Executive Engineer
electy 400 Kv S S Div Banda
Work of Supply and fixing of Smoke Detection System for 400 KV ACDB, DCDB , RELAY panel at 400 KV S/S Banda
2023_UPTCL_854684_1
T-20/E.400KVS/SDIV.(B)/2023-24
Open Tender
Electrical Works
Lump-sum
electy. 400 Kv S S Div Banda
Detail Enclosed
2 documents required · 2 mandatory
₹590
Executive engineer
₹4,000
3 Nov 2023
23 Oct 2023
3 Nov 2023
23 Oct 2023
3 Nov 2023
23 Oct 2023
23 Oct 2023 - 3 Nov 2023
Amount
Description of Works
Supply of Ionisation type Smoke Detector , the detector shall be sesitive to all type of smokes, will be sensitive to amount of light, air drafts and changes with the operating temprature and volatge ranges. The detector shall meet the requirement of either EN54/FMUL or LPC and shall be specifically approved by FM/UL/LPCB Apollo/System Sensor/Edward/Bosch.
Supply of Response Indicator lamp assembly consisting of lamp holder and lamp shall be suitable for mounting on walls partition etc. The housing shall be suitable for surface/Flush monting on walls on 1.5 mm thick steel sheet and facia 03 mm acrylic mounted outside a Kiosk and directly connected to detector
Supply of heat Detector (for battery room) it is combination of rate of rise & fixied temprature prinicpal using & with automatice compenasation for changes of ambient condtions. The themral detectors are rested and approved to (FN54 part 5/2000) class air apollo/system sensor/edward/Bosch
Supply of Fire Siron going to 02 Km away.
Supply and laying of of (150mtr) of 2x1.5 sq. mm. PVC insulated and seathed standard copper wire, wiring for fire alarm system in general shall comply with IS-2189 and IS-732 ammended up to date. The Detectors shall be wired by ISI marked 1.5 sq. mm. PVC Insulated standard FRLS copper conductor wires of 1100 volts grade requiored and desired on site. Crimping type of lugs are also included in the rates of laying of wires and its connections PVC insulated copper conductor wire shall confirm to IS:694. the work also include to add new fire system to existing system install at control room(ACDB, DCDB, DC CHARGER) , SPR (CONTROL AND RELAY panels) and rectify the probem of any problem occur in old fire sytem.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
M/S SAI RAM ENTERPRISES
V K BACKUP SOLUTIONS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .