REPAIR/MAINTENANCE OF MAIN RECEIVING SUB STATION AND 11 KV SUB STATION EQUIPMENT AND CONNECTED WORKS IN AGE E/M EXT (ELECT) UNDER GE E/M LUCKNOW
2022_MES_527952_1
CWE/LKO/EM/T-27 OF 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
LUCKNOW
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE E/M LUCKNOW
₹60,000
Yes
26 Jul 2022
2 Jun 2022
30 Jun 2022
2 Jun 2022
28 Jun 2022
16 Jun 2022
Amount
M&L for GOD (horizontal type) suitable for oudoor type three phase double break,centre rotating type suitable manual operation 3 moving contact of all isolator (roatate through 90 degree from their fully collosed position to fully open position so that the break is distinct and clearly visible from ground lever conforing to IS 9921/IEC-62271-102, phase, rated nominal/ maximum rated voltage 33/36 KV, rated current 1250 Amp isolator as per existing make and mode incl taking down old one etc complte as specified and directed.
M&L for polymeric lightining arrester(as per existing make/model/ capacity to be fixed on existing structure) complete with all fitting, transmission class, discharge capacity 400 Amp suitable for 33000 volts incl taking down old one etc complete as specified and directed.
M&L for single phase paper impregnate oil immersed current transformer for different phase in comman tank equipped with wather proof bushing for out door type suitable for earth fault,over current, differenceal relay and other relay as per existing make/model/type confiring IS:2705-1992 for CT,IS5621-1992 for insulator/busing and IS335-1983 for oil suitable for existing make and model of ratio 100/50/5-5A,Class 0.5/5S, HSV -36KV, I.L 36/70/170(P)KV, S.T.C 20.1 KA for 3 second , burdden 30 VA incl taking down old one etc complete as specified and directed.
M&L for three phase four wire 33/110V oil cooled outdoor type PT conforming to IS 3156/1992 nominal/highest system voltage 33/36 Kvimpulse withstand voltage 170 KVP (primery 70 KV , 50 HZ rate out put burden 30 VA per phase , class accuracy 0.5,winding connection star/delta ,rated voltage factor/time 1.2 contineuse and 1.9 for 30 second etc as per existing make and mode including taking down old one coplete as specified and directed.
Supply and fixing in repairs 2U hardware clamp straight or angle to clamping the jumper & disc insulators uses with suitable GI nut, bolt, and washers as per existing size complete as specified and directed
All as per item No 5 but sub station connector of Aluminum straight tee tubing main to tubing tap with suitable sizes of GI nut & bolts as per existing size etc complete as specified and directed.
All as per item No 5 but sub station connectors Aluminum horizontal bus support tube to insulators with GI nut & bolts as per existing size complete as specified and directed.
All as per item No 5 but Aluminum straight tee tubing main to cable/ conductor tap as per existing size and capacit complete as specified and directed.
Supply and fixing in repair aluminum binding wire 14 SWG suitable for binding the jumpers and other accessories of 4 pole structure complete.
Supply and fixing in repairs GI nuts ,bolts as washer as per sample kept in office complete all as specified and directed.
Disconnecting and taking down unserviceable single core cable from existing gantary/ 33 KV yard and supply,fixing and testing PVC insulated seathted unarmoured single core copper conductor cable of size 95 sqmm incl new copper lugs lugs,nut,bolt and washer etc complete as directed
M&L for bore earthing by manual boring dwon through the ground level 150 mm bore with boring tools,complressor and pumping water continuosly including insertion of copper strip 32x6mm passing through & including GI pipe 50 mm bore 30 meter long lowered up to water level and connected/brazed at bottom to 32x6mm copper strip cone at periphery of pipe end inside borehole of suitable shape/size so that its bottom most end remain submerged in water always complete incl connecting 600 mm long pice of GI pipe at top for watering purpose in event of need by inserting tee 50x50x50 mm tee incl upcomming 50 mm bore strip protection pipe duly pluged at top complete all as per Sketch-P kept in office of the AGE E/M Ext (Elect) sub division and specified and directed by Engr-in-charge. Note- The contractor will be bound to redo the earthing unit result of earth resistance is achieve below 1.0 Ohm. Earth test result taken in presence of Engr-in-charge for three consecutive days after completing the job shall be submitted by contractor to Engr-in-charge before incl in work done statememnt of RAR.
Supply & fix in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing as required 32x6mm copper strip complete as specified and directed
All as per item No 13 above but 20x3mm
Supply and laying in replacement GI Pipe 40 mm bore medium grade ISI marked laying in trneches/fixed on wall with help of suitable size ms clamp and nut bolts incl taking down old one etc complete as specified and directed.
All as per item No 15 but 25 mm dia
All as per item No 15 but 20 mm dia
All as per item No 15 but 15mm dia
S&F in repair PVC bib tap 15 mm borestandard for PTMT any colour high pressure screwed for iron pipe and fixed etc complete as specified and directed incl taking down old one
M&L for making earthing high conductive, non corosive maintenance free, non fluctuation of ohmic value 80 mmX3000mm (inner strip-3000x50x6mm, connection terminal 100x50x6mm, therminal hole 16mm, Inner filling CCM lectrode pipe-B class) GI pipe in pipe filled with super conductive crysteline with earth plus 50 kg (2x25 Kg bag) containing mixture of graphite,activated carbon,sulphat,silica, alumina iron oxide,ctitanium oxide,sodium oxide,zing oxide,etc) back fill compound should be ROHS including heavy duty polymer Earth pit chember with cover GI strip 32x6 mm which desire complete all accesories for design modification to achieve the earth terminal rod resistance value below 1 ohm incl taking down old one complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repair pvc insulated single core ISI marked sheathed copper wire of size 70 sqmm incl copper lugs,nut,bolt and washer etc complete as specified and directed
Removing the excavated material (mix earth/aggregate) from switch yard boundary and deposited approx 3 KM away as directed place etc complete.
M&L for cutting the tree branches any type/shape/thick any height with the help of hydra, electrical cutting machine/manual of over the building/near the building /srounding the installation/equipement (RMU) etc complete the as directed by Engr-in-charge. Note- all branches of one tree measured as one job
M&L for preperation old steel surface(fencing) any description over 10 cm in width or girth not other wise decribed and painting with one coat of synthetic enamelled paind etc complete as directed
S&F in repair galvanised 2 stranded steel barbed wire with 2.24mm dia barbed with 2 mm dia barbs at 75 mm spacing and straiing and fixing to any type of standard rails strain-ing bolts, incl securing or tying at crossing with and provision of galvanised mild steel wire staples or steel pins etc as directed (each line wire to be measured etc as directed
M&L for Cleaning, servicing and testing various type equipment 33/11 KV equipment in switch yard and other connected works etc complete all as specified and directed for the following:-
(a) line isolator, 33 KV (Horizontal type) :- Servicing of line isolator (Horizontal break outdoor type) including cleaning of contact (knife) by CTC liquid proper oiling greasing on contacts & moving rod / handle for proper function of moveable rod for smooth ON / OFF position and checking,tightining the incoming and outgoing connection (terminal lugs to be replaced if required as per existing size with GI nut bolts,washer) and testing with following (i) Meggar testing between phase to phase & phase to earth shall be carried out etc complete as specified and directed.
(b) HT Potential Transformer (33 KV / 110 Volt) :- Cleaning of bushing and terminal of HT potential transformer 33000 / 110 volts (outdoor type) by CTC liquid and checking of oil level incl rectify the any leakage and proper connection checking and testing with following :- (i) Meggar testing between phase to phase& phase to earth (ii) Checking output voltage (iii) Testing the oil dielectric strength (BD test)
(c) HT Vacuum Circuit Breaker (VCB) 33 KV: Cleaning & servicing of HT 33 KV vacuum circuit breaker (VCB) 400 Amp, 3 phase, 13.1 KA outdoor type, checking of each moving parts, spring, charging system, closing & trip coil assembly and proper oiling, greasing and proper adjustment of trip bars, closing bar complete with the following testing:- (i) ON/OFF testing in local and remote position. (ii )Spring charge system testing shall be carried out. (iii) Tripping test in over and earth fault position by external current injecting Kit on Primary Secondary side. (iv) Meggar testing between phase to phase and phase to earth in ON / OFF position both.
(d) HT 33 KV Current Transformer (CT): Cleaning of bushing and terminal by CTC solution of CT rating 100 / 5 + 5 + 1 Amp rating, 33 KV and checking of oil level , rectify the leakage if any and testing the oil strength (BD test) and proper connection checking and testing with following :- (i) Meggar testing between phase to phase& phase to earth
(f) Transformer 33 / 11 KV, 5 MVA :- Cleaning of power transformer 33 /11 KV, 5 MVA, outdoor type externally including all accessories (such as conservator tank, marshaling box, bushings, bucholz relay Radiator, bushings oil level indicator,rectyfy the leakage if any) complete and checking the incoming and outgoing terminal connection complete with the following testing :- (i) Transformer oil dielectric strength (BD voltage) test. (ii) Buccholz relay Alarm & trip testing. (iii) Oil temperature Alarm & trip testing. (iv) Winding temperature Alarm & trip testing. (v) Meggar testing between HV to earth. (vi) Meggar testing between LV to earth. (vii) Meggar testing between HV to LV . (viii) Earth resistance test of transformer neutral. (ix) Earth resistance test for body earthing. (x) Replacement the all packing in marshalling box (if required)
(g) Transformer 33/ 0.433 KV, 25 KVA (Station Transformer) :- Cleaning of station transformer (outdoor type) externally including all accessories and checking of all incoming & outgoing connection and rectify the leakave if any incl with the following testing :- (i) Transformer oil dielectric strength (BD) test. (ii) Meggar testing between HV to earth. (iii) Meggar testing between LV to earth. (iv) Meggar testing between HV to LV . (v) Earth resistance test of transformer neutral. (vi) Earth resistance test for body earthing.
(h) D.O. Fuse: Cleaning of HT insulators & checking the incoming & outgoing joint connection and testing with the following :- (i) Meggar testing between phase to phase& phase to earth.
M&L for painting of 33 /11 KV Old MRS switch yard MS structure with one coats of asian make aluminum paint after cleaning and making good surface for panting of the following structure:- (a) Bus bar Gantry:- Painting of busbarGantry of MS channel (I Section) size 150 mm x 75 mm x 5 mtr long - 12 Nos (b) Lightening arresters (LA):- Painting of lightening Arresters of MS channel (C-section) of size 100 mm x 50 mm x 3.0 mtr long -02 Nos with MS Angle iron 50x 50 x 2.5 mtr long -04 Nos complete - 03 Job (c) Line isolator (LI):- Painting Line isolator of MS channel ( C-section) of size (125 mm x 50mm x 3.00 mtr long -04 Nos) and ( 100 mm x 50 mm x 1.00 mtr -02 Nos) with MS flat bracing (50mm x 50mm x 0.30 mtr -6 Nos) and MS Angle iron ( 50 mm x 50 mm x 2.5 mtr long-02 Nos) complete -07 Job (d) Horn Gap fuse:- All as per item No 12 (C) here in before. Qty - 04 Job Contd.....
(e) VCB / CT / PT stand:- Painting of CT PT VCB structure made out of MS channel ( C-section) of size ( 100 mm x 50 mm x 2.30 mtr long- 04 Nos) and ( 100 mm x 50 mm x 0.80 mtr long- 04 Nos) and ( 100 mm x 50 mm x 1.90 mtr long- 04 Nos) and Angle iron of size ( 50 mm x 50 mm x 1.10 mtr -04 No) complete long- 04 Nos), ( 50 mm x 50 mm x 0.70 mtr long- 06 Nos) and (50 mm x 50mm x 0.25 Mtr long - 05 Nos) complete -03 Job (f) Pin insulator supporting structure(Station Transformer):- Painting of structure made out of MS channel (C- section) of size (100mm x 50mm x 3.00 mtr long- 02 Nos) with Angle iron of size (50mm x 50 mm 2.50 mtr long - 04 Nos) complete -01 Job.
All as per item No. 27 above but station transformer 33 / 0.433 KV, 25 KVA rating.
All as per item No 27 above but 5 MVA Transformer 33/11 KV rating
All as per item No. 27 above but of size approx (outdoor type), 400 Amps rating size of VCB 700 mm wide x 500 mm deep x 900 mm height including painting of CT's & PT's all as directed by EIC.
M and L for opening the top cover of current transformer and Potencial tranformer of out door VCBs 33 KV and servicing of fixed and moving contacts, repair and replacement of defective components incl replacment of defective parts of panel such as lamp indicators, calibration of digital meters, over load protection relay, time delay relay / earth fault relay, charging spring etc. Cleaning the fixed and moving contact inside the VCBs properly, servicing and greasing all moveable mechanism, replacement of defective fuses, wiring and reassembling and testing complete all as per the direction of Engineer-in-Charge.
S&F in repair breather unit with superior quality blue colour silica jelly and fill up the oil maintain the exact level as per existing size and capacity suitable for transformer of cap 5 MVA, 33/11 KV complete all as specified and directed.
All as per item No 32 above but for 33 / 0.433 KV, 25 KVA (Station Transformer)
Supply & Fixing in repair HV bushing suitable for 33KV 5 MVA transformers as per existing size/ make /model complete all as specified.
Supply and fixing in repasir LV bushing suitable for 33 KV 5 MVA transformer as per existing size/make/model for transformers complete all as specified.
Supply & fix in repair HV spindles (metal Part) of brass with nuts and washers as per existing size suitable for 5 MVA 33 KV Transformer complete all as specified
Supply & fixing in repair LV spindles (metal Part) of brass with nuts and washers as pe existing size suitabe for 5 MVA 33 KV transformer complete all as specified
Supply and fixing in repair oil level indicator of 5 MVA Transformer (0-100) as per existing make/model/type/capacity complete all as specified and directed.
Supply & topping up transformer oil low viscosity, dielectric strength above 50 KV confirming to IS-335 complete for filling / topping up in HT CT/PT Transformers complete all as specified and directed.
M&L centrifuging of transformer oil 33/11 KVA 5 MVA power transformers including filter action using automatic centrifuging machine to achieve minimum 35 to 40 KV breaking capacity at 4 mm gap by absorbing and abolishing all sludge particle for use all as specified and directed.
Supply and fixing in repairs oil temperature gauge with trip and alarm contacts as per existing make/size/capacity suitable for 5 MVA TRF complete all as specified and directed.
Supply and fixing in repairs winding temperature guage with trip and alarm contacts as per existing make/size/capacity suitable for 5 MVA TRF complete all as specified and directed.
Hiring of cable fault detector, to detect exact position of fault for XLPE /PVC HT cable, 11000 Volts/3300 volt grade heavy duty aluminum conductor of any size any length in switch yard including disconnection,jointing & testing complete as directed by EIC
Dismantling of floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises etc complete as directed.
M&L for cement concrete tiles Renewing tiles in patches, area n exc 5 sq.m. including removing and cleaning old tiles, preparing beds and laying or setting, jointing and pointing new or old tiles complete
M&L for 80mm thick PCC interlocking tiles, rubber moulded using grey cement and pigment of size and shape as approved, including 50mm thick bed with PCC (1:3:6) type C1 with 20 mm graded aggregate and including layer of dry sand not less than 40 mm thick, interstices filed in floors/pathway including locking the tiles on all four sides with PCC complete all as specified and directed.
M&L for RCC cable duct cover with 8mm dia ms bar as required at site incl 12 mm dia ms bar moveable handle both side of cable cover etc as specified and directed by Engr-in-charge
M&L for aluminum conductor steel reinforced (ACSR) on pole, stringing properly on insulators and binding with aluminum binding wire, jumpers etc complete for any size (Ferret,Weasel ,Squirel) of conductor incl taking down old one complete. Note : - Measurement & Payment shall be made by measuring horizontal distance between centre of two adjacent pole and adding 3% extra for sag, joints and jumper etc.
Supply & fix in repair insulator pin type porcelain, vitreous, white, brown or green 150 mm height and 150 mm dia including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nuts for conductor working pressure 33000 Volts grade complete.
Supply & fix in repair insulator disc type porcelain, vitreous, white, brown or green including galvanised mild steel straps, washers,insulator bolts, washers and nuts 150 mm height and 150 mm dia including working pressure 33000 Volts grade complete.
M&L for servicing / Cleaning of solar street light PV module, checking the all electric loose connection, replacement of terminal, distilled water of battery & checking of mechanical/electric system for proper functioning of solar lights at various places complete all as specified and directed.
M&L for servicing / Cleaning of inverter/ups checking the all electric loose connection, replacement of terminal, distilled water of battery, wiring system & checking of mechanical/electric system for proper functioning of inverter at various places complete all as specified and directed.
Cable joint kit for 33 KV (earthed) grade cable for straight through heatshrink type joint complete with jointing material and accessories sutable for XLPE armoured aluminium conductor cable of size 185-240 sqmm 3 core incl dicconnection & connection cable,jointing,testing,earth works any type of soil etc complete as specified and directed.
Cable joint kit for 11 KV (earthed) grade cable for straight through heatshrink type joint complete with jointing material and accessories sutable for XLPE armoured aluminium conductor cable of size 120-185 sqmm 3 core incl disconnection ,connecting of cable,joinnting,testing and earth works in any type of soil etc complete as specified and directed.
Cable joint kit for 33 KV (earthed) grade cable for out door termination heatshrink type joint with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 185-240 sqmm incl disconnecntion / connection, jointing and testing complete as specified and directed.
Cable joint kit for 11 KV (earthed) grade cable for out door termination kit heatshrink type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 120-185 sqmm 3 core incl diconnection,connection,jointing and testing of cable etc complette as specified and directed.
Cable joint kit for 33 KV (earthed) grade cable for end termination indoor heatshrink type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 185-240 sqmm 3 core incl connection,disconnection,jointing and testing complete as specified and directed.
Cable joint kit for 11 KV (earthed) grade cable for end termination indoor heatshrink type joint complete with jointing material and accessories suitable XLPE armoured aluminium conductor cable of size 120-185 sqmm 3 core incl disconnection,connection ,jointing and testing etc complte as spcified and directed.
Disconnecting the all electrical connection from battery bank and taking out unserviceable part & supply and fix new parts as required incl serviceing, connecting ,tighting,greasing,wiring & testing as required voltage including cleaning and painting with one coat of synthetic enamelled paint complete as directed .Note - if any parts not included in the specification of works, contractor will provide own cost and deem to quoated cost if requied for functioning of equipment .
(a) Supply only transformer suitable for 110/30 volts
(b) Supply only voltmeter as per existing size and capcity
(c ) Supply only Ammeter as per existing size and capacity
(d) Supply only slector switch as per existing make and capacity
(e) Supply only push button as per existing size amd make
(f) Supply only 2 volt 100 AH maintenance free battery as per existing make/model/capacity etc
Supply and fix in repair battery charger suitable for 110 volt as per existing make/model/capacity etc complete as specified and directed
S&F in repair 08 window annouciator 30 V DC operated and with buchholz trip, winding temp high trip, oil temp high trip, buchholz alarm, winding temp high alarm, oil temp high alarm spare complete all as per existing make.model/size etc complte as directe
Supply and fixing in repair hooter for announciator panel as per existing make/model/capacity complete all as specified and directed.
Supply and fix in repairs relay suitable for earth,over current,differecncial and bchholz Alarm, Winding & Oil temp alarm suitable for 5 MVA 33/11 KV Transformer as per existing make/model etc complete all as specified and directed.
Supply and fixing in repair master trip relay as per existing make/model/capacity complete all as specified and directed.
Supply and fix in repairs numerical earth fault,over current relay suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs remote switch suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs push button suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs heater switch suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs multifuction digital metetr suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs cut out suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs DC switch suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs AC switch suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs thermostate suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
Supply and fix in repairs TNC switch suitable for 11 KV HT panel as per existing make/model earth etc complete all as specified and directed.
S&F Ammeter digital type 100A/5A or 60A/5A CTR of 150mm x 150mm including taking out of old unserviceable ammeter complete all as specified and directed.
S&F Voltmeter digital type 15 KV of 110/30 V PTR. Size 150mm x 150mm including taking out old unserviceable voltmeter complete all as specified and directed.
S&F indicator light (LED type) suitable to operate on 30 volts DC/110 V AC having two covers red/green/blue for HT VCB panel including taking down old complete all as specified and directed.
Supply, fixing and testing in repairs Power Pack units with maintenance free solid batteries in sheet metal enclosure with arrangements for mounting on the existing 11 KV VCBs panels with nuts and bolts and capable of providing 30 V DC current to the VCBs during power failure for a continuous period of not less than 12 hours, for functioning of relays, charging motor and other parameters complete all as specified and directed.
Supply, fixing and testing in repairs Power Pack units with maintenance free solid batteries in sheet metal enclosure with arrangements for mounting on the existing 11 KV VCBs panels with nuts and bolts and capable of providing 110V DC current to the VCBs during power failure for a continuous period of not less than 12 hours, for functioning of relays, charging motor and other parameters complete all as specified and directed.
S & F in repair PVC insulated seathed unarmoured 4 core copper conductor cable of size 2.5 sqmm complete all as specified and directed.
S & F in repair PVC insulated 4 core copper conductor cable of size 4 sqmm complete all as specified and directed.
Supply and fixing fire retardant electric insulation synthetic mat INSULATICA 2000" for 33 KV 3.0 mm thick +10% conforming to BIS DOC No ETD -02 (5231) P dt 2003. meeting requirement of IS 3043, IS: 5216 (Part 1,2,3) IS : 8437 and IEC 479 pub-1 IEC 61111 & 61112 tested for brake down strength tensile /elongation ageing properties. Insulation resistance, affects of acid , alkaline, Diesel & transformer oil, leakage current test fire test etc. having min width of 1000m + 20 mm complete as required suitable and using adhesive and allied chemical and scaling of all joints and border ends and fixing decorative taps the installed sheet complete all as specified and directed by Engineer-in-Charge.
Supply and fix epoxy cast resin current transformer as per existing make/model/capacity suitable for 11 KV panel etc complete incl taking down old one
Supply and fix epoxy cast resin potencial transformer as per existing make/model/capacity suitable for 11 KV panel etc complete incl taking down old one
Servicing and calibration to 11KV HT VCB/(SF-6 type) complete with the following:- (a) Taking out 11KV HT VCB/(SF6 type) of 400/800 Amps rating trolley from HT Panel after switching off electric supply . Checking the mechanical system of equipment and cleaning & servicing the fixed/ moving contact & blowing out dust and applying the proper lubrication/ greasing and reassembling the VCB/(SF6 type) and testing complete after switching one the VCB as directed. Make of VCB (ABB/Schnieder/Crompton) (b) Caliberation of relay any type/make/model on HT panel (2 Nos over current & 01 No earth fault relay) as per load or as directed by Engr-in-charge and cleaning cleaning the contact (NO+NC) by CTC solution and adjust the contact and testing the relay by testing kit etc complete all as specified and directed. (c) Opening the HT panel bus bar and cleaning the bus bar and closed the whole by putty and other material in all respect etc complete as specified and directed. Note for (a) & (c):- (i) Replacing new items shall be measured and paid separately as supply only. (ii) Contractor shall submit the connected test report to Engr-in-charge
(a) Make of ABB model No Vlnd (as per existing model/type) 11 KV
(i) Supply only Tulip contac assy 8 finger 630/800 Amp
(ii) Supply only Tripping spring assy
(iii) Supply only Pole 630 Amp
(iv) Supply only Insulating cap assy
(v) Supply only Sliding pocket contact
(vi) Supply only Auxiliary switch (5NO+5NC)
(vii) Supply only Control switch
(viii) Supply only Oeration counter
(ix) Supply only Presa per accessori
(x) Supply only Coil support (EL)
(xi) Supply only APPL-RL1 (110V AC/DC)
(xii) Supply only MO2 Assy 110 volts
(xiii) Supply only Open coil MO1 110 volts
(ixx) Supply only MO co As 11o volts
(xx) Supply only MC closing coil
(xxi) Supply only Motor 100-130 V DC-AC
(xxii) Supply only Oper Mech EL2 Vmax
(xxiii) Supply only Aux. switch 20 3C silvered
(xxiv) Supply only Shock absorber
(xxv) Supply only Locking handle as per exiting make/model
(b) Make of VCB/SF6 Areva (Schnieder) model No PIX-MV 11 KV as per existing make/model
(i) Supply only Isolating contact flat type 800/1250 A
(ii) Supply only Vaccum interrupter VG2
(iii) Supply only Breaker housing
(iv) Supply only VCB operating mechanism
(v) Supply only Closing coil 30 VDC
(vi) Supply only Tripping coil 30 VDC
(vii) Supply only Spring charging motor 110 AC/DC
(viii) Supply only Breaker Auxiliary switch 6NO + 6 NC
(ix) Supply only Motor cut off switch
(x) Supply only Main drive shaft assembly
(xi) Supply only Trip form linkage assembly
(xii) Supply only Ratchet wheel
(xiii) Supply only Pin for ratchet
(xiv) Supply only Handle block assembly
(xv) Supply only closing coil box assembly
(vi) Supply only Trip coil box assembly
(vii) Supply only Motor cut off lever assy
(viii) Supply only Trip prop support assy
(ix) Supply only Release lever
(x) Supply only Pin for release lever
(xi) Supply only Auxilary switch drive assembly
(xiii) Supply only Charging Pawl
(xiv) Supply only Buffer for spring
(xv) Supply only Over ride stop and in
(xvi) Supply only 24 pin plug and socket assy
(xvii) Supply only RYB busbar phase spout 800 Amp (upper and lower)
(xviii) Supply only Circuit spout
(xix) Supply only Spring charging handle
(xx) Supply only Limit switch assy
(ae) Supply and fix in repair Elstein HFS panel heater 300 watt suitable for 11/33 kv VCB for removing the moisture
Supplying, fixing in repair maintenance free tubular battery suitable for solar/invertor light, 12 volts, 180 AH or equivalent as per existing including initial charging and connction and testing complete as specified and directed.
Shree Kanth Technologies
Prime power system
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .