SE ETC MUZAFFARNAGAR
NEAR 132 KV SUB STATION BHOPA ROAD MUZAFFARNAGAR
WORK TENDER
2023_UPTCL_794289_1
ETC MU T 01 2023 24 very short term
Open Tender
Electrical Works
Item Rate
10 days
SAHARANPUR
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
EE ETD MUZAFFARNAGAR
₹6,000
15 Apr 2023
5 Apr 2023
12 Apr 2023
5 Apr 2023
11 Apr 2023
5 Apr 2023
Amount
Dismantling of HV side LAs and their structure of 63 MVA T/F Including earthing of Structure at 220 KV S/S Nanauta
Erection of HV side LAs and their structure of 63 MVA T/F Including earthing of Structure at 220 KV S/S Nanauta
Dismantling of defective 63 MVA T/F-II including Opening jumpers of HV/LV side, removal of earthing strip from Neutral bushings and transformer body, & its accessories including radiator, HV/LV bushing HV/LV turret, HV/LV neutral bushing, buchholz relay, oil pipe line from conservator tank to main tank, oil pipe line to OLTC and surge relay conservator tank at 220 KV S/S Nanauta .
Shifting/ Dragging of defective 63 MVA T/F from plinth to near open space (Distance about 20 Mtr.), including turning of main tank upto required angle at 220 KV Sub-Station Nanauta.
(a) Additional shifting including turning of main tank 1 for every 5 Mtr.
Dragging of 63 MVA T/F Main tank from unloading site to T/F Plinth at 220 KV S/S Nanauta . Approx distance - 20 Mtr.
(a) Additional shifting including turning of main tank 1 for every 5 Mtr.
Complete, Erection of 63 MVA T/F by erection of radiator, conservator tank, bushing with its turrets, connecting of all oil pipe line, erection of cooling fans, making control cable connections, buchholz relay etc. for completing the work, topping up of T/F oil and final oil filling in tank, radiator, conservator tank and all other associated work for completion of .
Making of delta earthing for 63 MVA T/F consisting of fabrication of delta set with 03 Nos. 40mm dia electrode having length of 03 Mtrs, its placing inside the ground and connecting all 03 electrodes with 75x10 mm MS flat 700 mm deep and with Neutral bushing of transformer as required.
Earthing of main tank at two designated points & neutral bushing of HV and LV side of 63 MVA T/F by using M.S. flat 50x6 / 75x10 mm size, its jointing with already laid earth mat / Deltas. neutral bushing support for its earthing work.
Replacement & fitting of RTCC panel of 63 MVA T/F by RTCC panel of 63 MVA T/F in control room at 220 KV S/S Nanauta including laying of control cables as per requirement and their De-termination /Termination, earthing of RTCC panel of 63 MVA T/F.
Connection of the control and power cable as per new cable schedule of new 63 MVA, 132/33 KV Transformer and its OLTC/RTCC panel at both end and control & relay panel cooling fans and pumps marshaling box etc. using existing cables.
Centrifuging of complete T/F oil (approx. 20 KL) in T/F tank by connecting centrifuging pipes, circulating the T/F oil through Private centrifuging machine and taking the BDV value of the oil periodically till the required value is achieved. ( UNIT IN LTR)
Sampling and testing of transformer oil at PGCIL or any other NABL accredited testing lab including cost of transportation of s in standard sampling bottles (adequate number of bottles to be arranged by contractor), s to be tested as follows.
Water content (Moisture content)
Di Electric dissipiation factor
Specific resistance
Dissolved gas analysis
Jumpering of T/F from HV side with single Panther and LV side with double Zebra complete up to 33 KV main bus.
Technocrat Electrical
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .