| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 LAccepted-AOC CHANDIGARH | CHANDIGARH | CHANDIGARH | 160001 | ₹1.6 L | L1 | Accepted-AOC L1 |
| 2 | L2₹2.5 L+₹88,638.48 (55.1%)Rejected-Finance PLOT NO 74 INDUSTRIAL AREA PHASE 1 CHANDIGARH | NA | NA | 160001 | ₹2.5 L+₹88,638.48 (55.1%) | L2 | Rejected-Finance L2 |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not qualified technical bid |
Tender Value
₹2.1 L
EMD Value
₹4,200
Closing Date
25 Jun 2026, 12:00 pmClosed
Er. Chander Shekhar
Office of the Executive Engineer, Electrical Division No. 3 Sector-4, Chandigarh.
MAINTENANCE OF E.I. IN NRB AT PUNJAB AND HARYANA VIDHAN SABHA BUILDING, SECTOR-1, CHANDIGARH (LOCATING OF FAULT IN VARIOUS BUILDINGS AND 11 KV SUB STATION UNDER THE JURISDICTION OF ELECTRICAL SUB DIVISION NO.7, CHANDIGARH (FOR 12 MONTHS) (CHARGEABLE
2026_CHD_93447_1
E3/47W/62
Open Tender
Electrical Works
Percentage
365 days
Chandigarh
AS PER NIT
2 documents required · 2 mandatory
₹0
₹4,200
19 Aug 2026
19 Jun 2026
25 Jun 2026
19 Jun 2026
25 Jun 2026
19 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1DSR Item No.11.4 Supplying and making indoor cable end termination with heat shrinkable Jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminum conductor cable of 11 KV grade as required | |||||
| 1.01 | 3 ½ x 70 sq. mm | 4 | Each | 3,623 | ₹14,492 |
| 2 | Repair and servicing of HT-OCB's / VCB's of 400 Amps. To 800 Amp. 350 MVA of various types of make. The job includes the dismantling of OCB's/ VCB's & reinstallation of the same in the control panel unit. The cost also includes cleaning the 11KV contacts of HT OCB/VCB, Lubrication of movable parts of mechanism of the panel units, replacements of minor pars during the servicing job being done at site. The job also includes servicing & the cost of minor parts & other, petty material required to complete the job i.e. VCB shunt trip coil, mechanism greasing etc. The job includes the guarantee. | 6 | Each | 5,000 | ₹30,000 |
| 3 | Repair and servicing of LT ACB's of various rating from 630 amp to 1600 amp. of various make. The job includes the dismantling of ACB's and reinstalling of the same in the control panel after the servicing and repairing etc. The cost also includes cleaning of LT contacts mechanism of the panel units, replacement of minor parts during the servicing job being done at site. The job also includes servicing and the cost of minor parts and other petty material required to complete the job i.e. ACB trip coil, mechanism greasing etc. The job includes the guarantee, free servicing and mtc for one year including the repair of the same and replacement of minor parts setting of protection relays, NO/NC contacts, strip coil etc, free of cost during service tenure of 1 year. | 8 | Each | 3,000 | ₹24,000 |
| 4 | Locating of HT/LT underground cable fault approx. 1 mtr. Below ground level with the help of cable fault locating machine. The job includes the cost of digging the excavation/removing the bricks from trench after locating the fault in cable and refilling the trench in original finish after removing the fault and other petty material etc. as required to complete the job. | 2 | Each | 6,000 | ₹12,000 |
| 5 | Supply and Refilling of transformer oil in the existing transformer. The job includes the cost of all petty material require to complete the job to entire satisfaction of Engineer-in –change. | 100 | P.Ltr. | 150 | ₹15,000 |
| 6 | Servicing of 500 KVA Oil Type and 1000 KVA dry type indoor transformer after dismantling all the HT /LT connections to check the insulation resistance to locate the fault with help of magger. The job includes the cost of stepping up / down as per the requirement. The job includes cost of all petty material charges required to complete the job at site to the entire satisfaction to the Engineer-in-Charge. | 3 | Each | 3,500 | ₹10,500 |
| 7 | Checking the faulty CT/PT metering unit after opening the incomer / outgoing 11 KV cables. The job includes the cost of all petty material require to complete the job to entire satisfaction of Engineer-in –change. | 2 | Each | 3,000 | ₹6,000 |
| 8 | Supply, erection, testing & commissioning of stationary battery charger set comprising of 2 nos. 12 volts 100AH mtc. free batteries of make Exide/Amara Raja/Luminous only, Charging Unit and suitable capacity of multifunction meter for current and voltage including connection with 2.5sq.mm. FRLS insulated copper conductor cable etc., duly houses in cabinet of size (L x W x D) 36"x24"x18" made of 14 gauge CRCE sheet having 4 Nos. legs of 8" length made of M.S. angle of size 50 x 50 x 6mm. The complete cabinet inner and outer side is powder coated of approved shade. The cabinet should have open able door on front side with locking arrangement complete in all respect. Further the charging unit should be suitable for boost mode and trickle mode with display of input & output voltage and current and provided with suitable rating Miniature Circuit Breaker for protection at input supply and output of the battery charger. | 2 | Each | 36,572 | ₹73,144 |
| 9Repair/ dusting and servicing of LT panel including all type of MCCB and bus bars. The job includes the cost of thimbles/ lungs, if required to replace in whole panel as per the satisfaction of Engineer-in-charge. The qty of the job given below; | |||||
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 23.82 MB
BOQ_114409.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .