Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.1 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹13.1 L+₹3.2 L (32.1%)Rejected-AOC | L2 | Rejected-AOC L2 Bidder | |
| 3 | L3₹13.2 L+₹3.3 L (33.1%)Rejected-AOC 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | L3 | Rejected-AOC L3 Bidder | |
| 4 | L4₹13.4 L+₹3.5 L (35.2%)Rejected-AOC | L4 | Rejected-AOC L4 Bidder | |
| 5 | L5₹15.1 L+₹5.2 L (52.0%)Rejected-AOC 15 15 KHERIYA BHAN PURANI CHAWANI GWALIOR GWALIOR GWALIOR MADHYA PRADESH 474010 | GWALIOR | MADHYA PRADESH | 474010 | L5 | Rejected-AOC L5 Bidder |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
25 Aug 2021, 6:00 pmClosed
GE I RND Delhi
MILITARY ENGINEER SERVICES, GARRISON ENGINEER (I) RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
REPAIR/ REPLACEMENT OF LT OVERHEAD LINES, LT CABLE AND REPAIR / MAINTENANCE OF EARTHING, MCCBs AND OTHER CONNECTED WORKS AT DRDE GWALIOR UNDER GE I RND DELHI
2021_MES_462159_1
GE/RND-44/GWL/2021-2022
Open Tender
Civil Works
Item Rate
270 days
Gwalior
Class- E, cat b(i)
2 documents required · 2 mandatory
₹500
GE I RND Delhi
₹40,000
Yes
23 Oct 2021
23 Jul 2021
27 Aug 2021
23 Jul 2021
25 Aug 2021
13 Aug 2021
Amount
Restringing of existing ACSR’s conductors and earth wires including cradles, of any description, size & shape and in any position, as in LT/HT overhead lines, on existing poles, including opening of connections and binding wires, restringing and tightening of conductors/earth wire in position, removing sag, binding to insulators with new aluminum wire, making and connecting jumper connections etc. including testing complete all as specified and directed. The quoted rates shall be deemed to include the following provisions also :- (i) Setting/adjusting etc in position of cradles. (ii) Old serviceable spacers of ACSR conductor shall be reused and fixed as directed.
Dismantling & taking down of existing worn out / unserviceable aluminium conductor, steel reinforced (ACSR) of any description /size & in any position from existing LT/HT Poles/Lines complete all as specified & directed.
Supply and fixing of aluminium conductor, steel reinforced (ACSR) of any size/description on LT poles/lines including stringing, tightening, binding to insulators with aluminium wire making and connecting jumpers, connections etc including connecting, commissioning and testing complete all as specified & directed. Note:-Old serviceable spacers obtained from taking down of ACSR conductor under item No 2 shall be reused and fixed as directed
Re-Fixing and stringing of old ACSR’s conductors and earth wires including cradles, of any description, size & shape and in any position, as in LT/HT overhead lines, on existing poles, including opening of connections and binding wires, restringing and tightening of conductors/earth wire in position, removing sag, binding to insulators with new aluminum wire, making and connecting jumper connections etc. including testing complete all as specified and directed. The quoted rates shall be deemed to include the following provisions also :- (i) Setting/adjusting etc in position of cradles. (ii) Old serviceable spacers of ACSR conductor shall be reused and fixed as directed.
Dismantling & taking down of existing worn out / unserviceable GI wire of any description/size & in any position from existing LT/HT Lines including cradle guard wires complete all as specified & directed.
Material and labour for supplying, stringing and fixing GI continuous GI earth wire of size 4 mm / 3.15 mm dia on LT/HT poles as in cradle guards / earth wires etc including binding complete all as specified & directed.
Dismantling & taking out of old existing steel & iron items from poles such as cross arms of channels/sections, bracing, supports, clamps and back plate fabricated from structural steel sections including nuts & bolts, washers of any description and in any position from LT over head line poles/ street light poles complete all as specified & directed.
Fixing Only old serviceable steel & iron ,mild steel such as cross arms, bracing, supports, clamps and back plate fabricated from structural steel sections including nuts & bolts, washers and including painting with one coat of synthetic enamel paint complete all as specified & directed.
Supply, fabrication and fixing for mild steel such as cross arms, bracing, supports, clamps and back plate fabricated from structural steel sections including nuts & bolts, washers welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint of any description of LT over head line poles/ street light poles complete all as specified & directed.
Dismantling & taking out of old existing unserviceable insulators of any description and in any position from LT/HT poles complete all as specified & directed.
Supplying & Fixing single disc assembly for disc type insulator porcelain vitreous 145mm high and 255mm dia ball and socket type, white , brown or green HT 11 KV grade complete all as specified & directed.
Supply and fixing pin type porcelain, vitreous, white, brown or green insulators, including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, 150mm height and 150mm dia suitable for working pressure upto and including 11000 volts grade HT lines fixed on poles complete all as specified & directed.
All as per ser item No 12.00 above but of size 100mm height and 65mm dia suitable for 1100 volts grade LT lines fixed on poles complete all as specified & directed
Supplying & Fixing Shackle type 75mm height and 90mm dia insulator, porcelain, vitreous, white, brown or green including galvanised mild steel strap 31mm X 3mm, insulator bolts 12mm dia with suitable washers and nut, suitable for working pressure upto & including 1100 volts complete all as specified and directed.
Disconnecting, dismantling and taking down existing unserviceable spacers of any description and in any position from the LT electric overhead lines of any height and supplying and fixing new best quality, waterproof & shockproof PVC insulated spacers, 12mm dia flexible type suitable for making / turning to any shape and size (straight or spiral) and suitable for 2 or 3 conductor runs complete all as specified and directed.
All as per srl item No 15.00 above but spacers suitable for five conductors run.
All as per srl item No 15.00 above but PVC insulated straight strip type spacers of width 25 mm suitable for five conductor run overhead lines.
Disconnecting, dismantling & taking out existing unserviceable gang operated switch & Supply, fixing, commissioning and testing of outdoor, gang operated switch, tilting type, 11KV of current rating upto 200 Amps, triple pole, each pole consisting of galvanized steel base, HT insulators as per IS, non ferrous knife and spray, loaded contacts, arcing horns of adequate section to break magnetizing current of the transformers, horizontal GI pipe of adequate length for phase separation, adequate length of GI pipes for operation from ground level and operating handle with locking arrangement complete in both OFF & ON positions. All ferrous parts hot dripped galvanized and non ferrous heavily tinned to with stand weather and suitable for vertical mounting complete all as specified and as directed
Dismantling 11 KV air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for insulators and operating mechanism and repair/replacement of broken/worn out components and insulators etc. complete all as specified and directed. Note :- New spare parts replaced for GOD shall be measured and paid for separately under respective items of Sch 'A' as “supply only” but fixing element of same shall be deemed to be included under this item.
Supply only the following new parts suitable for GOD of 11KV repaired NOTE: - (i) The new parts shall be suitable to match with the existing GOD. (ii) Fixing element of these items is deemed to be included under the rates quoted by the contractor for respective Schedule `A' item No 20 above.
Supply only 11KV post type insulator
Supply only Male contact/moving contact blade.
Supply only Female contact/fix contact Jaw
Supply only MS Jumper carrier
Supply only Tinned copper flexible jumper
Supply only Back connector plate
Dismantling and taking down existing unserviceable lightening arrestor of any capacity and any description.
Supply & fixing, commissioning & testing of Lightning arresters HIGH TENSION 11000 VOLT expulsion type complete with all fittings, transmission class discharge capacity 65 kilo amp confirming to EC-99 -41/1990 including brackets, clamps, bolts, nuts and washers complete all as specified and directed.
Dismantling and taking down existing unserviceable Stay assembly set of any description all as directed
M&L for stay assembly comprising of 16mm dia, 1.80 metre long galvanized stay rod, having 7/3.15mm GI stay wire stranded and 230mm x 230mm x 6mm thick stay plate, complete all as shown on electrical plate No 1 of SSR, Part-I with and including all necessary fittings/ accessories like loop type insulator, stay clamps, necessary excavation and earth work in any type of soil and PCC works in (1:3:6) type C-2 (using 40mm graded stone aggregate) including taking down and dismantling old unserviceable stay assembly etc complete all as specified and directed.
All as per srl item No 24.00 above but stay assembly having stay rod of 20mm dia and 2.15 metre long with 300mm x 500mm x 6mm thick MS plate.
Trimming/cutting of all trees branches and cleaning of bushes upto 2 metre distance both side from nearest conductor/Earth wire at LT/HT overhead line including cleaning of site and depositing of material upto 250 metre distance complete all as specified & directed.
Surface excavation,grass cutting over the areas around the poles/feeder piller boxes/ sub stations not exceeding 15cm depth including cleaning the bushes and vegetation/root of small trees and leveling incl removal of surplus soil in soft/hard dense soil and deposited complete all as specified & directed.
Dismantling and taking down existing unserviceable/worn out danger notice plate of any description& any position and supply & fixing for danger notice plate 20x15 cm size and 1.6 mm thick mild steel vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT complete complete all as specified and directed.
M&L for PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) including demolition of existing as in coping including necessary form work or in any situation complete all as specified and directed.
Supply and Fixing in repair PG Clamp by Compression/crimping type sleeve joints for jointing conductors /jumper connections including treatment with conducting jelly complete all as specified and directed.
Supply and Fixing in repair Vice type connectors consisting of two brass plates, and two steel bolts and nuts for 2 conductors of equal or unequal sizes, for non-tension connections 'including treatment of connector and ACSR conductor with conducting jelly complete all as specified and directed.
Dismantling & Taking down Old Anti climbing devices and Supply and Fixing For Anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered. Note : Clamps shall be measured & paid seperately
Disconnecting, taking out and removing old existing unserviceable underground, LT cable of any description and in any position complete including taking down protection pipe, PCC Cover/Bricks etc of following sizes complete all as specified and directed.
35 Sqmm to 70 Sqmm any core
95 Sqmm to 150 Sqmm any core
185 Sqmm to 300 Sqmm any core
Relaying only old serviceble cable , jointing and testing any description and any size laid in trenches/ducts, floors, fixed to walls etc of following sizes complete all as specified and directed
35 Sqmm to 70 Sqmm any core
95 Sqmm to 150 Sqmm any core
Supply, laying, jointing and testing XLPE insulated, armoured, heavy duty, aluminum conductor cable 1100 volts grade of any description laid in trenches/ ducts, floors, fixed to walls etc following sizes complete all as specified and directed for the following sizes :-
35 Sqmm 3.5 core
50 Sqmm 3.5 core
70 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
150 Sqmm 3.5 core
185 Sqmm 3.5 core
300 Sqmm 3.5 core
Excavation in trenches in soft loose soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as specified and directed. Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers.
Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed
Removal of surplus excavated soil exc. 50 mtr but n. exc. 250 mtr distance and depositing where directed at a level not exceeding 1.5 M above the starting point etc complete all as specified & directed.
M & L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed . NOTE: - Punned thickness shall be measured & paid seperately.
Supplying & Laying Sub Class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection complete all as specified and directed
Laying only old serviceable Sub Class `B’ bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection complete all as specified and directed
Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified & directed.
All as per srl item No 42.00 above but 2.5 mm thick for voltage upto 11 KV (size 2mx1m).
S&F in repair MCCB 3 pole , 125 Amps, 415 Volts, 36 KA breaking capacity incuding connected accessories, spreader terminals and connection on existing DPX box complete all as specified & directed
S&F in repair MCCB, 3 Pole ,415 V , 160 Amp Adjustable type with breaking capacity 36 KA incuding connected accessories, spreader terminals Model DPX 160 complete all as specified and as directed.
S&F in repair MCCB, 3 Pole ,415 V , Adjustable type,, 250 Amp with breaking capacity 25 KA incuding connected accessories, spreader terminals Model DPX 250 complete all as specified and as directed.
S&F in repair MCCB, 3 Pole ,415 V ,Adjustable type, 400 Amp with breaking capacity 36 KA incuding connected accessories, spreader terminals Model DPX 400 complete all as specified and as directed.
Material and Labour for earthing complete with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not less than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with galvanised iron strip of 25x4 mm by means of Copper nuts, bolts and washers. Strip laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) with following complete all as specified and shown in electrical plate No 3 of SSR Part-I & testing on completion :- (a) GI strip of size 25mm x 4mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) Excavation & earthwork in any type of soil PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 50mm thick 1:2:4 type B1 reinforced with 8mm dia mild steel bar 75mm centre to centre with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover.
Supply and fixing in repair LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp all as specified and directed.
Supply and fix in repairs Automatic Transfer Switch, 3 phase , 4 pole , AC, 415 Volts 160 Amps rating within enclosure with controller and complete protection for Automatic or manual operation complete all as specified and directed.
S&F in repairs ON load changeover switch with phase Barriers & Handle with door interlock kit and electrical interlocking , with SS enclosure 400 Amps, 4 Pole, 415 V, AC, 50 Hz complete all as specified & directed.
Supply and fixing in repair Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones insignal red colour and fixed with M.S. clamps, bolts and nuts of approved size for HT, 25x20cm size complete all as specified and directed.
M & L for preparation of old painted surfaces of steel tubular pole of 9/11 mtr strut pole (LT/HT) including protection pipe, cross arms, clamps, GI pipe bracket of street/ security light , anti climbing devices etc. including scraping out old rusted paint and applying one coat of red oxide primer and two coat of aluminium paint on all the metallic surfaces all as specified & directed by Engineer -in-Charge. Note:-(Numbering of the poles and repainting blue bands shall be done with synthetic enameled paint, letter/ band's shape & size shall be directed by Engr-in-Charge).
Supply, installation, Commissioning and testing LT panel board of size 1540mmx1200mmx500mm (approximate) as approved for 3 phase, 4 wire, 415 Volts ,AC , 50 Hz supply, Indoor cubical type Double door, dust and vermin proof, pedestal mounting type suitable for Indoor applications having suitable shape/ size, made out of 3.15 mm thick MS sheet with using 40mm x 40mm x 5mm angle iron frame and supports, duly finished with powder coated using two coats of synthetic enamel paint of approved colour over a coat of red oxide primer all over steel surfaces complete with separate compartment of suitable shape and size with shutter and locking arrangement for each switchgear and including PCC work for fixing panel legs. Bus bar of aluminium conductor suitable shape and size for 3 phase rating of 800 amps and for nuetral 600 Amps rating including taking out end connectinons of the existing cables and fixing the cable with the panel using new lugs and glands of suitable size, separate cable alley for outgoing cables including following switchgear & controls,CPRI approved, complete all as specified and directed
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 25x4 mm galvanised iron strip complete all as specified and directed.
Mukesh Enterprises
GUPTA ENGINEERING WORKS
M/S STEAD FAST
AUTOMATION AND SWITCHGEAR PANELS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .