Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.0 LAccepted-AOC | L1 | Accepted-AOC THE LOWEST TENDERER | |
| 2 | L2₹25.5 L+₹1.5 L (6.06%)Rejected-Finance 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L2 | Rejected-Finance NOT THE LOWEST TENDERER. | |
| 3 | Rejected-Technical | - | Rejected-Technical Appl for tender withdrawn given by the contractor |
| Sl No | Description | Qty | Unit | PURVA ELECTRICALS AND ENGINEERS L1 | Adinath Technical Services L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, install testing and commissioning in repair factory made out door type LT panel board of size not less than 1.5 mtrX1.2 mtrX0.450 mtr, 440 volts , 3 phase , 4 wire system with powder coating provided to make it dust /vermin proof manufactured from CPRI approved manufacturer, The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCA sheet,double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 800 Amps- 4Nos, including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resin insulator all housed in suitable bus bar chamber. All control wires shall be as per the OEM recommendations and shall be properly bunched,tied, ferrulled for proper indentification and crimped with adequate size of lugs and provision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:- | 1 | Each Job | 2,50,000 ₹2,50,000 | 2,18,514 ₹2,18,514 Lowest |
| 1.01Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50mmx50mmx6mm with bottam of panel having minimum 60cm height from existing ground/floor level. | |||||
| 1.02Aluminium bus bar strips with proper colour code -04 No, 800 Amp cap, insulator, nuts bolts etc complete. | |||||
| 1.03Indicator Lamp-01 Set (Set of three) | |||||
| 1.04Incommer MCCB 4P 400 Amp, 415V, 50 KA Ics = 100 Icu fixed thermal magnetic type - 01 No | |||||
| 1.05Outgoing, MCCB 4P 250 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 02 No | |||||
| 1.06Outgoing, MCCB 4P 160 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 02 No | |||||
| 1.07ON Load change over switch of capacity 400 Amps , 4 pole - 01 Nos | |||||
| 1.08Digital Voltmeter 0 to 500 V and Digital Ampmeter 0 to 500A.with selector switich | |||||
| 1.09Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. | |||||
Tender Value
Refer Docs
EMD Value
₹51,980
Closing Date
21 Oct 2025, 6:00 pmClosed
GE MH AND RH KHADKI
Military Engineer Services Garrison Engineer MH and Range Hills Range Hills Road Khadki, Pune 411003
REPLACEMENT OF OLD LT FEEDER PANELS AND MISC REPAIRS TO VARIOUS ELECTRIC SUB STATION AT RANGE HILLS AREA UNDER GE MH AND RH KHADKI
2025_MES_733550_1
8734/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE MH AND RH KHADKI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MH AND RH KHADKI
₹51,980
12 Jan 2026
1 Oct 2025
23 Oct 2025
1 Oct 2025
21 Oct 2025
14 Oct 2025
1 Oct 2025 - 21 Oct 2025
Amount
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50mmx50mmx6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Aluminium bus bar strips with proper colour code -04 No, 800 Amp cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 50 KA Ics = 100 Icu fixed thermal magnetic type - 01 No
Outgoing, MCCB 4P 250 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 02 No
Outgoing, MCCB 4P 160 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 02 No
ON Load change over switch of capacity 400 Amps , 4 pole - 01 Nos
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50mmx50mmx6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Aluminium bus bar strips with proper colour code -04 No, 800 Amp cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 50 KA Ics = 100 Icu fixed thermal magnetic type - 01 No
Outgoing, MCCB 4P 250 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 01 No
Outgoing, MCCB 4P 160 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 01 No
Outgoing, MCCB 4P 63 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 01 No
ON Load change over switch of capacity 400 Amps , 4 pole - 01 Nos
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50mmx50mmx6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Aluminium bus bar strips with proper colour code -04 No, 800 Amp cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 50 KA, Ics = 100 Icu fixed thermal magnetic type - 01 Nos
Outgoing, MCCB 4P 315 amp, 415V, 25 KA Ics = 100 Icu fixed thermal magnetic type - 01 Nos
Outgoing, MCCB 4P 125 amp, 415V, 25 KA, Ics = 100 Icu fixed thermal magnetic type - 03 Nos
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50mmx50mmx6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Aluminium bus bar strips with proper colour code -04 No, 800 Amp cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 50 KA Ics = 100 Icu Fixed thermal magnetic type - 01 No
Outgoing, MCCB 4P 250 amp, 415V, 25 KA Ics = 100 Icu Fixed thermal magnetic type - 01 No (for Ashok Nagar panel)
Outgoing, MCCB 4P 160 amp, 415V, 25 KA Ics = 100 Icu Fixed thermal magnetic type - 01 No (for KG School)
Outgoing, MCCB 4P 63 amp, 415V, 25 KA Ics = 100 Icu Fixed thermal magnetic type - 05 No (for Bldg DBs Panels BDTC area)
MCB TPN 63A,10KA C CURVE - 01 Nos for Street light panel
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50mmx50mmx6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Aluminium bus bar strips with proper colour code -04 No, 500 Amp cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 250 Amp, 415V, 36 KA Ics = 100 Icu Fixed thermal magnetic type - 01 No
Outgoing, MCCB 4P 125 amp, 415V, 25 KA Ics = 100 Icu Fixed thermal magneticstable type - 05 No
MCB TPN 63A,10KA C curve - 01 Nos for Street light panel
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Material and Labour in repair Earthing complete with galvanized steel earth plate electrode 60 cm x 60cmx6 mm thick, buried directly in ground vertically (earth pit not less than 2.25 mtr deep below ground level) with top edge of the earth plate not less than 1.5mtr below ground level , connected to 32mmx6 mm GI strip as earthling lead by means of bolts and nuts check nuts and washers of galvanized iron and connected to main switch board including watering arrangement with PCC chamber , MS funnel, wire gauge. CI cover with frame , 50 MM dia GI pipe light grade for protection of wire/strip etc including necessary excavation in any type of strata , returning, filling in, removal of soil outside MD land, filling of charcoal and salt complete all as shown in electrical plate No. 3 of MES Sch Part I , connected to Earthing test point complete all as specified and directed & testing on completion.
Supplying, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable in repair with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugs of appropriate size, pvc sleeve etccomplete all as specified and directed for following sizes . Make :- Havells / Gloster / Finolex / Polycab
300 sq mm 3.5 core .
240 sq mm 3.5 core
185 Sqmm 3.5 core
150 sq mm 3.5 core
95 sq mm 3.5 core
70 sq mm 3.5 core
50 sq mm 3.5 core .
35 sq mm 3.5 core
25 sq mm 3.5 core
16 sq mm 4 core
NOTE :- Earth work , bricks , riddled earth , GI pipe for protection of cable will be measured & paid under under relevant items of schdule .
Excavation in trenches not exceeding 1.5mtr wide and not exceeding 1.5mtr in depth for foundation of poles stays laying of electric cables, pipes etc and getting out in soft/loose soil complete all as specified and directed.
Ditto item no 8 but in hard/dense soil.
Removing excavated material soil to a distance not exceeding 50mtr and depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified and directed
Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed.
Material and Labour for riddled earth for cushioning to under ground electric cable including spreading , levelling and hand punning complete all as specified and directed. Note - Punned thickness shall only be measured & paid .
Material and Labour for road cutting / foot path and making good with PCC 1:3:6 TYPE C-2 ( using 40 mm graded stone aggregate ) of 150 mm depth/width complete all as specified and directed.
Supply and laying un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mm for Under ground cable complete all as specified and directed.
Supply and laying GI tubes light grade, galvanized, 40 mm bore, laid in trenches or under floor or fixed with poles/walls for protection of electric cable complete all as specified and directed.
Ditto item no -15 but 80 mm bore complete all as specified and directed.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size 25 Sqmm to 50 Sqmm 3.5 core /4 core cable complete all as specified and directed.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 70 Sqmm up to 120 Sqmm 3.5 core /4 core cable complete all as specified and directed.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 150 Sqmm to 185 Sqmm 3.5 core/4 core cable complete all as specified and directed.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 240 Sqmm to 300 Sqmm 3.5 core /4 core cable complete all as specified and directed.
Material and Labour for hardcore of gauge n.exc 63 mm ,deposited, spread, and levelled in layers n.exc 15 cm thickness (below or above ground level), watered and rammed to a true shape with broken stone or boulders existing available on site and making good complete all as specified and directed. (Sub Station Yards)
Adinath Technical Services (BID ID -3461713)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.13 MB
TENDER8734.pdf
Tender Documents • 0.79 MB
BOQ_821349.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .