Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.1 CrAccepted-AOC | ₹23.1 Cr Quoted ₹23.2 Cr | L1 | Accepted-AOC Acceptance |
| 2 | L2₹24.3 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹24.3 Cr | L2 | Rejected-Finance Rejected not being L1 |
| 3 | Rejected-Technical SF 201 S 201 203 SECOND FLOOR SATYAMEV EMINENCE B S SAPTAK BUNGALOWS SCIENCE CITY ROAD SOLA AHMEDABAD GUJARAT 380060 UDYAM GJ 01 0053639 | AHMADABAD | GUJARAT | 380060 | - | - | Rejected-Technical Not meeting the NIT Criteria |
| Sl No | Description | Qty | Unit | SOOD ASSOCIATES PVT LTD L2 | SHELL REFRACTORIES and INSULATIONS L1 |
|---|---|---|---|---|---|
| 1.00LIST OF WORKS (Schedule A Part I to Part XVII) | |||||
| 2.00 | Total amount of Sch 'A' Part-I (Building Works) brought forwarded from sl page No 26 . | 1 | Lump sum | 12,86,88,513.13 ₹12.9 Cr | 11,40,61,364 ₹11.4 Cr |
| 3.00 | Total amount of Sch 'A' Part-II (Repair /Rehabiliation work) brought forwarded from sl page No 30. | 1 | Lump sum | 1,60,43,905.33 ₹1.6 Cr | 1,26,32,996.32 ₹1.3 Cr |
| 4.00 | Total amount of Sch 'A' Part-III (Internal Electrification) brought forwarded from sl page No 39 . | 1 | Lump sum | 76,29,249.33 ₹76.3 L | 69,93,478.55 ₹69.9 L |
| 5.00 | Total amount of Sch 'A' Part-IV (Internal Water supply) brought forwarded from sl page No 40 . | 1 | Lump sum | 92,473.7 ₹92,473.70 | 1,01,980.34 ₹1.0 L |
| 6.00 | Total amount of Sch 'A' Part-V (External water supply) brought forwarded from sl page No 42 . | 1 | Lump sum | 5,94,685.84 ₹5.9 L | 3,86,377.8 ₹3.9 L |
| 7.00 | Total amount of Sch 'A' Part-VI (External Electrification ) brought forwarded from sl page No 43. | 1 | Lump sum | 41,27,751.45 ₹41.3 L | 35,10,213.83 ₹35.1 L |
| 8.00 | Total amount of Sch 'A' Part-VII (Sewage Disposal) brought forwarded from sl page No 44 . | 1 | Lump sum | 1,65,996.53 ₹1.7 L | 1,67,415.31 ₹1.7 L |
| 9.00 | Total amount of Sch 'A' Part-VIII (Area Drainage) brought forwarded from sl page No 45. | 1 | Lump sum | 6,77,209.22 ₹6.8 L | 6,36,692.43 ₹6.4 L |
| 10.00 | Total amount of Sch 'A' part- IX (Fire fighting) brought forwarded from sl page No 51. | 1 | Lump sum | 79,97,139.36 ₹80.0 L | 63,04,314.24 ₹63.0 L |
Updated dates
Tender Value
₹21.6 Cr
EMD Value
₹14.0 L
Closing Date
2 Dec 2025, 6:00 pmClosed
Sr DDG and CE
DGNP Mumbai, Naval Dockyard, SBS Road
AUGMENTATION OF MISSILE BOAT ENGINE REPAIR SHOP AT ND (MBI)
2025_MES_724480_3
8551
Open Tender
Civil Works - Others
DGNP MUMBAI
Please refer Tender documents.
10 documents required · 10 mandatory
₹3,000
DGNP Mumbai
₹14.0 L
12 Feb 2026
4 Nov 2025
9 Dec 2025
4 Nov 2025
2 Dec 2025
18 Nov 2025
LIST OF WORKS (Schedule A Part I to Part XVII)
Total amount of Sch 'A' Part-I (Building Works) brought forwarded from sl page No 26 .
Total amount of Sch 'A' Part-II (Repair /Rehabiliation work) brought forwarded from sl page No 30.
Total amount of Sch 'A' Part-III (Internal Electrification) brought forwarded from sl page No 39 .
Total amount of Sch 'A' Part-IV (Internal Water supply) brought forwarded from sl page No 40 .
Total amount of Sch 'A' Part-V (External water supply) brought forwarded from sl page No 42 .
Total amount of Sch 'A' Part-VI (External Electrification ) brought forwarded from sl page No 43.
Total amount of Sch 'A' Part-VII (Sewage Disposal) brought forwarded from sl page No 44 .
Total amount of Sch 'A' Part-VIII (Area Drainage) brought forwarded from sl page No 45.
Total amount of Sch 'A' part- IX (Fire fighting) brought forwarded from sl page No 51.
Total amount of Sch 'A' part- X (Lift) brought forwarded from sl page No 53.
Total amount of Sch 'A' part- XI (Air conditioning) brought forwarded from sl page No 54.
Total amount of Sch 'A' part- XII (Road/Path/Hard standing ) brought forwarded from sl page No 56.
Total amount of Sch 'A' part- XIII (Water cooler) brought forwarded from sl page No 57.
Total amount of Sch 'A' part- XIV (EOT Crane) brought forwarded from sl page No 58.
Total amount of Sch 'A' part- XV (Demolition & Dismantling) brought forwarded from sl page No 60.
Total amount of Sch 'A' part- XVI (Excavation & Earth work) brought forwarded from sl page No 61.
Subtotal
Sch 'A' Part- XVII (MISCELLANEOUS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
S & F vertical triple pole & neutral, double door, metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB up to 250 A as incomer and SP/TP MCBs as outgoing, reversible metal door, fully insulated 250 A copper busbar for each phase, two fully insulated & shrouded neutral bars, two earthbars, cable ties for cable management, prefitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed by engineer-in-charge of following size:- Make: Legrand, Schneider, L & T NOTES: [i] FP MCCB & SP/TP MCBs shall be measured and paid separately.
Verticle triple pole & neutral double door DB, 8 way
Verticle triple pole & neutral double door DB, 4 way
S & F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed by the engineer-in-charge of following capacity:- Make: Schneider, Legrand, L & T
6- 32 A, 230 V, 50 Hz, SP MCB (C curve)
6- 32 A, 230 V, 50 Hz, SPN / DP MCB (C curve)
6- 32 A, 415 V, 50 Hz, TP MCB (C curve)
6- 32 A, 415 V, 50 Hz, FP MCB (C curve)
S & F moulded case circuit breaker (MCCB) with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 1.5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% as per IEC 60947-2 complete all as specified and directed by engineer-in-charge of following capacity:- Make: Schneider, Legrand, L & T
200 A, 25 kA, 415 V, 50 Hz, FP MCCB
63 A, 25 kA, 415 V, 50 Hz, TP MCCB
63 A, 25 kA, 415 V, 50 Hz, FP MCCB
40A, 25 KA, 425V 50HZ, TP MCCB
40A, 25 KA, 425V 50HZ, FP MCCB
S & F 20 W surface / wall mounted LED batten capable of delivering 2000 lumen, having PC diffuser, luminous efficacy of > 90 lumen/W, CRI > 80, PF > 0.9, CCT 6500K, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. Make: Philips Cat-Part No. BN 021C LED20S- PSU CW GR S2 or equivalent model of Havells Cat-Part No. LHEXAPP7IN1W020 or Wipro Cat-Part No. LL20-281-XXX-65AL1
S & F 30 W recessed mounted square shape 2' X 2' LED panel capable of delivering 3000 lumen having high efficiency long life LED package in integral module with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, high transmittance polystyrene opal diffuser, housed in white powder coated pressure die-cast aluminium heat sink having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. Make: Philips Cat-Part No.RC380B LED30S-4000 L60W60 PSU OD S1 or equivalent model of Havells Cat-Part No. VENUSNEOHE2X2R28WLED857PIRSENSOR or Wipro Cat-Part No. CRCO10R038HP57G1
S & F 10 W recessed mounted square shape 2' X 2' LED panel capable of delivering 3000 lumen having high efficiency long life LED package in integral module with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, high transmittance polystyrene opal diffuser, housed in white powder coated pressure die-cast aluminium heat sink having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. Make: Philips Cat-Part No.RC380B LED30S-4000 L60W60 PSU OD S1 or equivalent model of Havells Cat-Part No. VENUSNEOHE2X2R28WLED857PIRSENSOR or Wipro Cat-Part No. CRCO10R038HP57G1
S & F BEE five star rated energy efficient high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 200 CMM, operating voltage 220-240 V and frequency 50 Hz, including a downroad of suitable size complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. ENTRUST 50- 5 STAR or equivalent model of Havells Cat-Part No. ES - 50 Premium or BAJAJ Cat-Part No. Electra 50
S & F engery efficient metalic exhaust fan having blade sweep 300 mm, air delivery not less than 6000 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. EXHD300- 4-1 or equivalent model of Havells Cat-Part No. Ventil Air - DSP or BAJAJ Cat-Part No. Max Air
S & F pedestal fan having blade sweep 450 mm, air delivery not less than 125 m³/min, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. SSTORM2 or equivalent model of Havells Cat-Part No. Windstorm or BAJAJ Cat-Part No. Victor VP01 18"
S & F wall fan having blade sweep 400 mm, air delivery not less than 125 m³/min, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. WMSDX 120 or equivalent model of Havells Cat-Part No. Turbo Force or BAJAJ Cat-Part No. Esteem
M & L for XLPE insulated, unarmoured heavy duty electric cable with copper conductor, 1100 volts grade, following cross-sectional area.
4x4 sq. mm
4x6 sq. mm
4x10 sq. mm
4x16 sq. mm
4x25 sq. mm
4x35 sq. mm
Supply and drawing of UTP 4 pair CAT 6 LAN 1 run of cable (1.53.1) in the surface /resessed Steel/PVC conduit as required.
Supplying and drawing 02 pair 0.5 sq mm FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. Including conduit
Supply and fixing following modular switch/ socket as required Including cost of socket, sunken box, cover plate etc all as specified and directed by Engineer-in-Charge.
Telephone socket outlet
TV antenna socket outlet
RJ45 LAN socket outlet
Supply,installation,testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor with day light dimming(lighting level shall be regulated as per availability of natural day light in an area along with occupancy detection.) having high preformance, regulating programmable type, suitable for connected load upto 10 A, for mounting height up to 2.8 meter and for 5 meter diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
S&F Cable End Box (Loose Wire Box) suitable for 8 way, Double door TPN MCBDB triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required.
M&L for cement concrete tiles 300x300x22 mm thick machine pressed, set joined in cement slurry and pointed in epoxy grout including 15 mm screed bed in CM 1:4, complete all as specified and directed by Engr- in- charge.
Supply and installing of size 300 mm width X 50 mm depth X 1.6mm thickness perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
Supply and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the surface/ recessed steel/ PVC conduit as required all as specified and directed by Engineer-in-Charge..
Incomer:-
2000 Amps 4 Pole 50kA ACB Manual Drawout type with microprocessor release and protection for over load and short circuit built-in Earth Fault protection - 1 Nos.
Outgoings:-
63 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 4 nos.
630 Amps 4 Pole MCCB with Ics=Icu=50KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 3 nos.
400 Amps 4 Pole MCCB with Ics=Icu=36KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 5 nos.
100 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 2 nos.
250 Amps 4 Pole MCCB with Ics=Icu=36KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 2 nos.
LED Type Phase Indicating lamp For RYB -17 Sets
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
Notes:- (i) All MCCB's shall be provided with front operated rotary handles, phase barriers, phase spreaders complete as reqd. (ii) The panel manufacturer shall have CPRI certification Degree of Protection IP-54, Short circuit withstand strength shall be 50KA , Rated current for short circuit not less than 6000A (iii)Drawing of panel board shall be got approved from GE before fabrication (iv) Panel shall have provision (only provision but suppression system will be measured and paid separately) for installation of tube based Panel Fire Supression System having 4 kg automatic fire cylinder of CO2
Supply & Erection of LT Panel -1 factory fabricated & wired metal clad dust and vermin proof floor mountin
Incomer:-
Outgoings:-
630 Amps 4 Pole MCCB with Ics=Icu=50KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 1 no.
25 to 100 Amps 3 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 2 nos.
125 Amps 3 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 3 nos.
63 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 3 nos.
25 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (19A-25A) - 3 nos.
4 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (2.5A-4A) - 2 nos.
2.5 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (1.6A-2.5A) - 2 nos.
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
Notes:- (i) All MCCB's shall be provided with front operated rotary handles, phase barriers, phase spreaders complete as reqd. (ii) The panel manufacturer shall have CPRI certification Degree of Protection IP-54, Short circuit withstand strength shall be 50KA , Rated current for short circuit not less than 6000A (iii)Drawing of panel board shall be got approved from GE before fabrication (iv) Panel shall have provision (only provision but suppression system will be measured and paid separately) for installation of tube based Panel Fire Supression System having 4 kg automatic fire cylinder of CO2
LED Type Phase Indicating lamp For RYB -16 Sets
Incomer:-
Outgoings:-
400 Amps 4 Pole MCCB with Ics=Icu=36KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 1 nos.
250 Amps 4 Pole MCCB with Ics=Icu=36KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 3 nos.
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
LED Type Phase Indicating lamp For RYB -4 Sets
Notes:- (i) All MCCB's shall be provided with front operated rotary handles, phase barriers, phase spreaders complete as reqd. (ii) The panel manufacturer shall have CPRI certification Degree of Protection IP-54, Short circuit withstand strength shall be 50KA , Rated current for short circuit not less than 6000A (iii)Drawing of panel board shall be got approved from GE before fabrication (iv) Panel shall have provision (only provision but suppression system will be measured and paid separately) for installation of tube based Panel Fire Supression System having 4 kg automatic fire cylinder of CO2
Incomer:-
Outgoings:-
16 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (11-16A) - 5 nos.
32 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (24-32A) - 3 nos.
25 to 100 Amps 3 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 3 nos.
25 to 100 Amps 3 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 2 nos.
63 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 4 nos.
25 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (19-25A) - 2 nos.
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
LED Type Phase Indicating lamp For RYB -4 Sets
LED Type Phase Indicating lamp For RYB -21 Sets
Incomer:-
Outgoings:-
250 Amps 4 Pole MCCB with Ics=Icu=36KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 1 nos.
25 to 100 Amps 3 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 7 nos.
10 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (6.30-10A) - 6 nos.
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
Notes:- (i) All MCCB's shall be provided with front operated rotary handles, phase barriers, phase spreaders complete as reqd. (ii) The panel manufacturer shall have CPRI certification Degree of Protection IP-54, Short circuit withstand strength shall be 50KA , Rated current for short circuit not less than 6000A (iii)Drawing of panel board shall be got approved from GE before fabrication (iv) Panel shall have provision (only provision but suppression system will be measured and paid separately) for installation of tube based Panel Fire Supression System having 4 kg automatic fire cylinder of CO2
LED Type Phase Indicating lamp For RYB -19 Sets
Incomer:-
Outgoings:-
63 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 1 nos.
100 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 6 nos.
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
LED Type Phase Indicating lamp For RYB -4 Sets
LED Type Phase Indicating lamp For RYB -8 Set
Incomer:-
Outgoings:-
63 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 4 nos.
100 Amps 4 Pole MCCB with Ics=Icu=16KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 1 nos.
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
Notes:- (i) All MCCB's shall be provided with front operated rotary handles, phase barriers, phase spreaders complete as reqd. (ii) The panel manufacturer shall have CPRI certification Degree of Protection IP-54, Short circuit withstand strength shall be 50KA , Rated current for short circuit not less than 6000A (iii)Drawing of panel board shall be got approved from GE before fabrication (iv) Panel shall have provision (only provision but suppression system will be measured and paid separately) for installation of tube based Panel Fire Supression System having 4 kg automatic fire cylinder of CO2
LED Type Phase Indicating lamp For RYB -5 Sets
Design, Supply, installation, testing & commissioning of UL listed tube based Panel Fire Supression System having minimum 4 kg automatic fire cylinde
r of CO2, linear pneumatic detection tube, CO₂ discharge tubing with nozzles for protected panel space, master control unit having LED flasher, electronic hooter, LED indicator, silent switch, etc. with a provision for integration with the FACP along with all necessary accessories complete all as specified and directed by the engineer-in-charge. Notes: Design and drawings shall be got approved from AO before placing purchase order.
Supplying and layingDWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required of following sizes:-
160 mm dia (OD-160 mm & ID-135 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
Providing and fixing single stage Vertical inline Pumping set suitable for operation on 415 volts ± 10%, 3 phase and 50 HZ AC supply. The pump shall be made of C.I casing, bronze impeller (hard finished and dynamically balanced), stainless steel (316) shaft and sleeve with mechanical seal capable of delivering suitable capacity and connected by a flexible coupling to a totally enclosed fan cooled (TEFC) induction motor as per IEC standard. Both pump and motor mounted on common M.S. structural base plate bolted to cement concrete foundations complete with Pressure gauge, gunmetal isolation cock, vibration eliminating pads required as per specification. The pump set includes VFD & pressure switch along with necessary cable from panel to pump panel etc. complete.
Set of 2
Domestic Water Transfer Pump (Including VFD)
Capacity of Pump - 45 LPM
No. of pumps - 1 Set = 2 Nos. (1 w + 1 s)
Head - 55 Mtr
Motor HP - 3 HP each (Approx.) or as per manufacturer's recommendation.
Degree of Protection - IP "54"
Class of Insulation - "F"
Location of Pump - In Pump ROOM
Supplying, Installation, Testing & Commissioning of single stage submersible sump pumps of closed coupled construction. The pump shall be made of C.I. body, SS-316 impeller and S.S.-316 shaft, suitable for handling waste water, with motors for drainage application complete with M.S guide rail, galvanised lifting chain of suitable length, fasteners, expansion bolts etc. Sump pump shall be having automatic operation complete with motors, built in suction cable, dry run preventive devices, bottom support frame, guide wires, motor control panel (including, earthing, cable tray, termination, Control cable from plumbing panel to Control Panel of required size & Submersible cable from the control panel to the pump motor), two nos. of sensors/probes for automatic operation complete as per specifications. One additional pair of NO/NC contacts should be available for BMS purposes.
Drainage Sump Pump for Plumbing Plant Room
Capacity of Pump - 150 LPM
No. of Pumps - 1 Set = 2 Nos. (1 W + 1 S)
Head of Pump - 15 Mtr
Motor HP - 2.0 HP each (Approx.) or as per manufacturer's recommendation.
Solid handling capacity - 20 mm (Non Cutter Type)
S&F reselient rubber neoprene lined arch vibration eliminators with unit control nuts, bolts, washers, companion flange as per table E complete suitable for working pressure of 15 Kg/sqcm of following sizes:-
80 mm dia
100 mm dia
S&F mild steel (MS) puddle flanges of required size with 5mm thick mild steel (MS) plate including necessary welding as per details shown on drawings and directions of Engineer-in-charge for water tanks.
25mm dia (4mm wall thickness)
32mm dia (4mm wall thickness)
40mm dia (4mm wall thickness)
50mm dia (4mm wall thickness)
65mm dia (4mm wall thickness)
80mm dia (4mm wall thickness)
100mm dia (4mm wall thickness)
150mm dia (6mm wall thickness)
Supply, Installation, jointing and testing antimosquito grating for 100 mm dia vent pipe & spare sleeve.
S&F toilet paper holder .Make :- Jaquar, CAT No.:- ACN-1155N
S&F Liquid soap container of standard shape with bracket of the same material with snap fitting of approved quality and colour. Make - Jaquar, CAT No.- CAN-1135N
S&F of CP brass two way bib cock including, necessary flange, cutting and making good he walls / floors wherever required complete.
2 core, 1.5 Sqmm
2 core, 2.5 Sqmm (supply to hooter/strobe)
M & L for low smoke zero halogen (LS0H) flame retardant fire alarm cable, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter,
RED in colour, including laying, termination and ferruling complete all as specified and directed by engineer-in-charge. Make: RR Kabel, Polycab, Havells
S&F tar based corrosion protection tape ( wrapped with one layer of 4 mm thick PYPKOAT ) complete as per specification by applying with two coats of zinc chromate primer, wrapping tape spirally and thermosealing complete.
Supply of fire axe's with rubber handle .
SITC weather proof M.S cabinet size 1200 mm x 2100 mm x 600mm .
Supply, installation, testing and commissioning of SITC weather proof M.S cabinet size 1200 mm x 2100 mm x 600mm deep fabricated from 1.6mm thick M.S. sheets and M.S angle 40mmx40mmx6mm complete with glass, locking arrangements to accommodate the following: -
Gunmetal single headed Hydrant valve - 1 No.
Fire Hoses 63mm, 15 M long with accessories - 2 Nos.
Short branch - 1 No.
First Aid hose Reel - 1 No.
Fire Extinguisher - 2 Nos.
Fireman's Axe - 1 No.
Pressure Gauge - 1 No.
Note:-The cabinet shall be painted with one coat of primer and 2 coats of synthetic enamel paint of approved shade.
S & F OF ISI markd (IS:15683) marked Water fire extinguisher (stored pressure) type capacity 9 ltrs. with gun-metal cap and nozzle and complete in all respects including initial fill and wall suspension bracket. Capacity 9 ltrs. (Inside FHC)
S & F OF ABC dry powder conforming to IS:15683, stored pressure type fire extinguishers (Mono ammonium phosphate confirming to IS 14609) minimum 85% effective discharge,Capacity 6 kg, finished externally with red enamel paint and fixed to wall with brackets, complete, with internal charge. (Inside FHC)
S & F of ISI marked (IS:16018) Fire and wall suspension bracket. Extinguisher, Trolley mounted carbon-dioxide type capacity 22.5 kg. flat base including valve, discharge hose of not less than 10 mm dia. I M long complete in all respects including wheeled trolley. (For Fire Plant Room / LT room / Transformer Room / STP)
S &Fof CO2 type fire extinguisher 4.5 kg capacity ISI marked fitted with screw, down type high pressure control valve confirming to IS:3224 with 1 mtr. Long wire braided high pressure discharge hose and electrically non conducting horn, manufactured conforming to IS 2878 complete with initial charge, wall mounted bracket/ screws etc. as required. (MAKE-Life guard/Agni/Ceasefire/Safex)
S&F of ABC Powder stored Pressure type (MAP 90%) Fire Exhinguisher 6 Kg capacity complete with pressure guage controller discharge mechanism with horn & nozzle Class A rating, 3A & Class B rating 21 B of following capacities confirming to IS: 15683 : 2006 with suitable clamps on existing wall as required. (MAKE-Life guard/Agni/Ceasefire/Safex)
S&F testing and commissioning 25mm diameter inspecting and testing assembly with brass isolation valve built-insight glass bypass valve and connected to 80mm drain line.
Supply, Installation, Testing and Commissioning Air release valve for sprinkler riser to release the trapped air inside the sprinkler riser installed at top of riser.
S&F vane type water flow switch suitable for installation on 65 mm dia line for a service pressure upto 20 kg/sq. cm. of Potter / System sensor /Angus
Supply, Installation, Testing & Commissioning of heavy class Galvanized Iron pipe (confirming to IS:1239 upto 150mm dia and IS 3589 above 200mm dia of Grade 330 with minimum 6.35mm thickness) ncluding cutting, welding and jointing with all fittings i.e tees, bends, elbows, flanges, reducers etc.complete including painting of pipes with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade including fabrication of all M.S. structural steel (Hot Deep Galvanized) work for clamping, supporting and hanging the pipes with GI rods (Hot Deep Galvanized) and dash fasteners etc, all complete including cutting holes in brick or RCC walls / slabs and making good the same, as directed by the Engineer in charge of following sizes:- Note: Pipe upto 50 mm dia shall have threaded joints, above 50 mm shall be welded joints.
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
S&F electronic type water level indicator with LED panel mounted as required by the Project Manager complete with probes & all control wiring etc.
Supply, installation, testing and commissioning of sight tube (of 3.5 to 4 mm length) with isolation valve at top / bottom, demarcation on tube for making the installation of level indication on the RCC water tank complete.
Supply, Installation, Testing & Commissioning of heavy class Galvanized Iron pipe (confirming to IS:1239 upto 150mm dia and IS 3589 above 200mm dia of Grade 330 with minimum 6.35mm thickness) ncluding cutting, welding and jointing with all fittings i.e tees, bends, elbows, flanges, reducers etc.complete including painting of pipes with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade including fabrication of all M.S. structural steel (Hot Deep Galvanized) work for clamping, supporting and hanging the pipes with GI rods (Hot Deep Galvanized) and dash fasteners etc, all complete including cutting holes in brick or RCC walls / slabs and making good the same, as directed by the Engineer in charge of following sizes:- Note: Pipe upto 50 mm dia shall have threaded joints, above 50 mm shall be welded joints.
S&F vane type water flow switch suitable for installation on 65 mm dia line for a service pressure upto 20 kg/sq. cm. of Potter / System sensor /Angus
S&F MS class 'C' diesel engine exhaust pipe (including all fittins) clamps stee support of suitable dia for the engine wrapped with 12 mm thick superceva ceramic fibre rope complete.
Incomer:-
Outgoings:-
S&F, testing & commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45oC temperature, working pressure 8.8 Kg/cm2 and test pressure 14 Kg/cm2 of following sizes:-
150 mm dia
For Main Electric Pump 65 HP, 200 Amps 4 Pole MCCB with Ics=Icu=36KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 1 nos.
For Jockey pump 10 HP, 16 Amps 4 Pole MPCB with Icu=50KA Motor protection Circuit Breaker shall be with protection release for over load and short circuit with thermal release range (11-16A) - 6 nos.
Providing and fixing Auto start panel activated with pressure switch for diesel engine complete with all accessories, batteries, battery charger of suitable rating, MCB timers, push buttons, microprocessor based alarm annunciator, wiring and cabling including connection to diesel engine complete as required ready for working.
Necessary cable alleys space for spare switches, internal wiring and copper earthing of all equipment shall also be included. All switch gears/control gears shall be motor duty rating.
Provision for starting the diesel engine fire pump. The diesel engine driven fire pump shall start automatically in the event of pressure drop beyond preset limit on mains failure or failure of electrical driven pumps to start and logic necessary for automatic start of diesel engine along with battery charger for the diesel engine batteries. Window type fault indicator and with alarm for diesel engine faults like LLOP, HWT etc. as per manufacture requirement. with 2 nos of 12 volt 150AH Batteris.
250 Amps 4 Pole MCCB with Ics=Icu=36KA Moulded Case Circuit Breaker shall be with thermomagnetic protection release for over load and short circuit, spreader terminals, built-in Earth Fault protection - 3 nos.
Danger notice plate vitreous enamelled white on both sides and inscription in signal red colour of mild steel (200mm x 150 x 2mm thick) - 2 Nos.
LED Type Phase Indicating lamp For RYB -4 Sets
One No. digital hour meter for jockey pump.
Boost/Trickle charger for starting the engine automatically with digital ammeter and voltmeter complete as requ
Provision shall be made for providing potential free contacts to all pumps starters for connection to building automation system.
S&F Addressable exit signage, single/ doubleside, directional arrow, staircase usage sign during fire complete as per site requirement, visible from 20 mtrs. with integral battery capacity of 2 hrs.
Supply, drawing, connecting, testing & commissioning of 2 core, 1.5 sq. mm. stranded copper conductor, pvc insulated PVC sheathed, aluminium myler tape shielded FRLS wire in existing conduit.
Supply and laying in position 25mm dia MS. conduits including providing all accessories complete as required. (For Fire Detection)
Supply, Assembly, field performance and handing over of Floor mounted type Double Skinned having thickness of 25±2 MM Sandwiched insulated (density 40kg/m3 CFC Free) sectionalized construction, with all Aluminium dampers and spring type vibration isolations (b/w Fan & Fan casing) comprising of Fan section with double width double inlet backward curved centrifugal fan with fix speed IP55/4P TEFC fan motor, canopy, connected with fire resistant flexible outlet connection, pre-filter (10micron) section. (Only for Supply Air Units). The unit shall be supplied along with MS-channel (ISMC) foundation frame suitable as per site requirement, canopy, bird screen, spring type vibration isolator b/w fresh air unit & foundation frame. The structure part shall be dully painted with double coat of paint and single coat of red-oxide.
Fresh Air Unit capacity : 12000 CFM, External Static pressure : 30 mmwg
Fresh Air Unit capacity : 5000 CFM, External Static pressure : 30 mmwg
Supply, Assembly, field performance, handing over of Floor mounted type Double Skinned having thickness of 25±2 MM Sandwiched insulated (density 40kg/m3 CFC Free) sectionalized construction, with all Aluminium dampers and spring type vibration isolations (b/w Fan & Fan casing) comprising of Fan section with double width double inlet backward curved centrifugal fan with fix speed IP55/4P TEFC fan motor, canopy, connected with fire resistant flexible outlet connection. The unit shall be supplied along with MS-channel (ISMC) foundation frame suitable as per site requirement, canopy, bird screen, spring type vibration isolator b/w Ex. air unit & foundation frame. The structure part shall be dully painted with double coat of paint and single coat of red-oxide.
Exhaust Air Unit capacity : 12000 CFM, External Static pressure : 30 mmwg
Exhaust Air Unit capacity : 5000 CFM, External Static pressure : 30 mmwg
Supply, Installation, testing and commissioning of AUTOMATIC VOLTAGE STABILIZER 4 KVA, (wall mounted type) with 3 step relay to convert 140-280 volts incoming power to 200-240 volts out going power, low/high voltage cutout, time delay relay, digital display of voltage / current.
Supply, fabrication, Installation, testing and commissioning of factory fabricated rectangular ducts using G.I Sheets (120GSM coating). including factory fabricated TDF flanges, turning vanes, splitter dampers, supports (factory fabricated, full threaded GI rod/hangers & G.I slotted channel), sealant, neoprene gasket, access door etc. The joints shall be with leak proof and shall be tested with pressure testing machine. The gasket shall be installed b/w duct & duct support to avoid mechanical contact all as directed. Note :- The Duct shall be manufactured as per SMACNA Standard but the minimum guage shall be 24 G. The exposed duct shall be fabricated with one higher gauge.
24 gauge galvanized sheet steel ( TDF 01- 750mm)
22 gauge galvanized sheet steel ( TDF 751 - 1500mm)
20 gauge galvanized sheet steel ( TDF 1501- 2250mm)
GSS VOLUME CONTROL DAMPER
Supply, installation, testing and balancing of opposed multiblade box type GI volume control damper within ducts to be provided with suitable links, levers and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system as per approved shop drawings & specifications made from. (Frame-14G, Blade-16G) and including all fan units VCD's unit outlet .
Supply, installation, testing and commissioning of multi blade sleeve type combined spring return fusible link type fire & smoke dampers. The damper shall be of atleast 2.0 hr. fire rating. The damper shall be as per CBRI approval.The damper shall be constructed out of 16G galvanised sheet steel (frame -14G, Blade-16G). The fire dampers shall be installed at locations shown in approved shop drawings and as per specifications. All Fire Damper shall be supplied along with MS sleeve of 3mm thick & 300mm long and having both site flange's for duct & Fire Damper connection.
Supply, installation, testing and balancing of powder coated Extruded Aluminium Supply air Grilles (Double louvered- Adjustable type) with aluminium volume control dampers (key operated) in accordance with the approved shop drawings and specifications.
Supply, installation, testing and balancing of powder coated Extruded Aluminium Supply air Grilles (Single louvered- Fixed type) without VCD in accordance with the approved shop drawings and specifications.
Supply, installation, testing & commissioning of fire resistant flexible canvas suitable for FAN etc. The flexible canvas shall be of atleast 2.0 hr. fire rating.
Details of outgoing feeders are for followings : Fresh air unit : 2nos. (12000CFM, 30mmwg-01 No & 5000CFM, 30mmwg-01 No) Exhaust air unit : 2nos. (12000CFM, 30mmwg-01 No & 5000CFM, 30mmwg-01 No) Split AC upto 1.5 TR : 5nos. Spare feeder : 10% of all outgoing feeders including all switchgers
Supplyin, laying, testing and commissioning of XLPE insulated copper conductor armored cables of 1.1 KV grade of following sizes directly on wall/structural frame/ cable trays or racks using approved type of clamps,End terminations with Double Compression type glands on both ends, cable tag on both side, double earthing with GI strip/wire of suitable size and hardware as per specifications.
3 Core x 6 Sq. mm (Copper)
3 Core x 4 Sq. mm (Copper)
4 Core x 2.5 Sq. mm (Copper)
Supply and laying readymade cable trays of 14 SWG GI sheet with pre Galvanizing (minimum 80 micron) with cover for outdoor applications. including for installation necessary anchor fasteners and 'L' angle supports at required interval etc., to suit site conditions as required of following size:-
50 mm wide
100 mm wide
150 mm wide
Supplying and laying of the earthing GI strip/wire clamped to wall with suitable clamps saddles and fixing bolts/ in ground as required and complete as required to comply with IS 3043:1987. All copper joints shall be tinned. The rates shall be inclusive of making test joints where ever required of following sizes:-
25 mm x 6 mm GI strip
8 SWG GI Wire
Supplying, installing, testing and commissioning of chilled water type central air Unit conditioning plant of capacity 52 TR (Approx)- 26 TR (02 Nos working and 01 No standby) with all equipments and accessories complete and comprising of the Job following:- (a) Three Nos of water cooled chiller unit factory assembled with nominal cooling capacity appox. 26TR ,duly prewired and run tested at the factory with capacity modulation in steps. (b) Intelligent:- Microprocessor control to ensure ease of operation significant power saving to reduced maint cost and lower instance of break downs. (i) Digital setting of temp levels enable setting of desired temperature level accurately to ensure optical cooling and significant power saving (c) Auto distribution load to ensure when the air condition is less than full capacity of the chiller microprocessor automatically to keep only the required compressor on and switch off rest. Moreover controller ensures all compressors evenly switched ON or OFF at regular interval to ensure efficient running of the chiller and ensure equal load on all the compressors. (d) BMS capability to ensure PC monitoring and remote connectivity features. (e) Protection mechanism:- The controller to protect the compressor from accidental phase reversal or single phasing errors .In built anti freeze protection ensure cutoff before freezing point to ensure lower instances of breakdown. 1.06 (f) Non volatile memory:- all setting on the controller are stored in the non volatile memory and stop through power failure for avoiding the need to reset the parameters after every power failure.
(g) Self diagnostics: - to help in identifying fault very quickly .technical fault can be detected and displayed on the controller to make trouble shooting simple. (h) Auto start:- The controller restart automatically with its original setting after the restoration of power supply (i) Three Nos chillers each comprising of two compressor of 13 TON hermatically sealed units using R - 407C refrigerant complete with suction and discharge shut off valves, automatic capacity control with the thermostats and solenoid valves, buift in suction strainer, oil pump, hot gas muffler, heat wheel, oil pressure, safety switch etc all as specified. (Make: Kirloskar/Blue Star/Carrier) (ii) Six Nos shell and tube type water cooled condenser for each compressor with fouling factor 0.00025 F f2 hr/Btu and Min rate of flow of water 67.6 USGPM and max flow of water 91 USGPM ,water inlet/outlet temp 29.44 degree/35 degree centrigrade MS Shell and integrally finned copper tubes complete with safety valve, drain valve, water inlet and out valves, hot gas inlet and liquid outlet isolating valves, thermometer and pressure gauges at water inlet/outlet and purge valve all as specified. (iii) Three Nos shell and tube type DX chiller with thermal insulation (iv) Three Nos stands fabricated out of MS powder coated chiller base frame of suitable size for mounting compressor., motor, and condenser. (v) Three set of neoprene rubber anti-vibration ribbed pads with MS channel in foundation etc complete as per manufacturer's instructions for installation of the plant. (vi) First charge of R - 407C refrigerant and Compressor oil for the complete plant. (vii) Bright annealed copper heavy duty refrigerant piping for suction, discharge and liquid line compete with fitting valves. suction line should be insulated. (j) Condenser water cooling arrangement comprising of the following :-
(i) Three Nos EEC Series (Engery efficient) monoblock centrifugal condenser cooling water pumping sets of Make: Kirloskarl Groundfoss/ Mather & Platt / Crompton IBeacon of suitable capacity not less than 3 HP to achieve desired dishcarge and head alongwith necessary valves in suction and delivery line each of 50% capacity (02 Nos working and 01 Nos Standby) and suitable for operation on 3 phase 50 cycles, 415 volts AC supply along with hydraulic vane type water meter for flow measurement and providing a pressure gauge in each pump set of suitable capacity including suitable foundation with neoprene rubber anti vibration ribbed pads all as specified. (ii) One No corrosion resistant, fire retardant, FRP induced draft, rectangular type counter flow cooling tower of capacity 120% of plant running capacity with maximum allowable temperature 50 degree centigrade, drift loss 0.005% of water circulation of Make: Mihir/ Paharpurll polo/ Deltal Advance with suitable foundation and float valve of suitable size and ) mounted on suitable stagging as specified. (k) PVC Make up water tank, closed lid, cylindrical shaped, 1SIl marked water tank of 5000 Ltrs capacity. Make:- Sintex or equivalent. (i) One lot of condenser water piping of MS 'C Class piping as per S-1239 from make up tank to cooling tower, from cooling tower to condenser and return complete with fittings, valves, pot/ Y strainers etc. (l) Chilled water circulation arrangement comprising of the following - (i) Three Nos monoblock centrifugal pumpsets of Make: Kirloskarl Groundfoss/ Mather & Platt Crompton /Beacon of capacity not less than 3 HP for circulating chilled water alongwith necessary valves in suction and delevery line each of 50% capacity (02 Nos working and 01 Nos Standby) and suitable for operation on 3 phase 50 cycles, 415 volts AC supply, along with one number pressure gauge in each pump set of suitable capacity including suitable foundation with neoprene ubber anti- vibration ribbed pads all as specified.
(ii) Chilled water piping :- (a) A lot of MS 'C class piping , 1SI marked pipe of Make Tatal Jindal with all fittings such as bends, elbow, tees, reducers, tees supports, flow indicators etc of suitable sizes as per site requirement to maintain the continuous and constant flow of chilled water from chiler unit to AHUs so that designed conditions can be met with.The chilled water pipe line network shall be laid under ground , above ground, floor, roof, a long wall etc. chilled water pipe line shall be insulated with EPS section of 50mm thickness with and including applying bitumenous compound and AL cladding with 27 gauge AL sheet to avoid the heatloss including water pipe line. Bidder shall ensure the quality of line insulation and adequate insulation be provided so that chilled water temperature of 8-9Degree celcius can be maintained at AHUs inlet point. (b) A lot of butter fly valve, gate valve, sluice valve in chilled piping network to maintain required flow in each branch line as per approved layout diagram (iii) Condensate water drain piping with Gl pipe-B class conforming to IS:1239 of suitable size including all fittings like anchor fasteners, couplings, bends, elbows, tees, thrust, blocks, wooden blocks, flanges, welding as required including insulation as specified. (iv) Chilled water expansion tank ISI marked, multi layered, closed lid, cylindrical shaped tank of syntex company having capacity 1000 ltrs and thermally insulated with 50 mm thick EPS TF quality sheet of suitable sizes having density not less than 65 Kgl Cu.m, thermal conductiivity 0.334 w MK at '0' degree centigrade of Make : Beard Sell or equivalent in Mag Hard insulator/ Zenith/ Modi with protecting covering of 27 gauge aluminium cladding and suppoting piping connections, valves, fittings etc all as (m) One Nos Air handling unit of Make: Edgetech/ Zeco/ Citizen/ BTS with not less than directed and specified. 25000 dehumidified air CFM ,static pressur 50mm WG suitable capacity with chiller unit of sectionalised construction, factory made double skinned six row deep cooling coil and 50 mm TSP complete with all accessories controls etc as per OEM specifications and comprising :- (i) Cooling coils of copper tube with aluminium fins. (ii) Prefilter, plenum and fire dampers in the supply air duct.
(iii) Heating Kit
s, strip type of min capacity 18 KWN arranged in banks to serve as relative humidity control of conditioned space including providing switchgears accessories, measuring devices, etc all as specified and directed complete with Controls. (iv) Blowers for AHU complete with suitable electric motor, TEFC squiral cage induction motors for operation on 415 Volt, 3 phase, AC supply, with V Belt and beltfs guard (v) Insulation of AHUs all as specified. (n) 01 Lot of air distribution system comprising of supply air ducts from AHU to all conditioned space and return air duct as per site requirement from conditioned space to AHU's etc including providing insulation to avoide condensation and effective designed condition in air conditioned space of all building including interconnectors as required from AHU to the conditioned space comprising of class VIll galvanised sheet with suitable supporting arrangements and bracing, supply /I return/ fresh air grilles on sheet metal frame work duly painted /finished to match with the exisiting ceiling. Fire dampers operated with fusiable link shall be provided. NOTE:The AC Duct drawing shall be produced for approval of ACcepting Oficer before fabrication of AC Duct work. (o) AHU Control panel - one Nos cubical wall mounted, indoor LT panel, dust and vermin proof factory fabricated, CPRI approved make, made out of not less than 2 mm thick CRCA sheet and powder coated protection class IP-52 suitable for operation an 3 phase 50 Hz, 415 volts, including internal wiring with 1100 volts grade single core, PVC insulated, FRLS, multistranded copper conductor cables of suitable current carrying capacity complete and comprising of the following accessories :- (i) One set of 250 Amps rated copper bus bar suitable for 3 phase 4 wire, 415 volts mounted on PVC/ hygroscopic insulators and PVC colour coded Sleeves of R,Y, B and green colour complete arranged in separate compartment. -01 set. (ii) Incoming MCCB, 4P, 125 Amps, 35 KA at 415 Volts - 01 No (iii) Outgoing MCCB, TP, 40 Amps, 25 KA, 415 volts - 01 Nos (For heater bank) (iv) Outgoing MCCB, TP, 63 Amps, 25 KA, 415 Volts - 01 No (For AHU motor)
(ix) M & L for earthing complete, with GI earth plate electrode of size 60cm x 60 cm x 6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5m below the normal ground level connected with GI Strip 32 x 6mm by means of bolts, nuts, check nuts and washers of galvanised iron steel including necessary excavation and earth work in any type of soil , removing surplus soil to a distance not exc 50, with and including PCC chamber in PCC (1:2:4), type B1, using (20mm graded stone aggregate), having outer dimensions 60 cm X 60 cm X 60 cm and internal dimensions 30 cm X 30 cm X 30 cm, "mild steel angle iron frame" made out of MS angle iron of size 40 x 40 x 6mm thick duly painted with two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer hinged with an including 10 mm thick Cl cover with handle, watering arrangment with funnel internally secured with wire mesh with 20 mm dia medium grade pipe for watering, 40 mm dia light grade, GI pipe for lead protection form electrode to Test Point/ Pannels/ accessories in & including alternate layers of charcoal dust and common salt complete- Each -6 ( Location : Near AC Plant)
Dismantling of old AC Plant including chiller, AHUs, ducting, piping, etc. and depositing JoD the dismantled equipment as well as scrap material to the user department.
Supply and install Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type wall mounted & designed for input variation between170 V to 230 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4.0 KVA including time delay control, Voltmeter, indication lamps etc all as specified and directed by Engr-in- charge
Design, Supply, installation, testing and commissioning of Grid supply net metering type Solar Power plant at roof top all as mentioned here-under complete with Solar PV panels and inverters of reputed make including necessary cabling upto net meters and LT Panels complete in all respects and specifications as directed by Ministry of New and Renewable Energy (MNRE) India. The cost includes Module Mounting Structures to install the system and necessary liasoning with MES. Contractor shall submit 5-year guarantee certificate for compl
Plant capacity 100 KWp (for Building No. P-173 having approximate shadow free area 8000 Sqft)
Plant capacity 40 KWp (for Building No. P-185 having approximate shadow free area 3200 Sqft)
Plant capacity 27 KWp (for Reconstruction of Building No. P-186, approximate shadow free area 2200 Sqft)
NOTES:- (i) The contarctor shall submit complete technical specification including installation drawing for the make offered by him and shall obtain the approval of accepting officer. (ii) The technical specification shall be confirming to the particular specification, any change shall be accepted subject to the superior and latest engineering practice and standardized without any upper price adjustment. (iii) Exact measurement shall be confirmed by contractor from drawings. (iv) Crane shall be designed as per data sheet in Particular Specification and to be vetted by NIT/Any Govt. Engineering College.
M & L 5.50mm Thick sun tinted sheet glass, ordinary quality and glazing with oil putty in square exc 0.5 sq. m in each pane complete all as specified and directed
Making V groove along the length of crack. Remove all dust and loose particles and replace NRV packers/linjection ports at spacing of 200 to 500 mm centre to centre spacing depending on the porosity of substrate, seal the cracks with epoxy putty Fosroc Nitocote VFlequivalent followed by pressure grouting with low viscous solvent free two component moisture insensitive epoxy resin Fosroc Conbextra EP10M having density of 1060 Kg/m3. The epoxy injecting materials shall have compressive strength 60 MPa as per ASTM D695, tensile strength 20 MPa as per ASTM C307-94, flexural strength 45 MPa as per BS6319 part 3 etc complete.”
Rust Removal: Cleaning of rust/ scales/corrosion from reinforcement bars using rust remover. The material to be applied to the rusted metal using brush and make leaving to dry for 30 mins & washing surface with fresh water as required to exposed reinforcement bars complete all as specified and directed. Make: BASF, Krishna conchem, Fosroc or equivalent
Design, supply, installation, testing and commissioning double girder EOT crane, 40 ton safe working capacity, Long Travel 24.37 metre, span 12.42 metre (centre to centre distance between rails) and main hoist lift height 08 metre, operation through Radio Remote Control, Pendant push button type (RRC PB) design standard - IS:3177-1999, IS: 807-2006 other relevant standards, duty of crane: Class III M7, shrouded/ MS angle type Down Shop Lead (DSL), Civil/grouting work, cable from Power Distribution Box (PDB) to DSL, cable tray, isolator switch, power supply: 415V AC, 50 Hz, power circuit limit switches with all accessories and components, crane painted with two coat of deep yellow paint confirming to IS 2932:2003 after primer coat followed by chemical treatment complete all as specified and as directed.
Epoxy bond coat: Providing and applying bond coat on the prepared surface to receive new polymer mortar / polymer modified concrete, with two components epoxy based bonding coat in one full coat. Laying of reinforcement polymer mortar or micro concrete shall be completed within the overlay time of bonding coat. This coat act as bonding agent between old and new concrete and also acts as ‘barrier coat’ to the migration of chloride ions from host concrete. Item rate is inclusive of the materials all labour, scaffolding, supervision, tools and tackles and transportation etc. complete as per specification and as directed. Make: BASF, Krishna conchem, Fosroc or equivalent
Polymer Modified Mortar (Pre-Packed): Providing and placing single component, dual shrinkage compensated, ready mixed high strength thixotropic repair mortar (up to 50 mm) as per specification for covering the damaged structural member and reinforcement in desired layer and thickness including scaffolding, curing inclusive of all labour, materials, equipment, scaffolding, etc. complete as per specification and instruction of Engineer in charge . Item rate is inclusive of materials all labour, tools and tackles, scaffolding and transportation etc. complete as per specification and as directed. Make: BASF, Krishna conchem, Fosroc or equivalent
Material and labour for chipping, removing carefully concerete work by low impact hammer, breaker without damaging the structure & cleaning and disposal of debries out side the premisies etc. including errection of double steel scaffolding, covering with green cloth and all the safety masure/precautions and remove the debris outside MD land(as pe directions of BMC) complete all specified and as directed.(Hard concrete should not be removed by force).
Replacement of steel reinforcement with TMT bars of appropriate size where 20% cross section is reduced including diamatntling of rusted steel and application of rust converter FEOVERT and applying protective coating IPNET_RB complete all as specified and directed.
Rebuilding the section of damaged RCC elements to size by providing and casting with microconcrete of grade M-40 and above including all lifts, drilling holes, providing and fixing of watertight framework all lead lift, mixing, placing, deshuttering, levelling the surface by grinding off cementitious slurry or consrtuction joint differences ir any to satisfaction of Engineer-in- charge etc. complete all as directed. Name of majufacturer: BASF/Fosroc/Sika/Dr Fixit.
Taking down existing sub main wiring and making good eisturbed sufrace of walls, floor, floor etc.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitt
ings, fans etc. removing materials to store for keeping in safe custody/deposit with user or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. Notes:- Fans (any type) are to be taken down, blades to be dismantled and handed over to MES all as specified and as directed.
Point
Taking down LT panel of any size complete all as specified and directed Each by Engineer in Charge.
Taking Up/down LT UG Cable of any size including rolling and kept RM aside for disposal action all as directed by Engr In Charge.
Taking down Junction Box/MCB/TPN DB of any type and capacity along Each with all connected accessories complete all as specified and as directed by Engr In Charge.
Taking down Earthing pit along with earth strip complete all as specified.
Subtotal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.41 MB
tenderdocuments8551.pdf
Tender Documents • 2.29 MB
BOQ_826743.xls
BOQ • 1.09 MB
drg3.rar
Additional Documents • 12.43 MB
drg6.rar
Additional Documents • 8.42 MB
drg4.rar
Additional Documents • 13.54 MB
drg5.rar
Additional Documents • 9.18 MB
Download all tender documents and submit your bid