| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAccepted-AOC 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | ₹1.2 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹1.3 Cr+₹7.7 L (6.24%)Rejected-Finance | ₹1.3 Cr+₹7.7 L (6.24%) | L2 | Rejected-Finance OTHER THAN LOWEST |
| 3 | L3₹1.4 Cr+₹16.0 L (13.0%)Rejected-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | ₹1.4 Cr+₹16.0 L (13.0%) | L3 | Rejected-Finance OTHER THAN LOWEST |
| 4 | L4₹1.5 Cr+₹24.3 L (19.8%)Rejected-Finance 13 29 3RD FLOOR EAST PATEL NAGAR NEW DELHI 110 008 | WEST | DELHI | 110008 | ₹1.5 Cr+₹24.3 L (19.8%) | L4 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
10 Aug 2020, 6:00 pmClosed
CWE NO 2
CWE NO 2 DELHI CANTT
ADDN / ALTN AND IMPROVEMENT OF OT LIGHTS FITTINGS (03 NOS SATELLITE OT PLUS 02 NOS AT OT COMPLEX) ALONG WITH STANDBY POWER SUPPLY UNDER GE (E/M) BASE HOSP, DELHI CANTT-10
2020_MES_344097_1
CWE/BH-42/2019-20
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE (E/M) BASE HOSPITAL
₹2.6 L
Yes
18 Sept 2020
12 May 2020
12 Aug 2020
12 May 2020
10 Aug 2020
29 Jul 2020
Amount
Supply, installation, commissioning and testing of LED based ceiling suspended double dome Operation Theater Light with provision only for Camera to be fitted inside the dome as and when required at later stage in compliance with medical device electric standard IEC-60601-2-41, with each dome consisting of minimum 30 LED's and maximum 120 LED's housed in dome with diameter ranging between 500 mm to 700mm, suspended through a ceiling assembly with spring arm system to provide precise positioning of the OT light as required during surgery complete with UPS including sealed Maintenance free batteries to provide instantaneous backup in case of power failure for 30 minutes complete with all necessary wiring for hanging arrangements as per manufacturers guidelines with following specifications :- TECHNICAL SPECIFICATION MAIN DOME SATELLITE DOME Intensity @ 1 Meter (Lux) 160000 + 10% 160000 + 10% Adjustable Field diameter (cm) 14-38 14-38 Depth of illumination L1+L2 (cm) > 100 > 100 Color Rendering Index (CRI) (Ra) 95 + 3% 95 + 3% Color temperature (K) 4500 + 10% 4,500 + 10% Intensity control (%) 25-100 25-100 Type of field focusing control By sterllizable By sterllizable handle handle (Dual Control: Manual and Remote) Type of Intensity control By control panel By control panel on lamp head on lamp head (Dual Control: Manual and Remote)
ELECTRICAL & MECHANICAL SPECIFICATIONS Power Supply input voltage (V) 220-230 V 220-230 V Power Consumption (W) < 150 < 150 Frequency (Htz) 50/60 50/60 Dome Diameter 500mm to 700mm 500mm to 700mm LED service life (hrs) > 50,000 > 50,000 Make :- Philips/Dr Mach/Hospedia medicare/ Stryker/ Dentis Note :- The contractor shall submit the details of Make/Model/Specification of the OT light for approval of GE before placing order. The Make and Model of OT light shall fulfill the requirement given here-in-before.
Supply , install, testing and commissioning of 30 KVA on line UPS with inbuilt isolation transformer and connected Battery Rack and link & Accessories including battery bank suitable for 30 Min back up with 2 Set of 20*12V/65AH Batteries and battery racks and terminal link with Battery fuse box and including connected accessories along with Mod Bus Card for connecting to UPS to BMS through RS485 & monitoring through BMS with development of adroid App for remote monitoring as per OEM standards complete all as specified and directed by Engg-in-charge. Note :- Detail specification for UPS mentioned in Particular specification .
Material and labour for earthing complete with gavanised steel earth plate electrode 60 cm x 60 cm x 6.3 mm thick burried directly into ground ( earth pit not less than 2.25 Mtrs below gorund level) with top edge of the plate not less than 1.5mtr beolw normal ground level, connected to galvanised earth strip 32 x 6mm size upto a distance of 7.5 mtr long by means of bolts, check nuts and washers of galvnised iron or steel all as shown in electrical plate no 5 at SSR Part-I of 2009 connected to earthing test point all as specified and indicated and testing complete including execvation earth work drilling holes for electrode PCC pit & cover , funnel , water pipe , lugs etc. complete all as specified and directed by Engg in charge. Note: Quoted rates shall be deem to include for earth wire with protection pipe up to 7.5 M length.
Material and labour for renewal of earthing complete with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly inTO ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanized steel wire 4 mm dia by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, medium grade, and 15 mm bore galvanised iron light grade for earth wire protection including all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm) with cast iron frame, with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion complete all as specified and directed. Note: Quoted rates shall be deem to include for earth wire with protection pipe up to 7.5 M length.
Supply , laying and testing cable XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt earthened of cross section of area 120 Sqmm of 3.5 Core complete all as specified and directed.
Supply , laying and testing cable XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt earthened of cross section of area 95 Sqmm of 3.5 Core complete all as specified and directed.
Supply , laying and testing cable XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty with standard aluminimum conductor 1100 Volt earthened of cross section of area 70 Sqmm of 3.5 Core complete all as specified and directed.
S & F distribution board (DB), double door (CRCA sheet) dust and vermin proof SPN 4 way with 200 Amps rated copper busbar, neutral bar, earth bar, IP 43 protection, single pole and neutral 250 Volts, flush to wall complete all as specified and directed. Make : Legrand Model: 507610 or equivalent in L&T/ Siemens/ ABB/ Schneider/ C&S Electric/ Crystal
S & F MCB TPN 63 Amp complete all as specified and directed.
M & L submain wiring using four run PVC insulated FRLS Copper conductor 10 sqmm with rigid non metalic PVC conduit of size 32 mm dia medium grade inclusive of boxes (junction/terminal) all tees, bends, elbows, reducers bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hook including all fixtures /fittings fixed on wall/ceiling with saddles PVC with earth continuity wire copper conductor PVC insulated unsheathed 10 Sq mm etc complete all as specified and directed. Note four runs of 10 sqmm copper FRLS cable & one run of 10 sqmm copper cable in and including 32 mm PVC conduit medium grade will be measured as one unit.
Supply, Laying, jointing and testing of under electric cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor laid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr-in-Charge for the following:-
4 core 10 Sqmm
4 core 16 Sqmm
M & L Sub main wiring using two single core PVC insulated FRLS cable 4 sqmm copper conductor multi stranded and 4.0 sqmm copper conductor insulated cable using as earth wire and drawing in to PVC conduit complete all as specified and directed. Note Two runs of 4sqmm copper FRLS cable & one run of 4.0 sqmm copper cable in and including 25mm PVC conduit medium grade will be measured as one unit.
M & L Sub main wiring using two single core PVC insulated FRLS cable 6 sqmm copper conductor multi stranded and 6.0 sqmm copper conductor insulated cable using as earth wire and drawing in to PVC conduit complete all as specified and directed. Note Two runs of 6 sqmm copper FRLS cable & one run of 6.0 sqmm copper cable in and including 32mm PVC conduit medium grade will be measured as one unit.
S & F MCB SPN, 240 Volts, 63 Amps complete all as specified and directed.
S & F MCB SP, 240 Volts, 40 Amps complete all as specified and directed.
Supply, installation, testing and commissioning of outdoor type 200 kVA Compact Package Substation, “Non walk in type” fabricated by GI Steel shall house having modular construction of Galvanized Sheet Steel. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for Transformer compartment. The enclosure exterior shall be powder coated. Enclosure should have slant roof suitable to avoid water accumulation. Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for each compartment, including PCC foundation 4 feet high of suitable size as per manufacturer instructions and having following equipments:- Make: Seimens/ABB/Schneider Note : (a) CSS shall be tested for IAC AB for 1 sec, considering utmost safety of Operator and pedestrian. (b)CSS ,RMU,LT Switchgear ,Vacuum Interrupter shall be of same make as CSS OEM to ensure life cycle optimization. (c)CSS shall be supplied by OEM only and not their authorized system integrators. Note :- The rates shall be inclusive of construction of making Platform as per OEM recommandatiion made with brickes and necessary PCC at Bottom and Top and plastering complete all as recommended by Engg-in-charge
(A) RMU 3 way type :- Indoor type Compact switch gear Ring Main unit built in type in CSS " CCV+ M " having 02 Nos. Load Break Switches and 01 Nos Vacuum circuit breaker all Motor Operated modules ( Total number of modules 3 Pcs + 1 Metering modules) ,with IP class as IP54 for outer door separately for CSS Enclosure , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X Note : (a) RMU shall be IAC AFL 20kA/1s tested to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU shall be completely motorized with all SCADA contacts terminated on a designated Terminal Block for easy Take off by the SCADA team for integration.Same contacts shall be clearly mapped in the Engineering drawings for approval with designated TB nos. for easy identification and integration. (e) RMU tank shall be of 304 grade ,Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (f) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site.
(B) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-2 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 95kV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs 150-300 - 02 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(C) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(D) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos (E) Metering Module Type M SafePlus M is an air insulated metering module. Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
(F) TRANSFORMER 200KVA 11KV/433V DYn11 Oil filled hermatically sealed transformer without conservator type of design & Top normal porcelein Bushings for HT & LT with Off load tap switch of rating +2.5% to -5% @2.5%. Temp Rise in Oil/Winding shall be 35/40 deg cel respectively (Make:- Nucon/Danish/Kotsons/Schneider/Cahors) Losses shall be as per IS1180 level 2 Max Losses at 50% Loading: 780 Watts Max Losses at 100% Loading: 2300 Watts Impedance: %Z - 4.5% (IS Tol.) WTI & OTI with Alarm & Trip Contact (G) LT PANEL 415V LT Indoor panel with Aluminium Busbars , Fabrication using 1.5/2 MM CRCA sheet steel , Ingress protection IP4X , complete with internal wiring consisting of following. MCCB 4 pole 400 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 01Nos MCCB 4 pole 200 Amps 36 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 02Nos MCCB 4 pole 100 Amps 16 KA (I/C)) with thermal magnetic release for over load and short circuit protection – 02Nos MCCB 4 pole 63 Amps 36 KA (O/G) – 02Nos Multi function digital meter cornel 4350 Make L&T or equivalent in Conzerv Panel wiring with 2.5 sqmm PVC sheathed, PVC insulated FR/HR stranded copper conductor cable through MCB DP 10 A mounted on DIN rail. Interconnection & Earthing Interconnection Between HT switchgear & Transformer using 1Cx3x95Sq.mm XLPE Single core cable & Interconnection between Transformer & LT switchgear using Busbars. Internal earthing connections shall be done by GI strips. - 01 Set
(H) APFC PANEL (100KVAR) 100KVAR (30KVAR x 2, 10KVAR x 3, 5KVAR x 2) Automatic power factor correction panel consisting of following 250A 433V 3P 50Hz 36KA Fixed Manual Type Moulded Case circuit breaker (MCCB) with thermal magnetic release for overload and magnetic shortcircuit (TMD) as Incomer for APFC. APFC RVT Relay (RVT) 30KVAR metallised polypropelen capacitor bank 10KVAR metallised polypropelen capacitor bank 5KVAR metallised polypropelen capacitor bank Capacitor duty contactor for switching on & switching off 30KVAR capacitor bank Capacitor duty contactor for switching on & switching off 10KVAR capacitor bank Capacitor duty contactor for switching on & switching off 5KVAR capacitor bank 63A,3P,10KA MCB for protection of 30KVAR Capacitor Bank 32A,3P,10KA MCB for protection of 10KVAR Capacitor Bank 16A,3P,10KA MCB for protection of 5KVAR Capacitor Bank Note :- (i) The Quoted rate shall include construction of foundation/plinth of PCC 1:2:4 type B-2 all as per manufacturer's instruction and standard drawing. Height of foundation shall be 800mm out of which 500mm shall be above ground level
Supply and installation, testing and commissioning of diesel Engine driven generating set of 160 KVA capacity 3 phase, 4 wire, 415 V, 1500 RPM AC power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integral acoustic enclosures (should have salient features) modular bolted construction, & pure polyester based coating to ensure long life in all weather conditions & for outdoor application / installation, integrated design thereby facilitating / easy handling. The design of integral acoustic enclosure should be approved by National Physical laboratory as per central pollution control board (CPCB) latest regulation / norms with fuel tank, battery & standard accessories, tools & spares as provided by manufacturer complete with necessary weather proof shed with MS pipe 80 mm dia for column and 40 mm dia MS pipe for beam and arms with CGI sheets and PCC foundations with block measonary work and plastering complete all as specified and directed by Engineer in charge with following specifications:-
(A) ENGINE- Water cooled diesel engine of at 1500 RPM capacity to match the 62.5 KVA alternator under NTP conditions with provision of 10 % over load for 1 hour in every 12 hours running confirming to BS 5514/ IS 10001/ 10002 the Engine shall consist of the following :- (i) Fly wheel with starter ring (ii) Flexible coupling with guard (iii) Cooling fan (iV) Radiator with guard and water pump engine mounted (V) Dynamo of suitable capacity (vi) Air cleaner heavy duty dry (vii) Fuel injection pump (viii) Radiator fan ( Blower type ) with guard (ix) Mechanical governor (x) Fuel filter (Mounted) (xi) Lubricating oil filters ( mounted) (xii) 12 v self regulating alternator belt driven by engine (xiii) Exhaust silencer heavy duty residential type (xiv) Corrosion resistor /scale inhibitor (xv) Starter 12 V DC (xvi) Lubricating oil cooler (xvii) Lubricating oil pump (Gear type ) (xviii) Turbo charger (xix) Exhaust piping shall be insulated with asbestos rope duly cladded with aluminium sheet.
(xx) Instrument panel complete with the followings :- (a) Auto manual Starting switch with key (b) Lubricating oil temperature gauge (c) Lubricating oil pressure gauge (d) Water temperature gauge (e) Battery charging ammeter (f) Battery charging indicating lamp (g) Hour meter with RPM indicator (h) Safety control against high temperature of water. (j) Safety control against low lubricating oil pressure . (k) Over speed stop with double driven adopter . (B) BRUSH LESS ALTERNATOR (i) Alternator coupled to engine indigenous make through a flexible coupling mounted on sturdy steel fabricated base frame suitable for mounting on a permanent foundation brushless alternator shall be confirming to BS -2613 or relevant of IS-4722/ IS 13364 (ii) Type ;- Self excited self regulated with automatic voltage regulator . (iii) Rating :- 62.5 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition . (iv) Speed;- 1500 RPM (v) System :- 415 V +/- 2.5 % AC 3 phase 4 wire 50 Hz. (vi) Connection :- 4 wire star connected . (vii) Enclosure ;- Screen protected drip proof . (viii) Ventilation :- Self ventilated. (ix) Insulation :- Insulation class H
(C) CONTROL PANEL The control panel with aluminium bas bar, bottom entry and exit of cable, current transformer, set of control fuses, Multifunctional Meter, it should display time and date, Volts, Frequency, Current, KW, KWH, PF, RPM, Cumulative Run Hours, Oil Pressure, Coolant Temp, Charging current (DC Amp Meter). Emergency off, factory made floor mounted, totally enclosed, epoxy powder coated suitable for 62.5 KVA DG Set including all necessary operating controlled devices as stated above and MCCBs as out going with protection fuse for panel instruments duly wired with flexible copper conductor cable and cable connection with lugs/thimbles complete as per latest IS/BS complete all as specified and directed. (D) ONE SET OF ACCESSORIES COMPRISING OF :- (a) Fuel tank -one No. fabricated with 3 mm thick MS sheet with necessary mild steel structure for mounting the tank higher than the DG set) with piping. Capacity of tank shall be to hold diesel sufficient for 16 hours running at full load, with following features :- (i) Level indicator. (ii) drain plug . (iii) MS class 'C' piping for inlet from pump to tank to engine. (iv) Fuel strainer. (v) Air vent. (b) Fuel PUMP;- Electrical operated fuel pump for filling diesel in the tank of adequate capacity with inlet connection to the tank with 5 meter flexible hose pipe heavy duty for suction of diesel from barrel.
(c) Sealed maintenance free Battery :- Heavy duty battery two no 24 plates 12 v 180 AH (1 Nos) connected to the system fully charged including lead and bty terminal's complete . (d) Base plate :- Fabricated out of MS channel's ISMC of suitable size suitable for fixing of DG set all specified by the manufacturer E) AMF PANEL ;- Supply & fix testing commisioning Auto main failure ( AMF) panel 15 SWG, 160 KVA DG Set Cubical consist of sheet steel enclosure of 2.00 mm thick totally enclosed dust and water proof duly painted with powder coated, ( shade No. 7032 Siemens gray ) fully wired up and ready to connect load & control lines in comprising the followings:- Make- Siemens/ Schnider/ Havells (a) Under Voltage relay 415V AC for main - 01 No. b) Under voltage relay 415 V AC for DG – 01 No. c) AC Timer 230 Volt, 2 No. +2 NC - 01 No. d) DC Timer 12/24 V - 01 No. e) Engine Start relay 12/ 24 V - 01 No. f) Control MCB SP 6 Amp. 230 V – 01 No. g) Transformer 12 / 24 V – 01 No. h) Rectifier suitable size – 01 No. i) LED Indicating Light for Main & DG - 06 Nos. j) LED Indicating Light for Main & Gen. ON – 02 Nos. k) LED Indicating Light for battery Charger – 01 No.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade 95 Sqmm ( Earth system) complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for in door termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Aluminium conductor cable of size 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 95 sqmm, Indoor/Outdoor type complete all as specified and directed.
Supply and fix 20 Amp Industrical type Plug and socket suitable for OT equipment connection suitable for Flush Mounting and surface mounting with Neutral Links with provision for mounting modular devices with inbuilt MCB DP 16 Amp complete all as specified and directed by Engg-in-charge. Make: Legrand, Model No 507860 or equivalent in Siemens/ ABB/ Schinder
Supply and fix 32 Amp Industrical type Plug and socket suitable for OT equipment connection suitable for Flush Mounting and surface mounting with Neutral Links with provision for mounting modular devices with inbuilt MCB TP 32 Amp complete all as specified and directed by Engg-in-charge. Make: Legrand, Model No 507861 or equivalent in Siemens/ ABB/ Schinder
Supply and fix 32 Amp Industrical type Plug and socket suitable for OT equipment connection suitable for Flush Mounting and surface mounting with Neutral Links with provision for mounting modular devices with inbuilt MCB DP 32 Amp complete all as specified and directed by Engg-in-charge. Make: Legrand, Model No 507863 or equivalent in Siemens/ ABB/ Schinder
Excavation in trenches not exc 1.5 m wide and n.exc 1.5 m in depth for foundation / fixing pole / laying cable and pipe line etc or for man hole etc not exc 10 sqm on plan and getting out in soft / loose soil complete all as specified and directed.
Returning filling in including spreading, levilling, watering and well ramming in layers, not exeecding 25 cm thick using excavated soil complete all as specified and directed.
Removing excavated Soil to a distence not exceeding 50 m and deposting where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Supply and fixing of 11 KV , 630 Amps, Outdoor type Compact switch gear Ring Main unit Extensible type " CCV+ M " having 02 Nos. Load Break Switches and 01 Nos Vacuum circuit breaker all Motor Operated modules ( Total number of modules 3 Pcs + 1 Metering modules) ,with IP class as IP54 for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foudnation work as recommended by manufactuer along with bottom cable entry and front cable termination with following specification :- (a) RMU shall be IAC AFLR 20kA/1s tested with gas release from top of the Switchgear to ensure utmost operator and pedestrian safety .Test report(from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU Note :- The rates inclusive of making Platform as per OEM recommandatiion made with brickes and necessary PCC 1:2:4 type B2 at Bottom and 1:2:4 type B1 Top and plastering complete all as specified and directed by Engg-in-charge
(A) 630A motorised Load Break Switch module for making of fault current alongwith Earth Switch of full making capacity-2 nos. Short time withstand current - 21KA/ 3 sec Making Capacity - 52.5kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38kV Impulse withstand voltage - 95kV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Snap action mechanism for manual operation Cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable Right angle non-touch proof Termination boots - 1 Set (R,Y,B) Set of 03nos. Ring Core Metering CTs 150-300 - 02 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos
(B) 630A motorised VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 nos. operated 630 A Vacuum circuit breaker having spring stored mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 21KA/ 3 sec Making Capacity - 52.5 kAp Auxiliary contacts - 1NO + 1NC Power frequency withstand voltage - 38KV Impulse withstand voltage - 98KV Nominal operating gas pressure - 1.4 Bar abs. Front cover mechanism - IP2X Cable covers - 3X Green(ON)/Red(OFF) push buttons to operate VCB. 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (C) Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Right angle non-touch proof Termination boots - 1 Set (R,Y,B)
(D) Stored energy mech. for motor operation - 01 Nos Control voltage, motor operation 24 V DC - 01 Nos Self Powered OC+EF Protection Relay - 01 Nos Set of 03nos. Ring Core Protection CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, 10P10 - 01 Nos Set of 03nos. Ring Core Metering CTs of ration 40-80A - 01 Nos as per feeder load, 2.5VA, Class 1.0 - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos Aux. Relay for generating Potential Free Contact from Capacitive Voltage Indicator - 01 Nos (E) Metering Module Type M SafePlus M is an air insulated metering module. Set of 03nos. single-phase potential transformers having ratio 11kV/rt3:110V/rt3, 25VA, Class 1.0 with HRC fuses for protection on primary side and MCBs for protection on secondary side.- 01 Nos Space Heater (230VAC)- 01 Nos Low Voltage Box inside the metering enclosure for mounting:- 01 Nos • Multifunction Meter for each feeder • CSPC make Under/Over Voltage Relay • 2x12VDC Battery+Charger scheme • R-Y-B Phase Indication Additional equipment delivered separately or mounted in respective panel. Set of Coupling busbars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle- 01 Nos
M&L for providing dry river sand as in sand cushioning to under ground electric cable including punning down of sand in layer complete all as specified and directed by Engg-in-Charge. Note: for measurement purpose punned thicness of sand only will be considered.
Supply and Laying burnt brick size 225 mm X 113 mm X 75 mm etc complete all as specified and directed.
N K BUILDERS
M P TYAGI ENGINEERS AND CONTRACTORS
Leo Air and Power Solution pvt Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .