| 1 | L1₹71.3 LAccepted-AOC 306 BAKSHI HOUSE 40 41 NEHRU PLACE NEW DELHI 110019 DELHI | SOUTH EAST | DELHI | 110019 | ₹71.3 L | L1 | Accepted-AOC L1 |
| 2 | L1₹1.3 CrAccepted-AOC | ₹1.3 Cr | L1 | Accepted-AOC L1 |
| 3 | NOT L1Rejected-Finance DIPENDRA PATIL E 66 MIDC AREA AJANTHA ROAD 94222 JALGAON MAHARASHTRA 425003 | JALGAON | MAHARASHTRA | 425003 | - | NOT L1 | Rejected-Finance NOT L1 |
| 4 | Not Admitted-Finance OLYMPIA PLATINA PLOT NO 33B SOUTH PHASE GUINDY CHENNAI 600032 | CHENNAI | CHENNAI | TAMIL NADU | 600032 | - | - | Not Admitted-Finance Techno-Commercially Acceptable. |
| Sl No | Description | Qty | Unit | VOLKS ENERGIE PVT LTD | Masstech Controls Pvt. Ltd. | CHHABI ELECTRICALS PRIVATE LIMITED |
|---|---|---|---|---|---|---|
| 1.00SUPPLY OF BATTERY CHARGER & BATTERIES | ||||||
| 1.01 | A) FOR MS BLOCK & INDMAX (SWITCHGEAR CONTROL POWER SUPPLY)
Following Battery Charger(s), DCDB & Battery system (110V DC) complete with all accessories in accordance with this specifications for Switchgear Control Power Supply
a. Battery Charger (Tag no: BC-118701 & BC-119701) - 110V, 170A, Dual redundant FCBC – 2 Nos
b. Battery Bank (Tag no: BB-118701A/B & BB-119701A/B): 2x50% configuration for each Battery charger, Ni-Cd battery bank of Capacity 350AH set for each battery charger with battery back up time of 120 Minute – 4 Sets
c. Non-integral type DCDB (Tag No. DCDB-118701 & 119701) – Refer DCDB feeder list (Doc.ID: 6745-ELT-405-EC-0005/0006) – 2 Nos
d. All Interconnecting cables from Battery charger to DCDB & Battery charger to Batteries etc. – 2 Lots
e. Switching devices/Battery isolators for each battery bank – 4 Nos
f. Condition monitoring system of Battery bank for each substation – Lot
g. Required Electrolyte with 10% extra for each Battery charger system – 2 Lots
h. Cell booster suitable for supplied battery rating – 2 Nos.
i. Accessories as specified in technical specification
SCOPE OF SUPPLY IS AS INDICATED ABOVE INCLUDING COMISSIONING SPARES, TOOLS AND TACKLES, TPI AND AS SPECIFIED IN MR DOCUMENTS FOR P25 PROJECT AT IOCL PANIPAT REFINERY. | 1 | Lot | 1,83,86,221.46 ₹1,83,86,221.46 Lowest | 2,40,48,288 ₹2,40,48,288 | 1,97,72,690.06 ₹1,97,72,690.06 |
| 1.02 | B) FOR MS BLOCK & INDMAX (CRITICAL LIGHTING)
Following Battery Charger(s), DCDB & Battery system (220V DC) complete with all accessories in accordance with this specifications for Critical Lighting
a. Battery Charger (Tag no: BC-118702 & BC-119702) - 220V, 30A, Dual redundant FCBC – 2 Nos
b. Battery Bank (Tag no: BB-118702A/B & BB-119702A/B): 2x50% configuration for each Battery charger, Ni-Cd battery bank of Capacity 50AH set for each battery charger with battery back up time of 120 Minute – 4 Sets
c. Non-integral type DCDB (Tag No. DCDB-118702 & 119702) – Refer DCDB feeder list (Doc.ID: 6745-ELT-405-EC-0005/0006) – 2 Nos
d. All Interconnecting cables from Battery charger to DCDB & Battery charger to Batteries etc. – 2 Lots
e. Switching devices/Battery isolators for each battery bank – 4 Nos
f. Condition monitoring system of Battery bank for each substation – Lot
g. Required Electrolyte with 10% extra for each Battery charger system – 2 Lots
h. Cell booster suitable for supplied battery rating – 2 Nos.
i. Accessories as specified in technical specification
SCOPE OF SUPPLY IS AS INDICATED ABOVE INCLUDING COMISSIONING SPARES, TOOLS AND TACKLES, TPI AND AS SPECIFIED IN MR DOCUMENTS FOR P25 PROJECT AT IOCL PANIPAT REFINERY. | 1 | Lot | 86,50,817.08 ₹86,50,817.08 Lowest | 1,22,08,578 ₹1,22,08,578 | 1,04,30,342.3 ₹1,04,30,342.3 |
Tender Value
Refer Docs
Closing Date
4 Jul 2024, 3:00 pmClosed
Mr. Nilesh Sathe
tkUIPL-Mumbai
SUPPLY OF BATTERY CHARGER AND BATTERIES FOR P25 PROJECT AT IOCL PANIPAT REFINERY
2024_REFHQ_177796_1
6745-PPM-000-CA-EL11
Limited
Electrical - All
Tender cum Auction
210 days
IOCL Panipat Refinery
Please refer Tender documents.
7 documents required · 7 mandatory
Exempted
9 Dec 2025
29 May 2024
5 Jul 2024
29 May 2024
4 Jul 2024
12 Jun 2024
SUPPLY OF BATTERY CHARGER & BATTERIES
A) FOR MS BLOCK & INDMAX (SWITCHGEAR CONTROL POWER SUPPLY) Following Battery Charger(s), DCDB & Battery system (110V DC) complete with all accessories in accordance with this specifications for Switchgear Control Power Supply a. Battery Charger (Tag no: BC-118701 & BC-119701) - 110V, 170A, Dual redundant FCBC – 2 Nos b. Battery Bank (Tag no: BB-118701A/B & BB-119701A/B): 2x50% configuration for each Battery charger, Ni-Cd battery bank of Capacity 350AH set for each battery charger with battery back up time of 120 Minute – 4 Sets c. Non-integral type DCDB (Tag No. DCDB-118701 & 119701) – Refer DCDB feeder list (Doc.ID: 6745-ELT-405-EC-0005/0006) – 2 Nos d. All Interconnecting cables from Battery charger to DCDB & Battery charger to Batteries etc. – 2 Lots e. Switching devices/Battery isolators for each battery bank – 4 Nos f. Condition monitoring system of Battery bank for each substation – Lot g. Required Electrolyte with 10% extra for each Battery charger system – 2 Lots h. Cell booster suitable for supplied battery rating – 2 Nos. i. Accessories as specified in technical specification SCOPE OF SUPPLY IS AS INDICATED ABOVE INCLUDING COMISSIONING SPARES, TOOLS AND TACKLES, TPI AND AS SPECIFIED IN MR DOCUMENTS FOR P25 PROJECT AT IOCL PANIPAT REFINERY.
B) FOR MS BLOCK & INDMAX (CRITICAL LIGHTING) Following Battery Charger(s), DCDB & Battery system (220V DC) complete with all accessories in accordance with this specifications for Critical Lighting a. Battery Charger (Tag no: BC-118702 & BC-119702) - 220V, 30A, Dual redundant FCBC – 2 Nos b. Battery Bank (Tag no: BB-118702A/B & BB-119702A/B): 2x50% configuration for each Battery charger, Ni-Cd battery bank of Capacity 50AH set for each battery charger with battery back up time of 120 Minute – 4 Sets c. Non-integral type DCDB (Tag No. DCDB-118702 & 119702) – Refer DCDB feeder list (Doc.ID: 6745-ELT-405-EC-0005/0006) – 2 Nos d. All Interconnecting cables from Battery charger to DCDB & Battery charger to Batteries etc. – 2 Lots e. Switching devices/Battery isolators for each battery bank – 4 Nos f. Condition monitoring system of Battery bank for each substation – Lot g. Required Electrolyte with 10% extra for each Battery charger system – 2 Lots h. Cell booster suitable for supplied battery rating – 2 Nos. i. Accessories as specified in technical specification SCOPE OF SUPPLY IS AS INDICATED ABOVE INCLUDING COMISSIONING SPARES, TOOLS AND TACKLES, TPI AND AS SPECIFIED IN MR DOCUMENTS FOR P25 PROJECT AT IOCL PANIPAT REFINERY.
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .