Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.8 LAccepted-AOC NETAJI MARKET MAHESHMATI ENGLISH BAZAR MALDA 732101 | ENGLISH BAZAR | MALDA | WEST BENGAL | 732101 | L1 | Accepted-AOC Agency stood L1 in the tendering Process. | |
| 2 | L2₹24.8 L+₹1.1 L (4.56%)Rejected-Finance 39 MAHESHMATI BANK COLONI MALDA WEST BENGAL | MALDA | MALDA | WEST BENGAL | 732101 | L2 | Rejected-Finance Agency Stood L2 in the Tendering Process. | |
| 3 | L3₹26.4 L+₹2.7 L (11.2%)Rejected-Finance 86 SOMNATH LAHIRI SARANI KOLKATA 700 053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | L3 | Rejected-Finance Agency Stood L3 in the Tendering Process. | |
| 4 | L4₹27.7 L+₹4.0 L (16.7%)Rejected-Finance | L4 | Rejected-Finance Agency Stood L4 in the Tendering Process. | |
| 5 | L5₹28.6 L+₹4.9 L (20.4%)Rejected-Finance 103 1A RAJA DINENDRA STREET KOLKATA 700 005 | KOLKATA | KOLKATA | WEST BENGAL | 700005 | L5 | Rejected-Finance Agency Stood L5 in the Tendering Process. |
Tender Value
Refer Docs
EMD Value
₹56,000
Closing Date
30 Mar 2022, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EXECUTIVE ENGG (P.W.D), D/DINAJPUR ELEC DIVN
O/O EXECUTIVE ENGG (P.W.D), D/DINAJPUR ELEC DIVN
EI work of the proposed PICU set up in the Old Building at Raiganj Government Medical College and Hospital, Raiganj, Uttar Dinajpur- SITC OF ERV UNITS AND AC MACHINES
2022_WBPWD_369095_1
WBPWD/EE/DDED/e-NIQ-21/2021-22
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Raiganj
Please refer tender documents
6 documents required · 6 mandatory
₹56,000
O/O EXECUTIVE ENGG (P.W.D), D/DINAJPUR ELEC DIVN
10 Aug 2022
11 Mar 2022
4 Apr 2022
11 Mar 2022
30 Mar 2022
16 Mar 2022
14 Mar 2022
120 days
Amount
SITC of ERV UNITS
Supply, Installation, Testing & Commissioning of DRI Make ERV units having following Specifications and Capacities, ceiling suspended / Floor Mounted, Fan Motors, Pre and fine Filters at supply & exhaust air. Fresh Air Systems consisting of centrifugal fan for Supply and exhaust air. There should be a Heat Recovery Wheel to recover energy from exhaust air. The Heat Recovery section shall include "ECOFRESH" make enthalpy wheels (ARI Certified) and shall have minimum recovery of 70% of total heat, i.e both sensible and latent (each being minimum 70%). The recovery of sensible and latent shall be equal. The wheel shall be made of pure aluminium foil coated with molecular sieve
desiccant “Ecosorb 300” with pore diameter of 3°A. NeoNatal Ward:1296 CFM./3000 CMH
Supply, fabrication, installation and testing of 24 SWG GI sheet metal less noise ducting for supply & return air including providing necessary arrangement. (Non Schedule)
Supply, fabrication, installation and testing of 22 SWG GI sheet metal less noise ducting for supply & return air including providing necessary arrangement.
Supply & fixing of powder coated aluminium grill for supply & return air including MS volume control dampers.
SITC of AC Machines
Supply 7.5TR capacity concealed type Split Air Conditioner of rated cooling capacity of 90000 BTU/hr. with 3Nos. twin rotary compressor, 3nos. IDU of rated power supply-230V-1ph-50Hz., 1no. ODU of rated power supply-400V-3ph-50Hz. Air-flow/per IDU:- 1000CFM. (Make: Hitachi/Carrier)
Supply 5.0TR capacity concealed type Split Air Conditioner of rated cooling capacity of 60000 BTU/hr. with 2Nos. twin rotary compressor, 2nos. IDU of rated power supply-230V-1ph-50Hz. , 1no. ODU of rated power supply-400V-3ph-50Hz. Air-flow/per IDU:- 1000CFM. (Make: Hitachi/ Carrier)
Erection & Commissioning Charges for following Air Conditioner
Supply & charging of refrigerant Gas. (Non Schedule)
Supply, Installation & commissioning of hard/soft copper refrigeration pipeline, complete with fittings, elbows, bends, supporting arrangement on walls (Make- Ryoku / Rajco / Mandev) (Non Schedule)
For Concealed Split AC
Liquid Line (3/8" OD with 0.6 mm thick)
Suction Line (5/8" OD with 0.7mm thick)
Liquid Line (1/4" OD with 0.7 mm thick)
Supply & Fixing 9mm nitrile rubber tube Insulation on suction line & Liquid Line copper pipe of ductable split AC (Make-Accoflex)
For Concealed Split AC
Liquid Line
Suction Line
Control Cabling from IDU to ODU
Supply & laying of 1.1 KV grade 4 core 2.5 sqmm PVC/A XLPE insulated copper cable (Make - Finolex / Polycab / Havells).
Supply & laying of 1.1 KV grade 3 core 2.5 sqmm PVC/A XLPE insulated copper cable (Make - Finolex / Polycab / Havells).
Supply and fixing flexible canvass connection for concealed split air-conditioners.
Supplying, fabrication & fixing 3 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) of 1m length for making Base Frame for installation of outdoor unit of 7.5TR/5.0TR/4.0TR Concealed split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with 2 Nos. horizontal angle of 50 mm x 50 mm x 6 mm of 1.2m length alongwith 2 nos. supporting Angle of 40 mm x 40 mm x 6 mm of 0.7 m length vertically.
Supply and fixing of Al powder coated continuous Grill (Non Schedule)
Supply & laying PVC Drain Pipe
25 mm dia
32 mm dia
Charges for Scaffolding arrangement including lifting for outdoor & indoor units.
Charges for drop ceiling to cover the Indoor Units made of Aluminium Composite Panel Board.
Charges for Trap Door made of Aluminium Channel frame & Aluminium Composite Board.
Transportation Charges for Concealed Split AC.
Supply and delivery of following Spilt type AC machines suitable for operation from Single Phase 230 Volt, 50 Hz ac supply with energey effiencient compressor including loading, unloading charges at work sites. (Make : 'O'-General / Mitshubishi Heavy Duty) (Non Schedule)
1.5 Ton or 1.8 Ton
Installation of the following AC Machines' indoor unit on wall and outdoor unit on outside wall by means of ready outdoor type frame fixed on wall by means of fasteners & bolts including mending good the damages to original finish. [Make-Venus]
1.5 Ton or 1.8 Ton
Supply and Febrication Installation of necy. copper refrigeration pipe (3/8'' 5/8'' or 5/8'' 1/4'') line with proper insulation arrangement from indoor unit to outdoor unit & outdoor unit to indoor unit as per direction of EIC.
Supply and laying 15 mm heavy type nylon reinforced PVC pipe with (Make as per Direction of EIC) for water drainage & laying through wall and mending good the damages.
S&F 240V, 25A, 3 pin Modular type plug top with indicator. (Make-Legrand-Myrius-Arteor/Crabtree-Amare) as per GS. [Page No-E-17, Item No-5-b as per P.W.D, Schedule of Rates For Electrical Works, Volume - I, November – 2017, including District Charge @7%]
S&F 3/4 inch or 5/8 inch flexible PVC breaded pipe for water drain.
Dismantling the existing Electrical installation by Co.'s own tools & tackles as per direction of EIC.
NOTE:- THE RATES TO BE QUOTED BY ALL THE BIDDERS SHOULD BE INCLUSIVE OF ALL TAXES INCLUDING GST AND OTHERS.
GITANJALI ELECTRONICS AND ELECTRICALS
Lyric International
AKELA CONSTRUCTION
NATIONAL AIRCON
technical_717201.pdf
PDF • 0.08 MB
techsummary_717201.pdf
PDF • 0.11 MB
finance_717201.pdf
PDF • 0.12 MB
BOQ Comparative Chart
xlsx • 0.01 MB
finsummary_717201.pdf
PDF • 9.29 MB
UntitledERVAC.pdf
PDF • 0.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .