| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.9 LAccepted-AOC | L1 | Accepted-AOC Accepted being lowest bidder | |
| 2 | L2₹43.4 L+₹7.0 L (19.1%)Rejected-Finance | L2 | Rejected-Finance Rejected being not lowest bidder | |
| 3 | L3₹46.2 L+₹9.8 L (26.8%)Rejected-Finance | L3 | Rejected-Finance Rejected being not lowest bidder |
Tender Value
₹44.7 L
EMD Value
₹89,400
Closing Date
15 Mar 2021, 6:00 pmClosed
CWE KIRKEE
Headquarters CWE Kirkee, Military Engineer Services, Range Hills Road, Kirkee, Pune-411003
SPECIAL REPAIR/REPLACEMENT OF HT UNDER GROUND CABLES AND ALL ALLIED WORKS AT MAIN POWER HOUSE 512 ABW UNDER AGE E / M UNDER GE(C) KIRKEE
2021_MES_422826_1
CWE/KKE/TOKEN-74 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KIRKEE
As per tender documents
5 documents required · 5 mandatory
₹500
Yes
GE CENTRAL KIRKEE
₹89,400
Yes
15 Apr 2021
16 Feb 2021
17 Mar 2021
16 Feb 2021
15 Mar 2021
2 Mar 2021
17 Feb 2021 - 22 Feb 2021
Amount
Disconnecting old HT UG cable from panels ,cutting and taking away /removing of from open trenches in peaces up to outside of sub stns and up to transformer of size 120 sqmm 3 core.complete all as specified and as directed. NOTE :- (a) Removing of cables and credit has not been consdiered for complete qty because the cost of removing shall be more than the cost of old material hence only open cables are concidered for removal and credit schedule.(b) The cable root is almost under the road or under the PCC between bldg and road hence removing of old cable is will also involed cutting and repair of road , PPC further increasing the cost
Disconnecting old HT UG cable from panels ,cutting and taking away /removing of from open trenches in peaces up to outside of sub stns and up to transformer of size 300 sqmm 3 core complete all as specified and as directed. NOTE :- (a) Removing of cables and credit has not been consdiered for complete qty because the cost of removing shall be more than the cost of old material hence only open cables are concidered for removal and credit schedule.(b) The cable root is almost under the road or under the PCC between bldg and road hence removing of old cable is will also involed cutting and repair of road , PPC further increasing the cost
Excavation in trenches n. exc 1.5 m wide and n. exc 1.5 mtr depth n exc 10 sqm on plan ffor taking out cable etc for repairs / laying cables etc and getting out in hard/dense soil complete all as specified and as directed.
Returning filling in including spreading, levelling, watering and well ramming in layers n.exc. 25cm in soils complete all as specified and as directed.
Removing excavated material( soil) to a distance not exceeding 50mtr and depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified and as directed.
M&L for stone dust cushioning to under ground cable in trenches including spreading levelling hand punning and consolidating complete all as specified and directed (Note: Thickness after punning down shall be measured and paid)
Supply and laying of un-reinforced prcast concrete cable cover, class HV, Type 1 with peak, size 300mm x 180mm x40mm complete all as specified and directed
M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed. NOTE - (a). Cost of cutting out of trench for accomodating the machine and making good to the surface after completion of the job are deemed to be inclusive in the quoted rate. (b). Contractor has to rectify any damage to cables, pipes or other govt. property free of cost to the complete satisfaction of Engr-in-Charge. (c). Any extra excavation or the any other connected jobs required other than as mentioned in the scope of work will be measured and paid under the relevant items of this schedule.
Supply, laying in trenches /ducts/fixing on pole ,Str/ in boar with suitable size of GI clamps made out of GI strip, XLPE insulated, screened, earthed, PVC bedded, galvanised steel strip armoured, electric power cable (heavy duty) of size 3 x 120 sqmm with aluminium conductor suitable for 22 KV (E) grade as per relevent IS including latest amendment for IS testing, commissionong along with and including S&F for HT cable route indicator for every 100 m or at turning with suitable PCC Foundation complete all as specified and directed Note:- (a) Earth work, EHV cable cover, sand coushioning & GI pipe will be measured and paid seperately. (b) High voltage test to be conducted at site with suitable voltage before and after laying of HT cable and reading shall be recorded jointly and test report to be submitted in triplicate to the Engineer-in-Charge. The cost of the same shall be deemed to be included in the unit rate quoted above . (C) The cost of straight through joint required for laying of new cable cotineously shall be inclued in the rate of cable in RM.
Supply, laying in trenches /ducts/fixing on pole ,Str/ in boar with suitable size of GI clamps made out of GI strip, XLPE insulated, screened, earthed, PVC bedded, galvanised steel strip armoured, electric power cable (heavy duty) of size 3 x 300 sqmm with aluminium conductor suitable for 22 KV (E) grade as per relevent IS including latest amendment for IS testing, commissionong along with and including S&F for HT cable route indicator for every 100 m or at turning with suitable PCC Foundation complete all as specified and directed Note:- (a) Earth work, EHV cable cover, sand coushioning & GI pipe will be measured and paid seperately. (b) High voltage test to be conducted at site with suitable voltage before and after laying of HT cable and reading shall be recorded jointly and test report to be submitted in triplicate to the Engineer-in-Charge. The cost of the same shall be deemed to be included in the unit rate quoted above . (C) The cost of straight through joint required for laying of new cable cotineously shall be inclued in the rate of cable in RM.
M&L in repairs Heat shrinkable indoor type end termination cable jointing kit suitable for earthed 3 core 120/150 sqmm HT 22KV XLPE aluminium conductor cable incld.testing and commissioning of the complete cable to the complete satisfaction of Engr-in-Charge all as specified and directed. Make:- Raychem/M-Seal/Denson. NOTE- a. The quoted rate is deemed to be inclusive of cost of saddling or clamping of cable all as directed by Engr-in-Charge.
M&L in repairs Heat shrinkable outdoor type end termination cable jointing kit suitable for earthed 3 core 120/150 sqmm HT 22KV XLPE aluminium conductor cable incld.testing and commissioning of the complete cable to the complete satisfaction of Engr-in-Charge all as specified and directed. Make:- Raychem/M-Seal/Denson. NOTE- a. The quoted rate is deemed to be inclusive of cost of saddling or clamping of cable all as directed by Engr-in-Charge.
M&L in repairs Heat shrinkable indoor type end termination cable jointing kit suitable for earthed 3 core 300 sqmm HT 22KV XLPE aluminium conductor cable incld.testing and commissioning of the complete cable to the complete satisfaction of Engr-in-Charge all as specified and directed. Make:- Raychem/M-Seal/Denson. NOTE- a. The quoted rate is deemed to be inclusive of cost of saddling or clamping of cable all as directed by Engr-in-Charge.
M&L in repairs Heat shrinkable outdoor type end termination cable jointing kit suitable for earthed 3 core 300 sqmm HT 22KV XLPE aluminium conductor cable incld.testing and commissioning of the complete cable to the complete satisfaction of Engr-in-Charge all as specified and directed. Make:- Raychem/M-Seal/Denson. NOTE- a. The quoted rate is deemed to be inclusive of cost of saddling or clamping of cable all as directed by Engr-in-Charge.
M&L in repairs Heat shrinkable straight through cable jointing kit suitable for earthed 3 core 150/120 sqmm HT 22KV XLPE aluminium conductor cable incld. disconnecting concerned cable, cutting out burnt/damaged jointing kit, jointing new kit inld. testing and commissioning of the complete cable to the complete satisfaction of Engr-in-Charge all as specified and directed. Make:- Raychem/ XICON/ M-Seal/Denson. NOTE- (a). The quoted rate is deemed to be inclusive of cost of saddling or clamping of cable all as directed by Engr-in-Charge. (b). Contractor has to arrange proper electrical shutdown after informing to depratment concerned. (c). Cost of connected excavation, soil removal, returning filling in, sand cusshioning and cable covers will be measured and paid in the respective items of the Schedule.
M&L in repairs Heat shrinkable straight through cable jointing kit suitable for earthed 3 core 300 sqmm HT 22KV XLPE aluminium conductor cable incld. disconnecting concerned cable, cutting out burnt/damaged jointing kit, jointing new kit inld. testing and commissioning of the complete cable to the complete satisfaction of Engr-in-Charge all as specified and directed. Make:- Raychem/ XICON/ M-Seal/Denson. NOTE- (a). The quoted rate is deemed to be inclusive of cost of saddling or clamping of cable all as directed by Engr-in-Charge. (b). Contractor has to arrange proper electrical shutdown after informing to depratment concerned. (c). Cost of connected excavation, soil removal, returning filling in, sand cusshioning and cable covers will be measured and paid in the respective items of the Schedule.
M &L GI pipe light grade for protection of cable laid under floor, clamped on wall,laid under road cross etc of bore 100 mm complete all as specified and as directed.
Supply, laying in trenches /ducts/fixing on pole ,Str/ in boar with suitable size of GI clamps made out of GI strip, XLPE insulated, screened, earthed, PVC bedded, galvanised steel strip, electric power cable (heavy duty) of size 6 core x 2.5 sqmm with copper conductor suitable for 1100 Volt grade as per relevent IS including latest amendment for IS testing, commissionong to laid along with HT cable complete all as specified and directed
Supply, laying in trenches /ducts/fixing on pole ,Str/ in boar with suitable size of GI clamps made out of GI strip, XLPE insulated, screened, earthed, PVC bedded, galvanised steel strip, electric power cable (heavy duty) of size 12 core x 2.5 sqmm with copper conductor suitable for 1100 Volt grade as per relevent IS including latest amendment for IS testing, commissionong to laid along with HT cable complete all as specified and directed
Supply, laying in trenches /ducts/fixing on pole ,Str/ in boar with suitable size of GI clamps made out of GI strip, XLPE insulated, screened, earthed, PVC bedded, galvanised steel strip, electric power cable (heavy duty) of size 19 core x 2.5 sqmm with copper conductor suitable for 1100 Volt grade as per relevent IS including latest amendment for IS testing, commissionong to laid along with HT cable complete all as specified and directed
NOTE for item no 18 to 20 above:- (a) Removing of cables and credit has not been conseedered for complete qty because the cost of removing shall be more than the cost of old material hence only open cables are concidered for removal and credit schedule .(b) The cable root is almost under the road or under the PCC between bldg and road hence removing of old cable is will also involed cutting and repair of road , PPC further increasing the cost
Pritam Electro Mechanical Services
Mahindra Electric Stores
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .