Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.5 LAccepted-AOC D 89 SHASTRI NAGAR MEERUT UTTAR PRADESH PIN 250004 | MEERUT | UTTAR PRADESH | 250004 | L1 | Accepted-AOC L1 and resonable | |
| 2 | L2₹48.0 L+₹9.5 L (24.6%)Rejected-Finance 114 SHASTRI NAGAR MEERUT | MEERUT | UTTAR PRADESH | 245206 | L2 | Rejected-Finance In Order but L2 |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
9 Apr 2022, 6:00 pmClosed
GE(U)E/M Meerut
Roorkee road Meerut Cantt
PROVN OF COVERED SHEDS FOR SATCOM BUC ( NEAR SATCOM ANTENNA) AND FOR STORING OPTICAL FIBER CABLE AND JELLY FILLED CABLE WITH HARD SURFACE AT DCN SUB GP DABATHWA AND PROVN OF 01X HIGH MAST LIGHTING SYS OF 16 MTR WITH 8 NOS OF 150W LED LIGHTS AT FASF
2022_MES_513420_1
8410/E8
Open Tender
Civil Works
Works
120 days
Meerut
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE(U)E/M Meerut
₹70,000
Yes
2 May 2022
12 Mar 2022
11 Apr 2022
12 Mar 2022
9 Apr 2022
26 Mar 2022
Amount
M&L for surface dressing n exc 15cm deep in soft/loose soil complete all as specified and directed
Excavation in trenches n,exc 1.5m wide and n,exc 1.5m in depth for foundation etc or for shafts wells cesspits manhole etc n,exc 10sqm on plan and n,exc m in depth and getting out in soft/loose soil, complete all as specified.
M&L cement concrete type D-2 1:4:8 (40mm graded aggregate) as in foundation filling and mass concrete, complete all as specified.
Formwork to sides of concrete foundations , footings base of columns, raft beams , sides and sofits ( if any) of foundation and plinth beam, and similer work vertical or to batter rough finished surfaces of concrete flat, complete all as specified.
Formork to sides of pillars posts and column rough finished surfaces of concrete rectangular/square size, complete all as specified.
M&L reinforceent cement concrete M-25 (20 m graded aggregate) design mix as foundation , footings foundation beams , plinth beas , bases of column etc , complete all as specified.
M&L reinforceent cement concrete M-25 (20 m graded aggregate) design mix as in lintel / roof beams, complete all as specified.
M&L reinforceent cement concrete M-25 (20 m graded aggregate) design mix as column etc , complete all as specified.
M&L mild steel TMT bars 10mm dia and over , cut to lenght , bend to shape required including cranking bending sprially for hooping columns, hooking ends and binding with and including mild steel wire ( annealed ) not les than 0.9mm dia or securing with clips quality , complete all as specified.
Ditto as above item no but 6mm to 8mm dia as in stirrups , complete all as specified.
Returning filling in, including spreading, levellin, watering and well ramming in layers n;exc 25 cm , complete all as specified.
Removing excavated material n ;exc 50 m and depositing where directed at a level n;exc 1.5 m above the starting point, complete all as specified.
M&L brick work with fly ash bricks ( old size) straight or curved on plan exc 6 m mean radius , built in CM 1:6, complete ass as specified and directed
M&L rendering 15 mm thick on fair faces of brick work or cocrete surfaces in cm 1:4 complete including water proofing compound (Nore WPC will be measured and paid separatly), complete all as specified.
Supply only intergal water proofing conpound Make:- sapseal, JK, Sikka or equivalent as approved by GE
M&L rendering 10 mm thick on fair faces of brick work or cocrete surfaces in cm 1:4, complete all as specified.
S&F steel windows with side hung shutters including proecting type hings with steel handle and steel peg stay complete with glazing bars, dovetailed or welded, complete all as specified.
S&F sheet glass3 mm thick ordinary quality and galzing with oil putty in squre n;exc 0.5 sqm in each pane , complete all as specified.
S&F 1.25mm thick laths rolling shutter with out ball bearing as specified including top cover anchoring rod, hasp and staple and one coat of primer as indicated complete push pull or manual type, complete all as specified.
S&F rolled trusses ( framed ), trussed purlins, crane and fastening feavy bracket framing ( bem, tee,anglechannel or flat sections) including distance pieces cleates etc confirming to Fe 410-W(Gde E-250 Quality), complete all as specified.
M & L for preparation of new or previously un treated steel and iron surfaces over 10cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint over one coat of red oxide or zinc chrome on steel and iron surfaces all as specified and directed.
S&F pre painted galvalume aluminium zinc coated GI based corrugated steel sheet 0.50 mm thick of an colour having a tensile strength of 550 Mpa as in roof covering / clading to wall fixed with self tapping screws as specified
Ditto as above item but in plain as in ridge all as specified.
S&F MS wind tie for roof including securing bolte etc omplete
M&L hardcore(broken stone/boulders) of guage exc. 63 mm but n,exc 100 mm thick deposited spread and levelled in layers n exc 15 mm thick watered and rolled /rammedto a true surfaces, complete all as specified and directed.
M&L cement concrete 75 mm thick type C1 1:3:6 ( 20 mm graged crushed stone aggregate as in plinth protection ), complete all as specified.
M&L 100 mm thick cement concrete type D-2 1:3:6 (40mm graded crushed stone aggregate) as in sub base of floor , complete all as specified and directed.
M&L 50 mm thick cement concrete type B 1:2:4 (20 mm graded aggregate) as in sub base of floor , complete all as specified and directed.
M&L 100 mm thick cement concrete type D-2 1:4:8 (40mm graded aggregate) as in sub base of floor , complete all as specified and directed.
M&L for preparing new plastered of walls and applying two coats of cement base paint all as specified and directed by EIC
M&L preparing surfaces of new plastered and applying two coat oil bound distemper over a coat of primer all as specified and directed.
M&L Cement concrete work in pavement/ hard-standing of flexural strength 40 kg/per square centimetre in field using 400 kg of cement per cubic metre, thickness of concrete 25 cm or less.all as specified and directed.
Material & labour point wiring with 1.5 sqmm nominal cross sectional area, single core, 1100 Volts grade, stranded, PVC insulated, unsheathed copper conductor cable in and including PVC concealed conduit of 25 mm dia or higher, medium grade complete with and including all PVC conduit accessories/ fittings, brass screws, washers etc, Sunk Zinc coated pressed steel terminal boxes including all cutting/chases etc in walls, with 3 mm thick plastic laminated sheet top cover concealed in wall with and including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated copper stranded conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed for the followings.
(a) One light /Tube point controlled by one, one way switch 05/06 Amps
(b) One 3 Pin, 05 /06 Amps socket outlet point on indpendent board controlled by one, one way 5/06 Amps switch
(c) One 3 Pin, 05 /06 Amps socket outlet point on same board controlled by one, one way 5/06 Amps switch
All as per serial item No 33 here in before but with 2.5 Sqmm nominal cross sectional area copper conductor cable for one 15 /16 Amps socket outlet point on independent board with and including continuous earth wire of size 2.5 Sqmm nominal cross sectional area, single core, PVC insulated copper conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed
Material & labour point wiring with 1.5 sqmm nominal cross sectional area, single core, 1100 Volts grade, stranded, PVC insulated, unsheathed copper conductor cable in and including PVC surface conduit of 25 mm dia or higher, medium grade complete with and including all PVC conduit accessories/fittings, brass screws, washers etc, Sunk Zinc coated pressed steel terminal boxes with 3 mm thick plastic laminated sheet top cover concealed in wall with and including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated copper stranded conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed for the followings.
Supply & fixing switch piano flush type, 05/06 Amps single pole , one way 240 volts complete all as specified & directed
Supply & fixing switch piano flush type, 15 /16 Amps single ploe, one way 240 volts complete all as specified & directed .
Supply & fixing socket outlet 3 pin, 05/06 Amps (2 -in-1 Multipurpose) flush type 240 volts complete all as specified & directed.
Supply & fixing of socket outlet 3 pin, 15/16 Amps (2 -in-1 Multipurpose) flush type 240 volts complete all as specified & directed.
Supply & fixing of ceiling rose surface bakelite 65x 50mm three terminals complete all as specified & directed.
S&F Light emitting Diode (LED) tube light fitting surface/ pendent mounting decorative box type AC 220-240V, 50 hz, CRCA body with acrylic diffuser 20 watt, 4' long, and making connections with and including 23/.0076 flexible cord of required length from ceiling rose to connector complete all as specified and directed.
Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC)
Supply & fixing MCB , SP, AC, 240 volts of 06 to 32 Amps capacity 10KA, 'B' series and making connections with suitable size of copper lugs complete all as specified & directed
Supply & fixing MCB SPN, AC, 240 volts of 40 Amps capacity 10KA, 'B' series and making connections with suitable size of copper lugs complete all as specified & directed.
S & F LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size
S&F epoxy powder coated distribution box, SPN, 4 ways, 240 volts, IP-43 ,metal double door for MCB , grouted flush to walls including making good disturbed surafces of wall to match the adjoining surfaces complete all as specified and directed.
M&L Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia ( 7.50 mtr long)by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate number 3 of SSR Part I complete all as specified and directed and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
M&L Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead GI strip 32x 6 mm ( 7.50 mtr long)by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate number 3 of SSR Part I complete all as specified and directed and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
M&L submain wiring with nominal cross sectional area of 4 Sqmm 2 run (FRLS) PVC insulated and unsheathed multistranded copper conductor alongwith one run of 4 sqmm earth continuity conductor drawn through and including 25 MM dia,PVC concealed conduit medium grade with all accessories all as directed.(Note: The rate of cutting chasis and making good of disturbed surfases shall be include in the quated rate)
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 10 sq. mm 2 core nominal cross section in service connections
M & L supply erection testing and commissioning of raising and lowering type 16 M high mast system , Mast shaft shall be maximum in two sections , hot dip galvanized inside and outside in single dip suitable for wind velocity as per IS 875 part 3 . There shall be only one longitudinal seam weld per section and no circumferential weld it shall also include accessories for high mast including head frame 2 point suspention system with steel wire rope 6 mm dia ( 97/19 guage construction ) double drum winch galvanized lantern carriage arrangement suitable for up to 8 Nos luminaries symmentrically lighting finial and integral power tool for raising and lowering operation of the high Mast including construction of suitable shallow foundation with PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate for the High Mast considering the safe soil bearing capacity at site as 10 ton per Sq mtr and considering depth as per manufacturer recommendation but not less than 2 mtr depth with all materials and labour foundation bolt manufactured from special steel along with nuts bolts and washers anchor plates and template all as specified and directed and comprising of followings : -
(a) Supply & fix twin dome LED aviation obstruction light including necessary connection complete all as directed by Engr-in-Charge- 01 No.
(b) Lightning Arrestor spike - 1 No.
Supply and fixing LED flood light fitting 150W, 230 volt , AC outdoor type with thermal management in multiple optics and equipped with IP 66 protection, with impact and corrosion resistance complete all as specified and directed.
Supply and fixing LED flood light fitting 120W, 230 volt , AC outdoor type with thermal management in multiple optics and equipped with IP 66 protection, with impact and corrosion resistance complete all as specified and directed.
Supplying laying and testing XLPE insulated ,armoured , LT electric cable (heavy duty) armoured , IS-7098, 1100 volt grade with staranded aluminium conductor, laid in trenches / ducts or fixed to walls / poles or passed through pipess complete all as specified of following sizes :-
(a) 95 Sqmm,3.5 core cable
(b) 50 Sqmm,3.5 core cable
(c) 16 Sqmm, 4 core cable.
(d) 25 Sqmm, 4 core cable.
Supply & fixing or laying galvanised steel tubing 80mm bore light grade (ISI marked) for protection of under ground cable on poles/ walls under road crossing etc
M & L for boaring in any type of soil under road 1.5 Mtr below the top surface of road by conventional method complete for passing through 80mm dia GI pipe and filling earth after laying of pipe including disposal of surplus soil complete all as specified and directed.
Supply, fixing, installation and testing LT pannel out door (Kiosk type) type, wheather & vermin proof MS sheet housing 3.15mm thick, double door front & rear openable type mounted on 50 X 50 X 6mm angle iron frame, floor mounted type with coloured horizontal Tinned aluminium bus bar 4 pole mounted on insulators of rating 400 Amps, one MCCB, 4 pole 200 Amps, 36 KA 415 volts at incoming supply. The panel size not less than 600x450x300mm with cable gland, duly powder coated, locking arrengement complete and including grouting in PCC block of suitable size all as directed by Engr-in-Charge.
Supply, fixing, installation and testing LT pannel out door (Kiosk type) type, wheather & vermin proof MS sheet housing 3.15mm thick, double door front & rear openable type mounted on 50 X 50 X 6mm angle iron frame, floor mounted type with coloured horizontal Tinned aluminium bus bar 4 pole mounted on insulators of rating 300 Amps, one MCCB, 4 pole 200 Amps, 36 KA 415 volts at incoming supply. The panel size not less than 600x450x300mm with cable gland, duly powder coated, locking arrengement complete and including grouting in PCC block of suitable size all as directed by Engr-in-Charge.
Supply installation testing and commissioning of 3 phase 5 KVA, GCMS (Group Control management System) central LT panel with on off of contractor for collective control, with input and out put MCB, 3 phase panel meter, remote data monitoring, notifications of faults, suitable for surge protection, rotary switch for manual operation, 2mm, MS sheet enclosure with proper earthing arrangements complete all as specified and directed. Note :- The GCMS have to following features :- (i) Input to GCMS shall be 3 phase/1phase grid power input and with 3 phase (Common phase/individual phase control)/1 phase output for load with option to switch on and off the load. (ii) GCMS shall able to measure voltage, current, power factor, Active power, apparent power, metering cumulative active energy, metering cumulative apparent energy. (iii) Time scheduling which could be defined from the GUI running locally in smart device. (iv) Communication-GPRS communication between GCMS and cloud server street lights for futuristic expansion. (v) Wireless local control for field staff to on/off GCMS in case of GSM failure.
Earthing complete with galvanised MS earth plate of size 600 x 600 x 6mm thick burried directly in ground not less than 2.25 Mtr below ground level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150mm in alternate layers, connected by GI earth strip of size 25 x 4 mm thick, soldered and revetted to earth plate. GI earth strip will be protected by using 40mm bore GI pipe (medium grade). The earthing includes PCC pit chamber, RCC pit cover and frame, watering pipe 20mm bore, funnel with wire mess with necessary earth work including disposal of surplus soil to a distance not less than 50 Mtr etc complete all as specified and shown in electrical plate No 3 of SSR Part-I.
Excavation in trenches in hard/dense soil n. exc. 1.5 meter wide and n. exc. 1.5 mtr depth and getting out, including trimming the sides and forming bottom surface to required levels for laying cables, foundation of poles, stay etc complete all as specified.
Returning, filling trenches including spreading, levelling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed.
Removing of excavated material (soil) to a distance n. exc. 50 Mtr and dispositing where directed at a level n. exc. 1.50 Mtr above the starting point complete as directed.
M & L Sand cushioning to UG cables (8cm deep before laying of cable and 15 cm deep over the cable). Note :- Punned thickness only will be considered for payment.
M & L Bricks for protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other complete all as specified and directed.
M&L for auguring of hole suitable for passing 40 to 100 mm bore pipe in true horizontal position under road / CC path etc, by mean of mechanicalring/ auger not exceeding 1.5 mtr below existing surface level of road and not exc 30 mtr in length complete all as specified and directed. Pipe shall be measured and paid separately
Supply & fixing or laying galvanised steel tubing 50mm bore medium grade (ISI marked) for protection of under ground cable on poles/ walls under road crossing etc complete all as specified and directed.
M&L for Octagonal pole mild steel of 12 mtr height powder coated hot dip galvenisede, pole top size 70 A/F mm and bottom size 175mm A/F with base plate size 275x275x16 mm with foundations nut bolt etc and round bracket fixed to top of pole suitable for 6 flood lights symetrically fitted along with their control at bottom and connection cable for each light from controle switch , RCC foundation as per height complete including necessary earth work and erectin of pole all as specified and directed.
S&F astronomical time switch will be used in Time lite DBs 32 Amps , 3 Pole 230 volts automatic operation street time switch having lighting control (ON/OFF) through astronomical calculation of sun rise/ set by setting time and date and degree of longitude and latitude without seprate light and sensors complete all as specified and directed. Make: Legrand, L&T, ABB, Indo Asian
Jain Traders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .