Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance GROUND FLOOR THAKUR COMPLEX BASANTPUR | BASANTPUR | SHIMLA | HIMACHAL PRADESH | 171018 | Admitted-Fee/PreQual/Technical/Finance |
| 4 | Not Admitted-Fee/PreQual/Technical/Finance | Not Admitted-Fee/PreQual/Technical/Finance Not qualified for AOC |
| 5 | Not Admitted-Fee/PreQual/Technical/Finance H NO 1300 PUSHP VIHAR COLONY GUPT GANGA ROAD KANGRA 176001 | KANGRA | KANGRA | HIMACHAL PRADESH | 176001 | Not Admitted-Fee/PreQual/Technical/Finance Not qualified for AOC |
Tender Value
₹95.2 L
EMD Value
₹1.3 L
Closing Date
28 Oct 2020, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer Electrical Division HPPWD Una
Executive Engineer Electrical Division HPPWD Una
Construction of Combined Office building at Bangana Distt.Una. HP SH Providing E.I.there in.
2020_PWD_41483_1
PW-EDU-CB-TA-Tender-2020-21- 1976-81 Dt-01-10-2020
Open Tender
Electrical Works
Item Rate
1095 days
Bangana Una
Please refer tender document
7 documents required · 7 mandatory
₹2,000
EE Electrical
₹1.3 L
29 Oct 2020
8 Oct 2020
29 Oct 2020
8 Oct 2020
28 Oct 2020
8 Oct 2020
120 days
Amount
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.(Make Legrand (Myrius/L&T (Orib) /Anchor(Roma Plus)
Group C.
Wiring for twin control light point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with 2-way, 5/6 amps. modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.(Make Legrand (Myrius/L&T (Orib) /Anchor(Roma Plus)
Group C.
Wiring for light plug with 2x1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(Finolex/KEI/Anchor/L&T make)
Wiring for power plug with 2x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(Finolex/KEI/Anchor/L&T make)
Wiring for power plug with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(Finolex/KEI/Anchor/L&T make)
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required.(Finolex/KEI/Anchor/L&T make)
2x1.5 Sq. mm.
2x4 sq.mm.
2x6.0 Sq. mm.
2x10 Sq. mm.
Wiring for circuit / sub-main with 4x6 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.6 Sq.mm. (4x6+2x6) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(Finolex/KEI/Anchor/L&T make)
Wiring for circuit / sub-main with 4x10 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.10 Sq.mm. (4x10+2x10) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.(Finolex/KEI/Anchor/L&T make)
Supplying and drawing following size of PVC insulated, heat resistant, flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in existing surface / recessed, Steel/PVC conduit as required.(Finolex/KEI/Anchor/L&T make)
3x1.5 Sq. mm.
6x1.5 Sq. mm.
Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required:-(Make:- Diplast/BEC/Cipalex)ISI marked.
25 mm. dia
Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required.(Make Legrand (Myrius/L&T (Orib) /Anchor(Roma Plus)
S.P. 5/ 6 Amps one way Modular switch.
5 pin, 5/ 6 Amps Modular socket outlet.
Supplying and fixing stepped type Modular fan regulator on the existing modular box including making connections etc. as required.(Make Legrand (Myrius/L&T (Orib) /Anchor(Roma Plus)
Supplying & fixing Modular blanking plate on the existing modular metal box as required:-
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 5 pin 5/6 amps modular socket outlet and 5/6 amps, modular switch, connections etc. as required..
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps, modular switch, connections etc. as required..
Supplying and fixing bakelite batten/angle holder including connections etc. as required:- (SSK/Anchor make) or IsI marked.
Supplying and fixing call bell / buzzer, suitable for D.C./A.C. single phase,230 volts complete as required:-
Supplying and fixing Ding-Dong / Electronic musical bell, suitable for D.C./A.C. single phase,230 volts complete as required:-(SSK/Anchor make)
Supplying and erection of wall mounted metal boards for switch gear mounting of suitable size, with permissible variation in size of plus minus 5mm, welded frame work made of M.S. angle iron 35 mm x 35 mm x 6 mm thick duly welded complete with 2.80mm thick M.S. sheet fixed with hinges as open able front, complete with locking arrangement including painting and bonding to the existing earth as required:-
Supplying and erection of following depth sheet metal cubical pedestal of suitable dimensions with plus-minus 5 cm variation made from (50 mm x 50 mm x 6 mm thick) M.S. angle iron frame, covered with 1.6 mm thick M.S. sheet duly welded on five sides & front side hinged, complete with locking arrangement with sufficient No. vertical and horizontal intermediate switchgear supporting members each of M.S. flat 50mmx6mm thick of suitable length duly welded. The cubical pedestal shall have cable entry box at one or two sides and 4 No. legs of 50mmx50mmx6mm thick M.S. angle iron each 60 cm long including, powder coated painting and bonding to the existing earth etc., the same shall be erected in the 1:2:4 cement concrete plat-form of suitable dimensions 15 cm high from ground level and 45 cm thick. The cubical pedestal shall be 15 cm from the top of cement concrete plat-form:-(EVA,Power & Control System,EV Electromatic Pvt. Ltd. make or its equivalent approved make)The Panel should be approved/Tested from the CPRI.Lab.and Should be conform to IS:64139
300 mm deep (nominal)
Supplying and fixing sheet metal bus-bar chamber suitable for 63 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 300mm & cross-sectional area (16mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (380mmx350mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:-(Legrand/Schneider/Siemens make)
Supplying and fixing copper strip bus-bars suitable for 100 Amp. 415 volts capacity 4 No. each of cross-sectional area (25.4mmx3.17mm),in the existing enclosure with all accessories including connections etc. as required:-
Supplying and fixing copper strip bus-bars suitable for 200 Amp. 415 volts capacity 4 No. each of cross-sectional area (25.4mmx4.75mm),in the existing enclosure with all accessories including connections etc. as required:-
Supplying and fixing copper strip bus-bars suitable for 800 Amp. 415 volts capacity 4 No. each of cross-sectional area (50.80mmx9.50mm),in the existing enclosure with all accessories including connections etc. as required:-
Providing and fixing following rating, four pole, 415 volts, On-Load change over switch unit, panel mounting, front handle operation, including drilling holes in the cubical, making connections, etc. as required.(L&T/ABB/Siemens make)
Providing and fixing following rating and breaking capacity MCCB in the existing cubical panel board including drilling holes in the cubicle panel, making connections, etc. as required.(L&T/ABB/Siemens make)
100 Amp. -10 KA
160 Amp. -16 KA
200 Amp. -25 KA
600 Amps.35 KA.
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:- (Hagger/ABB/L&T make)
Single pole. 6 Amps.Cat-A.
Single pole. 16 Amps.Cat-A.
Single pole. 25 Amps.Cat-A.
Supplying and erection of 40/50/63 amps rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-(Hagger/ABB/L&T make)
Double pole. 40 Amps.Cat-A.
Triple pole & Neutral. Cat-A.
Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Hagger/ABB/L&T make)
40 Amps. Cat-A.
63 Amps. Cat-A.
Supplying and fixing 20 Amps, 240 volts, SPN industrial socket outlet, 2-pole & earth, metal enclosed plug top, sheet steel enclosure, suitable to accommodate a 20 Amp SPN-MCB/DP, on surface or in recess, with chained metal cover for the socket outlet, complete with connections, testing and commissioning etc. as required.
Supplying and fixing 30 Amps, 415 volts, TPN industrial socket outlet, 4-pole & earth, metal enclosed plug top, sheet steel enclosure, suitable to accommodate a 30 Amp TPN-MCB, on surface or in recess, with chained metal cover for the socket outlet, complete with connections, testing and commissioning etc. as required.
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:- (Hagger/ABB/L&T make)
Single door-4 way
Single door-6 way
Single door-8 way
Single door-12 way
Single door-16 way
Double door-8 way
Earthing with copper earth plate 600 mmx600 mmx 3 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Extra for using salt and charcoal for G.I. or copper plate earth electrode complete as required.
Providing and fixing 25mm x 5mm copper strip on surface or in recess for earth connections etc. as required.
Supplying and laying 8 SWG Copper wire at 0.50 mtr. below ground level for earth electrode conductor, including soldering etc. as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia. 300 mm long copper tube, having single prong at top, with 85 mm dia 3 mm thick copper base plate including holes etc. complete as required.
Riveting, sweating and soldering of copper/ G.I. tape ( with another copper/G.I. tape, base of the finial or any other metallic object) as required.
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run)
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run)
Providing and fixing M.V.danger notice plate of 200 mm x 150 mm made of mild steel at least 2 mm thick, and vitreous enameled white on both sides and with inscription in signal red color on front side as required.
Providing and laying of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade direct in ground; to be laid 1 meter below the ground level including excavation sand cushioning, protective covering and refilling the trench etc. of the required size:-(Havells/KEI/Polycab )
Armoured cable 630 sq. mm (3.5 core)
Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, unarmoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:-(Havells/KEI/Polycab )
Armoured cable 630 sq. mm (3.5 core)
Providing and laying of aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade direct in ground in the same trench, in one tier horizontal formation to be laid 1 meter below the ground level including excavation and refilling the trench etc.as required, but excluding sand cushioning and protective covering etc. of required size:-(Havells/KEI/Polycab )
Armoured cable 4 sq. mm (twin core)
Armoured cable 6 sq. mm (twin core)
Armoured cable 10 sq. mm (twin core)
Armoured cable 10 sq. mm (four core)
Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes by means of Expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, providing and fixing of Non-return valve, Dead weight safety valve, 2 No C.P. connection rods 18" long, making good the damages, electrical connections, safety valve connections, testing and commissioning etc. as required:- (Recold/Usha/Jaquar make)
35 Liter capacity water heater (Cat-A)
Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:- (Usha - SPH Turbo HDEF 900 RPMISI or its Equivalent make)(Usha /Crompton Greaves/Bajaj)
Exhaust Fan, Heavy duty, 300 mm sweep
Providing, Installation, testing and commissioning of ceiling fan without regulator, including wiring the down rods of standard length (up to 30 cm) with 16/0.20 mm twin twisted flexible, cotton braided, copper cable, including providing and fixing phenolic laminated sheet cover on the fan box and earthing etc. as required:- ( Usha-Technixplus BEE 3 Star rated model) or its equivalent make)(Usha/Crompton Greaves/Bajaj/Ultima)(Min.3-star rating)
Ceiling Fan 1200 mm sweep, Category-A
Supplying and fixing Power plug socket with MCB Protection 25 Amps with Plug top and 4 Module box including making connections,testing etc,as required.(SSK ,Cat.No.PSM-1501,HSN Code 8536/Anchor/ L&T or its equivalent make)
Supplying and fixing of Bulk head fitting LED 10 watts and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficacy >100 Lumen per watts,CRI >80 ,6500 K suitable for input voltage 220-240 Volts,50 HZ, Length 232x Width 105x Height 50 mm size complete with connections etc,as required.(Panasonic Ellipto Code No.PBHM01107/Philips/ Jaquor/Tisva make )
S/F Computer board comprising 3 No.5 amps.switch (Modular) and 3 No.3 pin 5 amps. Socket out let (Modular) and 1 No.12 Modular switch board with cover plate and 1 No.4 modular switch board with cover plate and 1 No.computer jack with shutter including connections etc,as required,complete in all respects..(Make Legrand (Myrius/L&T (Orib) /Anchor(Roma Plus)
Supplying and fixing Fan box of M.S.sheet with iron rod hook 12 mm.in place of junction box complete as required.
Supplying and fixing exhaust fan louver shutter for 300 mm.exhaust fan on the existing wall,painting etc, as required.(National or its equivalent make)
Supplying and fixing LED digital mounting Ammeter 0 to 500 Amps.3 phase of size 96x96 sq.mm.flush mounting in the existing pannel complete with connections etc, as required.(L&T make Cat.No.WL131020OOOO or its equivalent make )
Supplying and fixing LED digital mounting Voltmeter 0 to 500 Amps.3 phase of size 96x96 sq.mm.flush mounting in the existing pannel complete with connections etc, as required.(L&T make Cat.No.WL132020OOOO or its equivalent make)
Supplying and fixing Coolio Fuzi LED Panel indicating set R,Y and B with 3 Nos.Kit kat (Neon type) to shown the three phase indicating in the existing panel complete with connections etc, as required.
Supplying and fixing of Rubber matt 1x2 mtrs.long 2.5 mm. thick (Jyoti) in the front of main panel etc,as required
Supplying and fixing shock trearment chart in main panel room on the existing wall etc, as required
Supplying and fixing C.T.coil 100/5 Amps.in the existing pannel complete with connections etc,as required.
Supplying and laying G.I.pipe of 40 mm. dia (Heavy duty) underground 1.00 mtr.below ground level for laying the wire/cable etc, as required
Supplying and laying G.I.pipe of 100 mm. dia (Heavy duty) underground 1.00 mtr.below ground level for laying the wire/cable etc, as required
Supplying and fixing LED indicating Red Green lamp on the 3 module box on the existing door/wall suitable for 240 volts & 50-60 HZ A.C.supply complete with connections etc, as required.(Goldmedal make code No.103649 or its equivalent make)
Supplying and fixing LED Batten 10 watts mirror light and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficacy >100 Lumen per watts,CRI >80 ,6500 K suitable for input voltage 220-240 Volts,50 HZ,IP rating 20,Surge rating up to 3 KV and length 59.5 cm. CCT 6500K complete with connections etc,as required.(Tisva Code No.FT10001WT/Pansonic /Philips make)
Providing and fixing LED surface/pendent mounting Tube fixture 20W/2000Lumens LED batten anodized extruded aluminium housing high transmissibility diffuser and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficacy >100 Lumen per watts,CRI >80 ,5700 K suitable for input voltage 220-240 Volts,50 HZ, Lenght 1175X30X36 mm.complete with connections and as per best satisfaction of Engineer-in-Charge complete as required.(Panasonic Harrowal Code No.PBTM08208/Philips/Jaquor/Tisva make)
Providing and fixing LED batten 40 watts surface mounting ,aluminium housing,high transmissibility diffuser with 4000 lumen output CCT 6500 K ,length 4',Input voltage 130 to 270 volts,Surge 3.0KV,Beam angle 120 degree complete with all accessories,connections,testing and commissioning etc,as required. (Clair Code No.ZD-LTD010-40W/Tisva/Pansonic/Philips make)
Providing and fixing LED Tube fixture 36 watts surface/pendent mounting ,extruded aluminium coated body and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficacy >100 Lumen per watts,CRI >80 ,6500 K suitable for input voltage 220-240 Volts,50 HZ,IP rating 20,Surge rating up to 3 KV and diamensions 121.5x5.4x7.3 mm. complete with all accessories,connections,testing and commissioning etc,as required. (Tisva Steller series code No.PL366203/Pansonic/Philips make )
Supplying and fixing surface mounting LED 18 watts metal Round down light for soft diffuse lighting cool white and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficacy >100 Lumen per watts,CRI >80 ,4000 K suitable for input voltage 220-240 Volts,50 HZ,IP rating 20,Surge rating up to 3 KV,diamensions 19.5X19.5x3.0 mm. complete with connections etc,as required. (Tisva Hector Pro Code No.DLP1862202/Pansonic/Philips/Jaquor make)
Providing and fixing MCCB four pole 32 amps to 63 amps.rating and 18 KA breaking capacity 415 volts AC.supply 50 HZ four pole DU 100 D type in the existing enclosure including making connections etc,as required. (L&T/ABB/Siemens make)
Providing and fixing MCCB enclosure for DU 100 D/DU MCCB following rating on the existing board complete as required.(L&T/ABB/Legrand make)
Providing and fixing MCCB two pole 32 to 63 amps.rating and 25 KA breaking capacity 240 volts AC.supply 50 HZ two pole DU 100 D type in the existing enclosure including making connections etc,as required. (L&T/ABB/Standard make)
Supplying and fixing Exhaust fan (Plastic) with louver shutter 300 mm. 1000 RPM. 1125 Air Delivery (CMM) on the existing opening,in/c making proper hole and providing 6 mm.ply board cover complete with connections etc, as required.(Bajaj Make/Usha/crompton Greaves)
Supplying and fixing LED Lamp 9 watts 6500 K E-27 ,900 Lumens 240 volts AC.supply 50 HZ in the existing batten holder,pendent holder,wall bracket & bulk head fitting etc, as required.(Tisva cat. No.AL946611X/Panasonic/Philips make)
Supplying and drawing Lan cable Cat.6,solid copper conductor protected with PVC.sheath in the existing surface/recessed steel/PVC conduit as required.( D-Link or its equivalent make)
Supplying and fixing Cabin/wall fan 400 mm.sweep,AC.supply,240 volts,50 HZ high speed on the existing wall complete with connections,testing and commissioning etc,as required.(Usha Strikr Hi speed WF or its equivalent make )/Crompton Greqaves/Bajaj.
Supplying and fixing Fancy wall bracket,single holder size 170x255 GLS 60w.mm.excluding of lamp,complete making connections etc,as required.(Decon make, Cat.No..05OQ or its equivalent make)
Supplying and fixing of Hub 8 port on the existing wall/board complete with connections etc, as required.(D-Link DES-1008P-Port Desktop or its equivalent make)
Supplying and fixing of Patch cord 2 mtr.length in the existing computer complete with connections etc, as required.(D-Link Cat.6 or its equivalent make)
Supplying and fixing recess mounting LED 18 watts metal round down light for soft diffuse lighting cool white and it should be compatible with specifications i.e.Power factor >0.9,Harmonic distortion <10% & efficency >100 Lumen per watts,CRI >80 ,6500 K suitable for input voltage 220-240 Volts,50 HZ,IP rating 20,Surge rating up to 3 KV,diamensions 21.2x20x3mm. complete with connections etc,as required. (Tisva EZIO Series Code No.DLP181623M/Pansonic/Philips or its equivalent make)
Providing and fixing LED Street light 60 watts aluminium Black/grey body ,AC 85-270 volts ,available color temperature 5700 K,CRI 80,IP rating 66, up to 10KVA electric surge protection and diamensions 375x144x108 mm. complete with all Bracket, accessories,connections,testing and commissioning etc,as required. (Pansonic Code No.PSTM16608/Clair/Philips make)
S/F of 1.5 ton split type air conditioner Hot & cold or its equivelent make & model 4 star rating-2 virus safe fittrer,triple filter,E-saver mode.Quit mode,white display,auto clean.Anti Bacteria filter jet cool ON/OFF timer,sleep mode compressor cordless remote complete in all respects or any other equivelent make as per Voltas comprising to ISI with latest amensment suitable to operate on 230/240 volts +/- 10% AC.supply capable to perform the function of cooling dehumidification air circulation,ventilation and fitting in the size of nominal cooling capacity complete with 4 KVA automatic voltage stabilizer Microtek model EM4170+ confiming to ISI specifications.The stabilizer should have high voltage trip and MCB high low voltage trip and time relay complete in all respects.inluding drain pipe 20 mm.dia approximatelly 3 mtrs.long,2 No.copper pipe with insulator for inlet and outlet approximatelly 3 mtrs.long and M.S.power coated frame/stand for errection of out door unit of split type A.C.including carriage of material with in all leads & lifts. (Voltas Make Invertor 4 Star Model No.Voltas SAC 184VSZS Fioral (R-32) or its equivalent make)(Make:- voltas/Toshiba (Carrier)/Daikin)
S/F of 2.0 ton split type air conditioner Hot & cold or its equivelent make & model 4 star rating-2 virus safe fittrer,triple filter,E-saver mode.Quit mode,white display,auto clean.Anti Bacteria filter jet cool ON/OFF timer,sleep mode compressor cordless remote complete in all respects or any other equivelent make as per Voltas comprising to ISI with latest amensment suitable to operate on 230/240 volts +/- 10% AC.supply capable to perform the function of cooling dehumidification air circulation,ventilation and fitting in the size of nominal cooling capacity complete with 5 KVA automatic voltage stabilizer Microtek model EM5170+ confiming to ISI specifications.The stabilizer should have high voltage trip and MCB high low voltage trip and time relay complete in all respects.inluding drain pipe 20 mm.dia approximatelly 3 mtrs.long,2 No.copper pipe with insulator for inlet and outlet approximatelly 3 mtrs.long and M.S.power coated frame/stand for errection of out door unit of split type A.C.including carriage of material with in all leads & lifts. (Voltas Make Invertor 4 Star Model No.Voltas SAC 244DZV(R-410) or its equivalent make)(Make:- voltas/Toshiba (Carrier) /Daikin)
TERM AND CONDITIONS :-1. Conduit pipe is to be laid simultaneously with the progress of civil work.2. No part rates for any single items in Schedule of quantity will be accepted and the tender will be accordingly rejected.3. The Electricity items/fixture of any other material for which absurd low rates are quoted by the Contractor will have to be supplied in first instance.Test certificate along with bill for the items demanded by the department will have to supplied before installation.
D.S Ranta Electrical Contractor
Rajesh Kumar Jaswal
stage.html
html • 0.03 MB
finance_61215.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .