Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.8 LAccepted-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹27.7 L+₹2.8 L (11.0%)Rejected-Finance 1ST SHAKUNTALA SADAN 04 RAMPURA BASTI LALGARH BIKANER RAJASTHAN 334001 | BIKANER | RAJASTHAN | 334001 | L2 | Rejected-Finance NOT BEING LOWEST BIDDER | |
| 3 | L3₹28.3 L+₹3.3 L (13.3%)Rejected-Finance | L3 | Rejected-Finance NOT BEING LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Aman Enterprises L3 | M/s Rohit Construction Co. L1 | J.D INFRA ENGINEERING L2 |
|---|---|---|---|---|---|---|
| 1.00 | Taking down U/S existing sub main wiring copper/ aluminium conductor including PVC or steel conduit/ casing and capping etc. | 1,460 | RM | 5 ₹7,300 Lowest | 10 ₹14,600 | 15 ₹21,900 |
| 2.00 | Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 16 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic ISI marked and accessories surface fixed on wall /floor etc all as specified.
Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. | 80 | RM | 550 ₹44,000 Lowest | 650 ₹52,000 | 680 ₹54,400 |
| 3.00 | Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 10 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit ISI marked and accessories surface fixed on wall /floor etc all as specified.
Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. | 90 | RM | 450 ₹40,500 Lowest | 500 ₹45,000 | 550 ₹49,500 |
| 4.00 | Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 6 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc all as specified.
Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. | 90 | RM | 350 ₹31,500 Lowest | 400 ₹36,000 | 450 ₹40,500 |
| 5.00 | Supply and laying sub main wiring complete with 03 runs ( Phase, Neutral & Earthing colour code) of single core 4 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc all as specified.
Note:- 03 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. | 250 | RM | 280 ₹70,000 | 250 ₹62,500 | 220 ₹55,000 Lowest |
| 6.00 | Supply and laying sub main wiring complete with 03 runs ( Phase, Neutral & Earthing colour code) of single core 2.5 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc all as specified.
Note:- 03 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. | 950 | RM | 220 ₹2,09,000 | 170 ₹1,61,500 | 150 ₹1,42,500 Lowest |
| 7.00 | Supply & fixing in repair LED 1x20 watt FLAME PROOF tube light fixture luminaire including integral reflector made of diecast alluminium alloy LM6 , with electronic ballast, bipin holders, .connector block, etc., and all accessories pre-wired and including connecting up with suitable size copper conductor twin core cable including taking out existing unserviceable normal or flame proof light complete all as specified and directed.
Crompton Cat Part No. of EXTN1LT8 16/20. or equivalent in Approved list of makes | 45 | Each | 5,500 ₹2,47,500 | 4,500 ₹2,02,500 | 4,250 ₹1,91,250 Lowest |
| 8.00 | S & F in repair round high bay light LED flameproof well glass in die cast AL housing with heat resisitant toughened glass suitable for Gas/Vapour group of IIA & IIB and zone 1 & 2 of 60 watt capacity including taking out existing unserviceable lights, complete all as specified and directed.
Crompton Cat part No.FWL1315-60-CDL or equivalent in Approved list of makes | 20 | Each | 4,800 ₹96,000 | 4,000 ₹80,000 | 3,880 ₹77,600 Lowest |
| 9.00 | Supply and fix in repair Flame proof - weather proof CMRI approved MCB socket & plug with 16 AMP rotary switch combined 16 A, 250V (2P+Earth) complete all as specified and as directed. | 12 | Each | 4,200 ₹50,400 | 3,500 ₹42,000 | 3,420 ₹41,040 Lowest |
| 10.00 | Supply and fix in repair Flame proof - weather proof CMRI approved 3 phase MCB socket & plug 32 Amp with rotary switch combined 500V(4P+Earth)complete all as specified and as directed. | 8 | Each | 5,000 ₹40,000 | 4,500 ₹36,000 | 4,350 ₹34,800 Lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
26 Jul 2025, 6:00 pmClosed
GE
GE
AS DESCRIBED IN BILL OF QUANTITIES
2025_MES_715190_1
GE (AF) NAL /T-27/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF NAL
AS PER NIT AND TENDER DOCUMENTS CATEGORY B(I) AND CLASS D AND ABOVE
9 documents required · 9 mandatory
₹500
GE AF NAL
₹60,000
Yes
28 Aug 2025
1 Jul 2025
28 Jul 2025
1 Jul 2025
26 Jul 2025
14 Jul 2025
1 Jul 2025 - 10 Jul 2025
Amount
Taking down U/S existing sub main wiring copper/ aluminium conductor including PVC or steel conduit/ casing and capping etc.
Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 16 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic ISI marked and accessories surface fixed on wall /floor etc all as specified. Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes.
Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 10 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit ISI marked and accessories surface fixed on wall /floor etc all as specified. Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes.
Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 6 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc all as specified. Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes.
Supply and laying sub main wiring complete with 03 runs ( Phase, Neutral & Earthing colour code) of single core 4 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc all as specified. Note:- 03 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes.
Supply and laying sub main wiring complete with 03 runs ( Phase, Neutral & Earthing colour code) of single core 2.5 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc all as specified. Note:- 03 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes.
Supply & fixing in repair LED 1x20 watt FLAME PROOF tube light fixture luminaire including integral reflector made of diecast alluminium alloy LM6 , with electronic ballast, bipin holders, .connector block, etc., and all accessories pre-wired and including connecting up with suitable size copper conductor twin core cable including taking out existing unserviceable normal or flame proof light complete all as specified and directed. Crompton Cat Part No. of EXTN1LT8 16/20. or equivalent in Approved list of makes
S & F in repair round high bay light LED flameproof well glass in die cast AL housing with heat resisitant toughened glass suitable for Gas/Vapour group of IIA & IIB and zone 1 & 2 of 60 watt capacity including taking out existing unserviceable lights, complete all as specified and directed. Crompton Cat part No.FWL1315-60-CDL or equivalent in Approved list of makes
Supply and fix in repair Flame proof - weather proof CMRI approved MCB socket & plug with 16 AMP rotary switch combined 16 A, 250V (2P+Earth) complete all as specified and as directed.
Supply and fix in repair Flame proof - weather proof CMRI approved 3 phase MCB socket & plug 32 Amp with rotary switch combined 500V(4P+Earth)complete all as specified and as directed.
Supply & fix in repair Flame proof Sheet metal enclsoure SPN 6 way for fixing MCBs 240 volt including MCB DP 32 A- 1 No as incomer & MCBs SP 6 to 16 Amps-4 Nos as outgoing complete all as specified and as directed.
Supply & fix in repair Flame proof Sheet metal enclsoure SPN 4 way for fixing MCBs 240 volt including MCB DP 20 A- 1 No as incomer & MCBs SP 6 to 16 Amps-2 Nos as outgoing complete all as specified and as directed .
Supply & fix in repair Flame proof Sheet metal enclsoure TPN 4 way for fixing MCBs 240 volt including MCB TPN 63 A- 1 No as incomer & MCBs SP 6 to 16 Amps-12 Nos as outgoing complete all as specified and as directed .
Supply & Fix in repair Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and as directed.
Supply & Fix in repair 3 way flame proof junction box suitable for carrying 4/6 sqmm 3 phase/single phase sub main wiring complete all as specified and as directed by Engr-In-Charge.
Supply & Fix in repair 4 way flame proof junction box suitable for carrying 4/6 sqmm 3 phase/single phase sub main wiring complete all as specified and as directed by Engr-In-Charge.
Supply and fixing in repair knobe suitable for existing flame proof SPN/TPN DB or rotary switch with complete all as specified and directed
M&L Dismantling blades, down rod, canopy and taking out burnt stator assy of flame proof/ weather proof ceiling fan 48"/56" sweep and taking down old burnt copper stator winding, cleaning stator slots, rewinding of stator assy with appropriate gauge of super enamelled copper winding wire, insulating material complete and assembling flame proof ceiling fan with flame proof cover and testing for proper function including provision of split pin of suitable sizes and writing MES No ( Letter size shall be minimum 5 mm width x 15 mm height) complete all as specified and directed. Note: (i) Cost of taking down of fan and re-fixing shall be included in the unit quoted rate (ii) The quoted rate for rewinding shall also include the rates of ball bearing/Bush bearing and capacitor of suitable size. (iii) painting and writing MES no also to be included in the quoted rate (iv) Contractor should be site visit before tender quoting.
M&L Dismantling blades, and taking out burnt stator assy of flame proof/ weather proof exhaust fan 300mm sweep and taking down old burnt copper stator winding, cleaning stator slots, rewinding of stator assy with appropriate gauge of super enamelled copper winding wire, insulating material complete and assembling flame proof exhaust fan with flame proof cover and testing for proper function including provision of split pin of suitable sizes and complete all as specified and directed. Note: (i) Cost of taking down of fan and re-fixing shall be included in the unit quoted rate (ii) The quoted rate for rewinding shall also include the rates of ball bearing/Bush bearing and capacitor of suitable size. (iii) painting and writing MES no also to be included in the quoted rate (iv) Contractor should be site visit before tender quoting.
S & F in repairs LED 150 W flood light fitting with lense, high luminous efficacy,protected to IP 66, toughened glass efficient high out put emitter LED for better distribution having surge protection 10 KV, sealed driver applicable for area lighting including electrical connection . Make : Crompton Cat Part No. LFLN-150-CDL/60-M or equivalent make in wipro and Philips
M&L for earthing complete with GI earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.50 Mtr below ground level. The earth plate to be connetced with earth lead of 4 mm dia galvanised iron or steel wire all as shown in para no 4 the earthing test point all as specified and directd.The GI earthing strip to be protected by galvanised iron pipe 15mm bore (medium grade) up to up to test point. Earthing shall be include with providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand and 2nd layer with 30 cm of Magnesium sulphate powder (compact thickness ) , 3rd layer with tibba sand up to the ground level. Earthing shall also be include for providing concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work including taking out old unsv earthing from existing location with complete all as specified and directed.
M & L for disconnecting the unserviceable cable from the transformer /panel board, cutting off worn out and Supply, laying and testing in replacement cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core including reconnecting the cable from existing with complete all as specified and directed.
All as above per item No 22.00 here-in-before but size 50 sqmm, 3.5 core.
All as above per item No 22.00 here-in-before but size 35 sqmm, 3.5 core.
All as above per item No 22.00 here-in-before but size 25 sqmm, 4 core.
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Returning filling in Including spreading, levelling. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for tiba sand for filling in trenches 8 cm below the UG Cable and 15 cm above the underground cables for cushioning of cables etc, complete all as specified. Note :- Punned thickness shall be measured for payment.
S&F sub class B bricks old size having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
M&L for bus bar chamber cubical inclined top out door type made out of 3 mm thick MS sheet of size minimum size 600 x 450 x 450 mm, MS angle section 35 x 35mm x 5mm frame with front and back openable double door with provision of locking arrangement dust & varmin proof , gasket, TPN busbar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof duly powder coated inside and outside of bus bar chamber with one coat of red oxide primer and two coat of synthetic enamel grey paint including aluminum busbar fixed horizontally in chamber of capacity 400 Amps for phases and 400 amps neutral for incoming and out going.(The gap between each bus bar should be minimum 100mm ) The panel shall be suitable for 415 volts, 50 Hz, 3 phase 4 wire system (suitable for 01 incomer and 06 outgoing ) and shall have MCCB 250 Amp 4 pole 36 KA as incommer, including taking out existing unsv bus bar chamber of any size with complete all as specified and directed by Engineer-in-charge Note :- (i) Earth work,1:2:4 PCC work for foundation and MS works shall be included in the unit qouted rate . (ii) Cable gland of brass for different size of cable as per requirement for incoming and outgoing cable
Supply and installation, testing, commissioning Outdoor type feeder piller Box factory made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 HZ supply factory made CPRI Approved, protection(IP -65) & MS angle section 40 x40x 5mm frame with front and back openable double door with provision of locking arrangement dust & varmin proof , gasket, TPN busbar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof duly powder coated inside and outside of panel with one coat of red oxide primer and two coat of synthetic enamel grey paint including taking out existing panel complete all as specifed and directed and consisting of the following equipments:-
Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 3.5 m below normal ground level) with top edge of earth plate not less than 2.5m below normal ground level, connected to galvanized iron strip 32X6 mm by means of electric arc welding of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other side complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe light grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI earthing and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply and fixing in repair EVE ER14250, 3.6V, 1200mAh 1/2AA lithium battery suitable for relay of Schneider RMU with complete all as specified and directed .
S&F as in repairs LED 70 W flood light fitting with lense, high luminous efficacy,protected to IP 66, toughened glass efficient high out put emitter LED for better distribution having surge protection 10 KV, sealed driver applicable for area lighting including electrical connection , complete all as specified and as directed. Make : Crompton Cat Part No. LFL-70-CDL/60-M or equivalent in list of makes.
S&F as in repairs LED 150 W high efficiency round highbay light fitting with lense, high luminous efficacy,protected to IP 66, toughened glass efficient high out put emitter LED for better distribution having surge protection 10 KV, sealed driver applicable for area lighting including electrical connection, complete all as specified and as directed. Make : Crompton Cat Part No. CIP-327-150-57-60D-HL2-LM-NSGor equivalent make in Havells and Philips
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine or manually without damage nearby electric cable, water pipe line etc including HDPE pipe of 40 mm dia suitable for 0.4 mpa working pressure and sealing the end of pipe complete all as specified and directed.
M& L for GI pipe light grade 40 mm dia for cable protection on wall/under road etc including fittings including taking out existing unsv GI pipe with complete all as specified and directed
Material and labour for LT cable route marker / LT joint marker made out of Jodhpur stone of size 250 mm width x 150 mm depth x 900mm height size with top oval shaped, engraved with 'LT cable' duly painted with approved colour with writing letter for both side, including necessary earth work, complete all as specified and directed by Engineer- in- Charge. Note: - (i) Route Marker shall be buried in ground upto a depth of 45cm below the natural Ground
J.D INFRA ENGINEERING (BID ID -3368183)
Aman Enterprises (BID ID -3364361)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .