Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.7 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹14.1 L+₹3.4 L (31.9%)Rejected-Finance 0000 UNNAMED ROAD GAJIYA KANTIT VINDHYACHAL MIRZAPUR UTTAR PRADESH 231307 | MIRZAPUR | UTTAR PRADESH | 231307 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹16.6 L+₹5.9 L (55.2%)Rejected-Finance B 182 NEHRU VIHAR TIMARPUR TIMARPUR NORTH DELHI DELHI 110054 UDYAM DL 04 0017438 | CENTRAL DELHI | DELHI | 110054 | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹20.7 L+₹10.0 L (92.9%)Rejected-Finance | L4 | Rejected-Finance Not Lowest |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
24 Dec 2019, 6:00 pmClosed
GE KAPURTHALA
GARRISON ENGINEER KAPURTHALA
Repair/ Replacement and maintenance of fire fighting system, repair to water supply installations and external water supply works at Mil Stn Beas and Jandiala Guru under GE Kapurthala
2019_MES_302578_1
GE KPT-30/2018-19
Open Tender
Civil Works
Item Rate
300 days
KAPURTHALA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE KAPURTHALA
₹50,000
Yes
29 Apr 2020
30 Nov 2019
26 Dec 2019
30 Nov 2019
24 Dec 2019
9 Dec 2019
Amount
Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying CI/GI/DI pipe lines and under ground cables including segragation of sand, bricks and stacking complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exceeding 25 cms thick each layer complete all as specified and directed by Engineer-in-Charge.
Removal of surplus soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge.
Dismantling and taking out old existing CI pipe line of 150/100/80 mm dia from trenches alongwith all fitting such as bends, reducers, sockets, tees, tail pieces and valves etc including jointing material of CI pipe complete all as specified and directed by Engineer in-charge.
All as per item ser No 4 above here in before but GI pipe line of 50/40/25/20 mm
Labour for relaying of CI Pipe of 100/80 mm dia after cleaning, washing, descaling and painting of serviceable good condition CI pipe with all fittings such as bends, reducers, sockets tees, valves etc including jointing material of CI pipe complete all as specified and directed by Engr in Charge. (Note : CI pipe of good condition to be used for relaying, fittings such as bends, reducer, sockets tee etc . Only lead joints will be measured and paid separately under respective items.
Labour for relaying/ refixing of of GI Pipe of 50/40 mm dia after cleaning, washing, descaling of serviceable good condition GI pipe with all fittings such as bends, reducers, sockets tees, valves etc including jointing material of GI pipe complete all as specified and directed by Engr in Charge.
Supplying & laying, jointing & testing CI pipe 100 mm dia centrifugally cast class LA confirming to IS -1536 spigot and socketed ends in any length laid in trenches complete all as specified and directed by Engineer-in-charge (Note : excavation,earth work,CI fitting and run lead joint/pressfit joint shall be measured and paid for separetaly).
All as per item ser No 8 above here in before but 80 mm bore
S & Fixing GI tubing medium grade 50mm bore (in any length) with required fitting duly laid in trenches and connecting up with water supply mains complete all as specified and as directed by Engr-in-Charge.
All as per item ser No 10 above here in before but GI pipe 40 mm bore
All as per item ser No 10 above here in before but GI pipe 25 mm bore
All as per item ser No 10 above here in before but GI pipe 20 mm bore
Supply and fixing in replacment cast iron sluice valve PN 1.6 150 mm bore with flanged ends ISI mark with Gun metal spindle CI gate with brass ring and iron wheel handle with jointing material such as nuts /bolts washers and rubber insertion sheet etc including taking out old U/S sluice valve complete all as specified
All as per item ser No 14 above here in before but 100 mm bore
All as per item ser No 14 above here in before but 80 mm bore
M&L for Run lead joint suitable for CI pipe 150 mm bore complete for laying of new pipe line including rectification of leakage in existing pipe line all as directed and specified by Engr in charge.
All as per item ser No 17 above but 100 mm bore
All as per item ser No 17 above but 80 mm bore
Job for deploying sufficient labour & Plumber (Skilled) for detecting & repairing of leakage/blockage of underground water carrying pipes of size 20 mm to 150 mm of any description such as CI/GI/DI, sluice valve at any location including excavation & earth work, cutting existing pipe lines, dewatering & refilling the earth after repair etc all as specified and directed by JE E/M or Engr in Charge. (Items/fittings required for rectification will be measured & paid separately under respective item of sch 'A' & Rate quoted shall be deemed inclusive of necessary T&P/JCB required as per site requirement)
Repair to existing valve pits of internal dimensions 90x 90 x 90 Cms making good disturbed/dismantled brick work in cement mortar (1:4) and PCC coping in cement concrete 1:2:4 type B-1 and providing MS cover in replacement made out of MS sheet 3 mm thick duly welded to MS angle iron frame 40x 40 x 6 mm including frame work as per existing size with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed by Engineer-in-Charge.
All as per item No 21 here in before but of size 75 x 75 x 75 cms of valve pit.
Supply and fixing glass sheet size 60 cms x 60 cm x 4 mm thick in MS box including provinding new rubber beading complete all as speicified and directed by Engr in - charge.
Supply and fix rubber gasket for fire hydrant coupling of any size complete all as specified and directed.
Supply and fix Male & Female brass coupling for fire hydrant post of any size complete all as specified and directed.
Supply and fixing in replacement of hose pipe rubberised fiber 70 mm dia ISI marked each length 30 Mtr with gun metal male and female coupling duly winding with wire suitable for fire hydrant 65 mm bore including taking out old unserviceable hose pipe complete all as specified and as directed by Engr -in-charge (Make Padmini or eqvivalend as approved by GE/ISI Marked )
Supply & fixing in repair gun metal glove or gate valve with iron wheel head screwd both ends for iron pipe 50 mm bore complete all as specified and as directed by Engr-in-charge.
All as per item ser No 27 above here in before but 40 mm bore
All as per item ser No 27 above here in before but 25 mm bore
All as per item ser No 27 above here in before but 20 mm bore
Material & labour for cleaning & flushing of RCC over head reservoir of capacity 25000 gallons at 60 feet staging removing of silt and sludge etc deposited inside the tank and cleaning of entire internal surfaces of tank with bleaching powder incl flushing with water, writing the capacity of tank and date of cleaning with black and white paint complete all as specified and as directed by Engr-in-Charge.
All as per item ser No 31 here in before but reservoir of capacity 4000 gln at 14 ft staging.
M & L for disconnecting electric connection , Pipe connection and taking out submersible pump & motor of capacity 7.5/10/12.5 HP from bore well and taking to workshop for repair and removal of burnt winding wire from motor and rewinding with new PVC insulated coppr winding wire for submersible motor of same guage and weight to existing including replacement of motor bush, thrust plate coupling complete with key and reassembling the motor and lowering it into bore well making it functional and testing complete all as specified.
All as per srl item No. 33 here-in-before but for 17.5 HP submersible pump.
All as per srl item No. 33 here-in-before but for 25 HP submersible pump.
All as per srl item No. 33 here-in-before but for 30 HP submersible pump.
All as per srl item No. 33 here-in-before but for 35 HP submersible pump.
All as per srl item No. 33 here-in-before but for 100 HP submersible pump.
M & L for disconnecting submersible pump from electric motor of cap 7.5/10/12.5 HP and taking it to work shop for repair and replacement of unserviceable part such as gun metal , bush impeller, assembly shaft, locking key and MS nuts & bolts of existing size and reassembling the pump with motor and making it functional condition testing the pump to the entire satisfaction of Engr-in charge.
All as per srl item No. 39 here-in-before but for 17.5 HP submersible pump.
All as per srl item No. 39 here-in-before but for 25 HP submersible pump.
All as per srl item No. 39 here-in-before but for 30 HP submersible pump.
All as per srl item No. 39 here-in-before but for 35 HP submersible pump.
All as per srl item No. 39 here-in-before but for 100 HP submersible pump.
Supply & fixing lowering submersible copper cable of 35 sq mm 3 core 1100 Volt flat type complete all as specified and as directed by Engr-in-Charge. Make : L & T, Havells/Kalinga/Polycab
All as per item No 45 here in before but 16 sq mm
All as per item No 45 here in before but 10 sq mm
S & F Bends (any type, radius and angle ) Tapers any type (straight , bend, increasing, decreasing or double socket etc) Tee pieces single branch Y junction double branch cross (all sockets and spigot) collars caps and plug etc suitable for CI pipes upto 150mm dia including taking down unserviceable bends and all as specified and directed as Enge-in-Charge.
M & L for fabricating, supply , Install & testing LT starter panel of submersible pump set upto 35 HP from CPRI approved manufacturer comprising of following parts. (a) MCCB 125 Amp, TP, 415V, 35 KA - 01 No. Make : L&T/Indo Asian/C&S/ HAVELL’S. (b) Digital type voltmeter 0-500 V - 01 Nos. Make : L&T/ESSMA/AE. (c) Digital type Ammeter 300/5 Amp with CT’s – 01 No. Make : L&T/ESSMA/AE (d) Indicator LED type 22.5 mm (R,Y,B) with HRC fuse fittings - 01 Set (e) HRC fuse kit of suitable capacity. (f) Fully automatic star delta starter comprising of the following items. Make : BCH/ABB (i) Contactor, 80 Amp, Coil Voltage 220 V - 03 Nos. (ii) Overload relay CT operated 66 – 110 Amp, (iii) Electronic timer star delta 220V, (iv) Single phase preventer – Make Minilac VSP-2 (v) Push button - 02 Nos. (vi) Indicator LED type (vii) Capacitor heavy duty APP type 20 KVAR - 01 No. Make : EPCOS/ L&T/ENERCON Note: All the wiring for starters should be done with suitable size single core copper conductor cable/copper strip with crimping type thimbles and connected with the existing cable of motors. The above rates includes dismantling of existing panel and fixing the new panel with PCC works as required on site
S & F in replacement chemical dozing pump single phase 415 volts 50 Hz including PVC pipe of suitable size and PVC double walled container of capacity 100 ltrs complete all as specified and directed. Make :Edoze/Rmco/Declibac
S & F in replacement of unserviceable water level indicator cum auto motor shutdown device electronic type including PVC copper cable 2.5 sqmm with GI steel wire for hanging and water censor 04-05 Nos with copper PVC cable as required as per site complete all as specified. Make- SECO or equivalent make as approved by Engr in Charge.
M&L for repair/maint of existing sluive valve by changing spindle, gasket, wheel etc to remove leakage at site all as specified and directed by Engr in Charge.
M&L for painting of CI/GI pipe 40 mm to 150mm dia laid in open surface/wall with 2 coat of super enamelled black paint after cleaning, brushing the existing surface of pipe at Pump houses in various location of Beas and Jandiala all as specified and directed by Engr in Charge.
M&L in replacement Cast Iron Air Valves with two air Outlets, suitable upto 80 mm dia bore and fixing Up in cast iron water supply mains all as specified and directed.
Taking out old unserviceable hose pipe fire box , supply and fixing sheet metal fire box panel 16 gauge of size 80 x 60 x 30 cms thick welded to MS angle iron frame of size 40 x 40 x 6 mm and legs (02 Nos ) welded to angle iron frame at one end of other to be embedded in cement concrete by drilling/grouting & cutting on existing platform and making the surface goodncluding providing 'L' type hook for supporting hose pipe including transparent fibre glass size 60 cms x 60 cm x 4 mm thick in MS box with rubber beading in openable door of panel (one side openable with hinges on other size) and painting with two coats of synthetic enameled RED paint over a coat of red oxide primer complete all as specified and as directed by Engr-in-charge.
M&L for painting of Sheet Metal Hose pipe fire box panel with two coats of synthetic enamelled Red Paint after cleaning/brushing the existing surface in 2 ASD Depot area all as specified and directed by Engr in Charge
Supply & fixing in replacement fire hydrant stand post/Stand post 80 mm dia GI/MS both flaged type 1.5 mtr height in 2 ASD Depot area and taking out old unserviceable stand all as specified and directed by Engr in Charge.
M&L for painting the fire hydrant stand post/Stand post 80 mm dia GI/MS both 1.5 mtr height after scrupping existing paint and applying two coats of paint after cleaning the existing surface with super enamelled BLACK/ RED paint as per site requirement in 2 ASD Depot area all as specified and directed by Engr in Charge.
Supply and fixing informatory name board of size 1200 mm x 900 mm made of aluminium sheet 2 mm thick with stainless steel rectangular frame using 25 x 15 mm rectangular pipe with 35 mm dia stainless pipe in outer border all around retro reflective high intensity 400 micron thick blue colour sheet pasted with heating process on both sides of the board including 75 mm to 100 mm high white colour letters cut to shape with special plotter and in proper manner indicating Pump House No, Location of Installation as directed by Engr in Charge. 02 Nos 75 mm dia stainless steel pipes of 304 grade glossy finish with MS plate 3 mm thick welded at bottom of pipes shall be provided .The board shall be fixed at height of 3.00 m (Top level of board) above GL and shall be embedded in ground using PCC 1:2:4 type B-1 of min size 300mm x 300mm x 600 mm including necessary form work ,excavation and earth work complete all as specified and directed.
J K AND COMPANY
sunrise engineers and contractors
R K ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .