Executive Engineer
Electric Division Udhampur JPDCL
Boundary Wall Fencing Pathways Entry Gate Borewell Beautification and Provision of Solar Panels Electrification at Mand Udhampur on turnkey basis.
2024_PDD_262092_1
ED/Udh/27 of 2024-25 dt. 24-10-2024
Open Tender
Electrical and Maintenance Works
Turn-key
90 days
At Mand Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric DivisionJPDCL
₹24,600
19 Nov 2024
24 Oct 2024
16 Nov 2024
24 Oct 2024
14 Nov 2024
24 Oct 2024
24 Oct 2024 - 31 Oct 2024
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor for Boundary Wall Fencing Pathways Entry Gate Borewell Beautification and Provision of Solar Panels Electrification at Mand Udhampur.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plate with clamps
Anti Climbling device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of LT line on 8 mtr. ST pole, 30mm² ACSR Conductor for Boundary Wall Fencing Pathways Entry Gate Borewell Beautification and Provision of Solar Panels Electrification at Mand Udhampur.
8 mtr. Long poles (ST-410 SP15)
GI M Clamps for shackle insulator
30mm² ACSR Weasel conductor
Shackle insualtor
Galvanized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 8 mtr. Long ST poles with two coat of Aluminium paint
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioningfor creation of 25 KVA Sub Station for Boundary Wall Fencing Pathways Entry Gate Borewell Beautification and Provision of Solar Panels Electrification at Mand Udhampur.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11kV GO,AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
95mm² 1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Distribution Box for 25 KVA DTR with MCCB for incomer AND SFU's For outgoing Circuits.
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Earthing of substation -Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV Tapping Point for creation of 25 KVA Sub Station for Boundary Wall Fencing Pathways Entry Gate Borewell Beautification and Provision of Solar Panels Electrification at Mand Udhampur.
9 Mtr. Long Pole( ST-410 SP33)
GI V-Cross arm with Top Bracket including clamp
GI Channel/Angle Iron including clamps
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
50 mm sq. ACSR Cond.
PG Clamps
11 KV polymeric composite Pin insulator, 12kv, 5 kn, lightening impulse 75 KV Positive and 80 KV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts.
Danger plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 9 mtr. Long ST poles with two coat of Aluminium paint
Cement Bottoming 1:2:4 as per REC standards 0.45 cum per pole
Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
M/S MENGI CONTRACTOR (BID ID -2232381)
VEENA CONSTRUCTION CO. (BID ID -2223279)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .