Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.0 LAccepted-AOC | ₹21.0 L Quoted ₹21.5 L | L1 | Accepted-AOC Being L1 bidder |
| 2 | L2₹23.0 LRejected-Finance H NO 29 DEVILAL COLONY TCP 2 HISAR CANTT HARYANA | HISAR | HISAR | HARYANA | 125006 | ₹23.0 L | L2 | Rejected-Finance Being L2 bidder |
| Sl No | Description | Qty | Unit | M/s Devendera construction L2 | FOUJI ELECTRIC WORKS L1 |
|---|---|---|---|---|---|
| 1.00 | Provide annual maintenance for 2x150 TR , Model: LCW2-160xx01536201, WC R134A screw compressor type water cooled chilling machines shall check and render preventive maintenance service to all the equipment every 3 months i.e three times during the currency of the contract complete all as specified and directed.
Operation Parametres : Chiller : Water Temperature IN - 54 F, Water Temperature OUT - 44 F , Fouling Factor - 0.0005 FPS
Condenser : Water Temperature IN - 90 F , Water Temperature OUT - 97.5 F , Fouling Factor - 0.001 FPS IKW/TR should not exceed 0.70 at full load , COP value should not exceed as mentioned in latest ECBC guidelines.
Note :- Each service will include the following deemed to be included in the quoted rate and the work shall be carried out by OEM i.e Blue Star Limited at Plant only. (a) Dismantling /transporations and refixing /installation.
(b) Checking the functioning of chiller unit & It's controls and all such equipment. (c) Free replacing of defective/worn out parts with new or repaired parts for compressor/thermostat/cut outs based.
(d) Repairng of equipment as listed in the equipment list at plant as the case may be. (e) Descaling of condensers with chemical replacement of pre filters based on assessment and working parameters of the plant.
(f) Replenishing refrigerant gas and compressor oil in the system arising out of system defect. (g) checking of compressor for its proper working.
(h) Annual pumping - down and restarting as and when required.
(j) Checking of Microprocessor control panel, control boards, transducers of chiller unit for their correctness and replace if necessary.
(k) Replacing of parts due to normal wear and tear. | 1 | Each Job | 3,00,000 ₹3 L | 2,25,000 ₹2.3 L |
| 2.00 | Provide annual maintenance for 3 X 80 TR , reciprocating compressors model no :90023386,90023387,90023416 type water cooled chilling machines shall check and render preventive maintenance service to all the equipment every 3 months i.e three times during the currency of the contract complete all as specified and directed.
Operation Parametres : Chiller : Water Temperature IN - 54 F, Water Temperature OUT - 44 F , Fouling Factor - 0.0005 FPS
Condenser : Water Temperature IN - 90 F , Water Temperature OUT - 97.5 F , Fouling Factor - 0.001 FPS IKW/TR should not exceed 0.70 at full load , COP value should not exceed as mentioned in latest ECBC guidelines.
Note :- Each service will include the following deemed to be included in the quoted rate and the work shall be carried out by OEM i.e VOLTAS at Plant only. (a) Dismantling /transporations and refixing /installation.
(b) Checking the functioning of chiller unit & It's controls and all such equipment. (c) Free replacing of defective/worn out parts with new or repaired parts for compressor/thermostat/cut outs based.
(d) Repairng of equipment as listed in the equipment list at plant as the case may be.
(e) Descaling of condensers with chemical replacement of pre filters based on assessment and working parameters of the plant.
(f) Replenishing refrigerant gas and compressor oil in the system arising out of system defect.
(g) checking of compressor for its proper working.
(h) Annual pumping - down and restarting as and when required.
(j) Checking of Microprocessor control panel, control boards, transducers of chiller unit for their correctness and replace if necessary.
(k) Replacing of parts due to normal wear and tear. | 1 | Each Job | 1,40,000 ₹1.4 L | 1,75,000 ₹1.8 L |
| 3.00 | Provide annual maintenance for 3 X 26TR , Model: LCW2-160xx01536201, WC R 407C twin scroll compressor type water cooled chilling machines shall check and render preventive maintenance service to all the equipment every 3 months i.e three times during the currency of the contract complete all as specified and directed.
Operation Parametres : Chiller : Water Temperature IN - 54 F, Water Temperature OUT - 44 F , Fouling Factor - 0.0005 FPS
Condenser : Water Temperature IN - 90 F , Water Temperature OUT - 97.5 F , Fouling Factor - 0.001 FPS IKW/TR should not exceed 0.70 at full load , COP value should not exceed as mentioned in latest ECBC guidelines.
Note :- Each service will include the following deemed to be included in the quoted rate and the work shall be carried out by OEM i.e Blue Star Limited at Plant only. (a) Dismantling /transporations and refixing /installation.
(b) Ch+E9ecking the functioning of chiller unit & It's controls and all such equipment.
(c) Free replacing of defective/worn out parts with new or repaired parts for compressor/thermostat/cut outs based.
(d) Repairng of equipment as listed in the equipment list at plant as the case may be.
(e) Descaling of condensers with chemical replacement of pre filters based on assessment and working parameters of the plant.
(f) Replenishing refrigerant gas and compressor oil in the system arising out of system defect.
(g) checking of compressor for its proper working.
(h) Annual pumping - down and restarting as and when required.
(j) Checking of Microprocessor control panel, control boards, transducers of chiller unit for their correctness and replace if necessary.
(k) Replacing of parts due to normal wear and tear. | 1 | Each Job | 1,50,000 ₹1.5 L | 75,000 ₹75,000 |
| 4.00 | Provide annual maintenance for 3 x 39 TR , model: 79339AL14,79339B L14,79339CL14 screw compressor type water cooled chilling machines shall check and render preventive maintenance service to all the equipment every 3 months i.e three times during the currency of the contract complete all as specified and directed.
Operation Parametres : Chiller : Water Temperature IN - 54 F, Water Temperature OUT - 44 F , Fouling Factor - 0.0005 FPS
Condenser : Water Temperature IN - 90 F , Water Temperature OUT - 97.5 F , Fouling Factor - 0.001 FPS IKW/TR should not exceed 0.70 at full load , COP value should not exceed as mentioned in latest ECBC guidelines.
Note :- Each service will include the following deemed to be included in the quoted rate and the work shall be carried out by OEM i.e BLUE STAR at Plant only. (a) Dismantling /transporations and refixing /installation.
(b) Checking the functioning of chiller unit & It's controls and all such equipment. (c) Free replacing of defective/worn out parts with new or repaired parts for compressor/thermostat/cut outs based.
(d) Repairng of equipment as listed in the equipment list at plant as the case may be.
(e) Descaling of condensers with chemical replacement of pre filters based on assessment and working parameters of the plant.
(f) Replenishing refrigerant gas and compressor oil in the system arising out of system defect.
(g) checking of compressor for its proper working.
(h) Annual pumping - down and restarting as and when required.
(j) Checking of Microprocessor control panel, control boards, transducers of chiller unit for their correctness and replace if necessary.
(k) Replacing of parts due to normal wear and tear. | 1 | Each Job | 1,50,000 ₹1.5 L | 1,05,000 ₹1.1 L |
| 5.00 | Provide annual maintenance for 3 X 7.5 TR , Pakage type AC plantModel: D000031,D000032,D3000033 water cooled chilling machines shall check and render preventive maintenance service to all the equipment every 3 months i.e three times during the currency of the contract complete all as specified and directed.
Operation Parametres : Chiller : Water Temperature IN - 54 F, Water Temperature OUT - 44 F , Fouling Factor - 0.0005 FPS
Condenser : Water Temperature IN - 90 F , Water Temperature OUT - 97.5 F , Fouling Factor - 0.001 FPS IKW/TR should not exceed 0.70 at full load , COP value should not exceed as mentioned in latest ECBC guidelines.
Note :- Each service will include the following deemed to be included in the quoted rate and the work shall be carried out by OEM i.e VOLTAS at Plant only. (a) Dismantling /transporations and refixing /installation.
(b) Checking the functioning of chiller unit & It's controls and all such equipment. (c) Free replacing of defective/worn out parts with new or repaired parts for compressor/thermostat/cut outs based.
(d) Repairng of equipment as listed in the equipment list at plant as the case may be. (e) Descaling of condensers with chemical replacement of pre filters based on assessment and working parameters of the plant.
(f) Replenishing refrigerant gas and compressor oil in the system arising out of system defect. (g) checking of compressor for its proper working.
(h) Annual pumping - down and restarting as and when required.
(j) Checking of Microprocessor control panel, control boards, transducers of chiller unit for their correctness and replace if necessary.
(k) Replacing of parts due to normal wear and tear. | 1 | Each Job | 40,000 ₹40,000 | 50,000 ₹50,000 |
| 6.00 | M&L for re-winding of electric motor 15 to 20 HP, 415 volts 3 phase, 50 Hz with super enamelled copper wire of superior quality as per existing gauge incl varnishing insulating material complete and replacement of defective bearing, greasing, oiling etc incl re-assembling, transporting, fixing in position, making connection, commissioning & testing complete all as specified and directed. | 3 | Each | 8,500 ₹25,500 | 9,000 ₹27,000 |
| 7.00 | Description all as per item No 6.00 above but 7.5 to 10 HP Motor. | 3 | Each | 5,500 ₹16,500 | 6,550 ₹19,650 |
| 8.00 | Description all as per item No 6.00 but 3 to 5 HP Motor. | 2 | Each | 3,200 ₹6,400 | 4,000 ₹8,000 |
| 9.00 | S&F in replacement of fan blade assembly suitable for 3 to 10 HP motor complete all as specified and directed. | 2 | Each | 500 ₹1,000 | 400 ₹800 |
| 10.00 | Description all as per item No 9.00 above but for 15 to 20 HP motor. | 2 | Each | 600 ₹1,200 | 750 ₹1,500 |
Updated dates
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
19 Mar 2026, 6:00 pmClosed
GE (W)
GE (W) HISAR HISAR MIL STN
CA NO. GE(W)/HSR-62/2025-26 REPAIR/ANNUAL MAINTENANCE OF CENTRAL AIR CONDITIONING PLANT AT HISAR MIL STN UNDER GE (W) HISAR
2026_MES_753277_1
CA NO. GE(W)/HSR-62/2025-26
Open Tender
Civil Works
270 days
HISAR
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (W) HISAR
₹80,000
GE (W) HISAR
27 Apr 2026
19 Feb 2026
21 Mar 2026
19 Feb 2026
19 Mar 2026
5 Mar 2026
20 Feb 2026 - 27 Feb 2026
27 Feb 2026
M&L for re-winding of electric motor 15 to 20 HP, 415 volts 3 phase, 50 Hz with super enamelled copper wire of superior quality as per existing gauge incl varnishing insulating material complete and replacement of defective bearing, greasing, oiling etc incl re-assembling, transporting, fixing in position, making connection, commissioning & testing complete all as specified and directed.
Description all as per item No 6.00 above but 7.5 to 10 HP Motor.
Description all as per item No 6.00 but 3 to 5 HP Motor.
S&F in replacement of fan blade assembly suitable for 3 to 10 HP motor complete all as specified and directed.
Description all as per item No 9.00 above but for 15 to 20 HP motor.
Supply & fixing in replacement Chilled water PVC water storage tank 500 Ltr complete all as specified and directed by Enger in charge.
S & F in replacement GI sheet ducting made out of 22/24 gauge as per 655 complete with support gas kit & nuts, bolts etc complete with pigwool insulation, chickenmesh and thermal insulation complete all as specified and directed.
S & F in replacement of V belt type A-40/1016(IS) for AHU NO 01 suitable for blower motor complete all as specified and directed. Make : Fenner / Unigrip / Delta premium or equivalent.
S & F in replacement of V belt type A-12042 LP/A-46(IS) for AHU NO 02, suitable for blower motor complete all as specified and directed. Make : Fenner / Unigrip / Delta premium or equivalent.
S & F in replacement of V belt type A-525LP/A-35(IS) for AHU NO 03, suitable for blower motor complete all as specified and directed. Make : Fenner / Unigrip / Delta premium or equivalent.
S & F in replacement of V belt type B 1872 LP/B-72 for AHU NO 04, suitable for blower motor complete all as specified and directed. Make : Fenner / Unigrip / Hercules premium or equivalent.
S & F in replacement of V belt type B 1618 LP/B-62 (IS)for AHU NO 05, suitable for blower motor complete all as specified and directed. Make : Fenner / Unigrip / Delta premium or equivalent.
S & F in replacement of oil pressure transducer (sensor) for Voltas / bluestar make or as required on existingsite Micro: Processor of 150 TR chilling unit complete all as specified and directed.
S & F in replacement of suction pressure transducer (sensor) for Voltas/ bluestar make or as required on existing site Make : Micro Processor of 150 TR chilling unit complete all as specified and directed.
S & F in replacement of discharge pressure transducer (sensor) for Voltas/ bluestar make or as required on existing site : Micro Processor of 150 TR chilling unit complete all as specified and directed.
S & F in replacement of thermostatic expansion valve for 150 TR chilling unit as required on existing site complete all as specified and directed. Make : Sporlon/Danfoss
S & F in replacement of oil pressure transducer (sensor) for Voltas/bluestar make or as required on existingsite Micro: Processor of 80TR chilling unit complete all as specified and directed.
S & F in replacement of suction pressure transducer (sensor) for Voltas/ bluestar make or as required on existing site Make : Micro Processor of 80 TR chilling unit complete all as specified and directed.
S & F in replacement of discharge pressure transducer (sensor) for Voltas/ bluestar make or as required on existing site : Micro Processor of 80 TR chilling unit complete all as specified and directed.
S & F in replacement of thermostatic expansion valve for 80 TR chilling unit as required on existing site complete all as specified and directed. Make : Sporlon/Danfoss
S & F in replacement of oil pressure transducer (sensor) for Voltas/bluestar make or as required on existingsite Micro: Processor of 39 TR/26 TR chilling unit complete all as specified and directed.
S & F in replacement of suction pressure transducer (sensor) for Voltas/ bluestar make or as required on existing site Make : Micro Processor of 39 TR/26 TR chilling unit complete all as specified and directed.
S & F in replacement of discharge pressure transducer (sensor) for Voltas/ bluestar make or as required on existing site : Micro Processor of 39 TR /26 TR chilling unit complete all as specified and directed.
S & F in replacement of thermostatic expansion valve for 39 TR/26 TR chilling unit as required on existing site complete all as specified and directed. Make : Sporlon/Danfoss
S & F in replacement of high flow HEPA filter in aluminium frame as per existing of min size 24"x24" complete all as specified and directed. Make : Athletic or thermo dyne
S & F in replacement of high flow HEPA filter in aluminium frame as per existing of min size 36"x36" complete all as specified and directed. Make : Athletic or thermo dyne
S & F in replacement of butter fly valve of size 80 mm ISI marked including testing complete all as specified and directed. Make : Castle / CGR
S & F in replacement of butter fly valve of size 100 mm to 100mm ISI marked including testing complete all as specified and directed. Make : Castle / CGR
S & F in replacement of NRV valve 100mm dia for chiller line and condenser line complete all as specified and directed. Make : Castle/ CGR
S & F in replacement of NRV valve 80mm dia for chiller line and condenser line complete all as specified and directed. Make : Castle/ CGR.
S & F in replacement of coupling tyre, type TC-011 suitable for 20 HP motor coupling with 150 TR condenser pump central AC plant complete all as specified and directed. Make : Unique QE or equivalent.
S & F in replacement of coupling tyre, type TC-011 suitable for 15 HP motor coupling with 80TR condenser pump central AC plant complete all as specified and directed. Make : Unique QE or equivalent.
S & F in replacement of coupling tyre, type TC-011 suitable for 10 HP motor coupling with 39/TR/26TR condenser pump central AC plant complete all as specified and directed. Make : Unique QE or equivalent.
M&L for Insulation for chiller water pipe line by 40mm thick rigid expanded polysterene having density of 16 Kg per Cum factory phased on inside with aluminium foil on outside reinforced with craft paper and fused to the insulation material suitable for 80mm/100mm/125mm including thoroughly cleaning of existing insulation with a wire brush and rendered free from old rushed and greased and applying a coat of red oxide primer and two coat of black bituminus paint over chilled water pipe of at any position/location complete all as specified and directed.
S & F in replacement of MCCB with fixed thermal magnetic setting, 415 volts, rupturing cap 25KA of capacity 200 Amps 3 pole complete all as specified and directed. Make : Schneider(MG) / ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replacement of MCCB with fixed thermal magnetic setting, 415 volts, rupturing cap 25KA of capacity 160 Amps 3 pole complete all as specified and directed. Make : Schneider(MG) / ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replacement of MCCB with fixed thermal magnetic setting 415 volts, rupturing cap 25KA of capacity 100 Amps 3 pole complete all as specified and directed. Make : Schneider / ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replacement of MCCB with fixed thermal magnetic setting 415 volts, rupturing cap 16KA of capacity 63 Amps 4 pole as per existing complete all as specified and directed. Make : Schneider /ABB/L&T or equivalent of makes as mentioned in Appx 'C' here-in-after.
S & F in replece PVC/ polycarbonate type insulated connector aluminium with lugs suitable for XLPE cable size for 16 Sqmm to 50 Sqmm size complete all as specified and directed.
S & F in replece PVC/ polycarbonatetype insulated connector aluminium with lugs suitable for XLPE cable size for 70 Sqmm to 95 Sqmm size complete all as specified and directed.
M & L for painting AC plant of capacity 2 X 150 TR and including preparation/scraping of old painted surface and repainting with two coats of synthetic enamel paint (superior quality) Blue colour or as required on site complete all as specified and directed.
M & L for painting AC plant of capacity 2 x 80 TR + 1 x 80 TR and including preparation/scraping of old painted surface and repainting with two coats of synthetic enamel paint (superior quality) Blue colour or as required on site complete all as specified and directed.
M & L for painting AC plant of capacity 2 x 39 TR + 1 x 39 TR and including preparation/scraping of old painted surface and repainting with two coats of synthetic enamel paint (superior quality) Blue colour or as required on site complete all as specified and directed.
M & L for painting AC plant of capacity 2 x 26 TR + 1 x 26 TR and including preparation/scraping of old painted surface and repainting with two coats of synthetic enamel paint (superior quality) Blue colour or as required on site complete all as specified and directed.
M & L for painting AC plant of capacity 2 x 7.5 TR + 1 x 7.5 TR and including preparation/scraping of old painted surface and repainting with two coats of synthetic enamel paint (superior quality) Blue colour or as required on site complete all as specified and directed.
S & F in replacement monoblock tullu pump LHP 240, Driven 5W, single phase, 230 V, 50 HZ, AC supply complete all as specified and directed.
S&F in replacement of shaft seal assembly as per existing (150 TR) complete all as specified and directed.
S&F in replacement of shaft seal cover plate as per existing (150 TR) complete all as specified and directed.
S&F in replacement of seal end bearing washer as per existing (150 TR) complete all as specified and directed.
S&F in replacement of seal end thrust washer as per existing (150 TR) complete all as specified and directed.
S&F in Replacement of shaft seal assembly as per existing (80 TR) complete all as specified and directed.
S&F in Replacement of shaft seal cover plate as per existing (80 TR) complete all as specified and directed.
S&F in Replacement of seal end bearing washer as per existing (80 TR) complete all as specified and directed.
S&F in Replacement of seal end thrust washer as per existing (80 TR) complete all as specified and directed.
S&F in Replacement of shaft seal assembly as per existing (24 TR) complete all as specified and directed.
S&F in Replacement of shaft seal cover plate as per existing (24 TR) complete all as specified and directed.
S&F in Replacement of seal end bearing washer as per existing (24 TR) complete all as specified and directed.
S&F in Replacement of seal end thrust washer as per existing (24 TR) complete all as specified and directed.
S&F in Replacement of shaft seal assembly as per existing (39 TR) complete all as specified and directed.
S&F in Replacement of shaft seal cover plate as per existing (39 TR) complete all as specified and directed.
S&F in Replacement of seal end bearing washer as per existing (39 TR) complete all as specified and directed.
S&F in Replacement of seal end thrust washer as per existing (39 TR) complete all as specified and directed.
S&F in Replacement of shaft seal assembly as per existing (7.5 TR) complete all as specified and directed.
S&F in Replacement of shaft seal cover plate as per existing (7.5 TR) complete all as specified and directed.
S&F in Replacement of seal end bearing washer as per existing (7.5 TR) complete all as specified and directed.
S&F in Replacement of seal end thrust washer as per existing (7.5 TR) complete all as specified and directed.
S&F in Replacement Time delay relay of range 0-30 min complete all as specified and directed. Make : L&T/ Siemens.
M & L Refrigerant gas charging ( R -22/R-407/R-410) or all as per plant requirement complete all as specified and directed.
S&F in replacement of power contactor type MNX12 Aux to MNX 20 contact 1 No for, 415 volts 3 pole complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in replacement of power contactor type MNX25 to MNX32 Aux contact 1 No for, 415 volts 3 pole complete all as specified and directed. Make : Siemens/L&T/C&S/BCH.
S&F in replacement of power contactor type MNX 40 Aux contact 1 No for, 415 volts 3 pole complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in Replacement of power contactor type MNX70 Aux contact 1 No for, 415 volts 3 pole. All as specified and directed by Engr in charge. Make : Siemens/L&T/C&S/BCH
S&F in Replacement of power contactor 3TF 49, AC3-85A, 50Hz, 3Ph, 415 volts with aux contacts for 415 volts complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in Replacement of power contactor 3TF 47, AC3-63A, 50Hz, 3Ph, 415 volts with aux contacts for 415 volts complete all as specified and directed. Make : Siemens/L&T/C&S/BCH.
S&F in Replacement of power contactor 3TF 46, AC3-45A, 50Hz, 3Ph, 415 volts with aux contacts for 415 volts complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in Replacement overload relay of range 14 to 23 Amps type, complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in Replacement overload relay of range 6 to 10 Amps type complete all as specified and directed. Make : Siemens/L&T/C&S/BCH
S&F in Replacement overload relay of range 3 to 5 Amps complete all as specified and directed. Make : Siemens/L&T/C&S/BCH.
S&F in Replacement over Voltage relay complete all as specified and directed. Make : Siemens/L&T/C&S/BCH.
Draining out old used oil and supply & filling new compressor oil recommended grade for Volta/bluestar make reciprocating / screw type compressor complete all as specified and directed.
M & L for PCC 1:2:4 type B1 using 20 mm graded stone aggregate as in broken coping / Foundation including slightly rounded or chamfered complete all as specified and directed.
Supply, laying, jointing and testing XLPE insulated armoured heavy duty LT under ground electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 50 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including taking out existing u/s cable complete all as specified and directed. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply, laying, jointing and testing XLPE insulated armoured heavy duty LT under ground electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 35 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including taking out existing u/s cable complete all as specified and directed. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
S & F in replacement of electric heater for heating compressor oil suitable for 150 TR compressor complete all as specified and directed. Make : L&T/GE/Schneider.
S & F in replacement of electric heater for heating compressor oil suitable for Voltas, make 80 TR compressor complete all as specified and directed. Make : L&T/GE/Schneider.
S & F in replacement of electric heater for heating compressor oil suitable for Voltas, make 26 TR compressor complete all as specified and directed. Make : L&T/GE/Schneider.
S & F in replacement of electric heater for heating compressor oil suitable for Voltas, make 7.5 TR compressor complete all as specified and directed. Make : L&T/GE/Schneider.
S & F in replacement of electric heater for heating compressor oil suitable for Voltas, make 39 TR compressor complete all as specified and directed. Make : L&T/GE/Schneider.
M&L for cross arms, bracing supports clamps and back plate fabricated from structural steel section including bolts, nuts, washers and welding, bending, cold or hot drilling holes for bolts,ERW pipe fittings in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint including dismantling old cross arms, bracing supports clamps complete all as specified and directed .
S&F in replacement Flow Switch suitable for 150 TR plant complete all as specified and directed.
S&F in replacement Flow Switch suitable for 80 TR plant complete all as specified and directed.
S&F in replacement Flow Switch suitable for 26 TR plant complete all as specified and directed.
S&F in replacement Flow Switch suitable for 39 TR plant complete all as specified and directed.
S&F in replacement Flow Switch suitable for 7.5 TR plant complete all as specified and directed.
S&F in replacement VLRP Single suitable for 150 TR plant complete all as specified and directed.
S&F in replacement MVPD Single suitable for 150 TR plant complete all as specified and directed.
S&F in replacement VLRP Single suitable for 26 TR plant complete all as specified and directed.
S&F in replacement MVPD Single suitable for 26 TR plant complete all as specified and directed.
S&F in replacement VLRP Single suitable for 80 TR plant complete all as specified and directed.
S&F in replacement MVPD Single suitable for 80 TR plant complete all as specified and directed.
S&F in replacement VLRP Single suitable for 39 TR plant complete all as specified and directed.
S&F in replacement MVPD Single suitable for 39 TR plant complete all as specified and directed.
S&F in replacement VLRP Single suitable for 7.5 TR plant complete all as specified and directed.
S&F in replacement MVPD Single suitable for 7.5 TR plant complete all as specified and directed.
Dehydration, compressor/condensor re-fixing, pressure testing, vaccumising & chiller tube repairing of condensor of 150 TR plant complete all as specified and directed.
Dehydration, compressor/condensor re-fixing,pressure testing, vaccumising & chiller tube repairing of condensor of 26 TR plant complete all as specified and directed.
Dehydration, compressor/condensor re-fixing,pressure testing, vaccumising & chiller tube repairing of condensor of 80 TR plant complete all as specified and directed.
Dehydration, compressor/condensor re-fixing,pressure testing, vaccumising & chiller tube repairing of condensor of 39TR plant complete all as specified and directed.
Dehydration, compressor/condensor re-fixing,pressure testing, vaccumising & chiller tube repairing of condensor of 7.5 TR plant complete all as specified and directed.
S & F in replacement danfoss scroll type sealed compressor, 12 /13 TR model SM 185 Refrigerant R-22 3 phase, 50Hz suitable for 24 TR central type AC plant Voltas complete all as specified and directed. Make Model ACWCDSO24OMNT complete.
S&F condensor safety valve suitable for 150 TR AC plant Make bluestar complete all as specified and directed.
S&F condensor safety valve suitable for 80 TR AC plant Make Voltas complete all as specified and directed.
S&F condensor safety valve suitable for 26 TR AC plant Make Voltas complete all as specified and directed.
S&F condensor safety valve suitable for 39 TR AC plant Make Voltas complete all as specified and directed.
S&F condensor safety valve suitable for 7.5 TR AC plant Make Bluestar complete all as specified and directed.
Repairing and painting of 7.5TR/24TR/39TR/80TR/150 TR AC Plant operating pannel such as wiring and cleaning and change the door lock, RYB light and other necessary item which is required on site complete all as specified and directed.
M&L for repair/maintenance of cooling tower of any capacity make a foundation inside of cooling tower with help of iron angle and change all UPVC pipe in any size, remove all the PVC fins as honey comb & refitted the honey comb which is workable and other new fitted complete all as specified and directed. Note: New honeycomb fins will be measured and paid seperately under the relevant item of BOQ. and New UPVC pipes are included in the unit rate item.
Repairing AHU door of 2x26 TR / 2x39 TR / 2x80 TR/150 TR/2x7.5 TR AC Plant & operating pannel such as wiring and cleaning and change the door lock, RYB light and other necessary item which is reqd on site complete all as specified and directed.
S & F in replacement PVC fills as honey comb of size 600x300x150mm suitable for cooling tower of make 80 TR/150 TR capacity complete testing of flow of water upto the requirement of temperature, limit for discharge pressure maintain complete all as specified and directed.
Taking out centrifugal mono block pump set, discharge capacity 640 GPM of 20 HP, from foundation with the help of special tools, opening the pump completely and remetling/ grinding pump shaft, replacement of defective bearing and gun metal bush, gasket packing etc, overhauling and re-assembling complete including CI welding of pump housing for fixing gland plate complete all as specified and directed.
S&F CI split gland plate capacity suitable for 5/7.5/10/15/20 HP pump complete all as specified and directed.
M&L fo repair of duct remove the all cable and cleaning the dust and particle and including filling up fine river sand upto 30 cm with cables make as per existing and including refixing the iron cover complete all as specified and directed.
S&F Replacement of heating strip of 3 KW capacity with stand complete suitable for the existing AHU or as per site requirement complete all as specified and directed. Make : DASPASS/ Powerpack.
Repair a foundation of 5HP/7.5/10HP/15HP/20HP motor of any AC plant make with iron angle and fixed with nuts and bolt size of motor and make a hole in wall and fixed a metal pipe from motor to wall out side suitable for water drain system if motor gland leakage than it water go out side complete all as specified and directed.
S&F of 80 TR AC plant spare parts suitable for existing compressor manufacture by voltas these are following:-
crank shaft
main bearing
Oil Pump
Connecting Rod
CR bearing
Piston Pin
loader
Liner
Discharge Guide
Valve Plate
Piston
Suction reed
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for pipe line in soft/loose soil, & getting out complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed.
M & L for sand cushioning with dry coarse sand to under ground cable 23 cm thick, 8 cm thick below the cable and 15 cm thick after laying the cable complete all as specified and directed. Note : Thickness after punning shall be considered for payment.
M & L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable size including concealed in wall etc one run of PVC insulated with 6.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 6 sqmm cable,one run of 6 sqmm cable and one run of PVC conduit will be measured as one unit.
M&L for Earthing complete with galvanised mild steel earth electrode plate 600 X 600 X 6 mm thick buried directly and vertically in ground connected to galvanised earth strip of size 25 x4 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of galvanised iron strip of size 25 x4 mm as earthing lead protected by galvanised iron 50 mm bore medium grade pipe with all fittings from the earth electrode fixed along pole or wall with and including 25 x 6mm flat iron clamp, bolts, nuts and washers and watering pipe shall be 20 mm bore GI medium grade from top of the earth pit to top of earth plate electrode including all excavation and earth work in any type of soil and removal of soil upto 50 metre, PCC pit with pre-cast RCC cover with handle, charcoal/salt, funnel , CI frame etc complete all as specified and directed. NOTES : (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth wire. Any variation in length shall be adjusted through deviation order (iii) Items includes cost of 7.5 metre earth lead wire. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
M & L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level, connecting to GI earth wire 4mm dia by means of bolts, nuts, check nuts, and washers of galvanized iron or steel including 15 mm dia. medium grade protection pipe for earth lead complete with charcoal and common salt including watering arrangement with galvanized iron pipe light grade 20 mm dia, PCC Chamber, CI frame and cover, MS funnel with wire mesh all as shown in electrical plate no 3 of SSR part I including excavation and earthwork in any type of soil/strata and testing on completion. Note :- GI earth wire 4 mm dia and 15 mm dia protection pipe upto 7.5 mtr from earth plate is deemed to be included in rate quoted.
S&F in replacement of V belt compatable for the existing plant of any capacity complete all as specified and directed.
M & L for brick protection with old size sub class 'B' bricks laid flat , length of bricks across the route of underground cable complete all as specified and directed.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.35 MB
TenderDocuments62.pdf
Tender Documents • 6.61 MB
BOQ_843718.xls
BOQ • 0.89 MB
Download all tender documents and submit your bid