O Indication Lamp-02 Nos,6A SP 'C' MCB-04Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 240 Sq mm. complete all as specified and as directed. Note : Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates.
-ditto- all as per item No 10 above but 3.5 core 185 sqmm
'-ditto- all as per item No 10 above but 3.5 core 120 sqmm
'-ditto- all as per item No 10 above but 3.5 core 95 sqmm
'-ditto- all as per item No 10 above but 3.5 core 70 sqmm
'-ditto- all as per item No 10 above but 3.5 core 50 sqmm
'-ditto- all as per item No 10 above but 4 core 35 sqmm
'-ditto- all as per item No 10 above but 4 core 25 sqmm
M&L for Boring of holes under road, pavement,hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 50mm bore for protection of UG cables complete all as specified and as directed.
All as per Item No. 19 above but 80 mm
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and laying 40mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 50mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 63mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 75mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
M&L for Maintenance Free Grounding Solution set earthing comprising of High tensile low carbon steel rod of 3 Mts length & 17.2 mm dia with 250micron ( average ) molecularly bonded copper on the outer surface along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. Back-fill compound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. Make: JEF Technology or equivalant in True power earthings Note:- a) Test certificate from the OEM has to be produced by the contractor for the material used in earthing. b) If the test result obtain from earthing is not less than 3 Ohms then earthing has to be done again at no extra cost. c) Rates for Excavation and earthwork in any type of soil/strata, testing on completion, copper clad steel conductor wire 4 mm dia and 15 mm dia protection pipe upto 7.5 mtr from Electrode is deemed to be included in rate quoted.)
S&F Earth conitnuity Copper clad steel conductor or main earthing lead fixed to wall on batten or reccess or chases or burried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc as required 8 mm dia after taking down the old one any type.
Note : 1. Performance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
BOQ_844895.xls
BOQ • 10.95 MB
tenderdocuments95.pdf
Tender Documents • 0.84 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .