Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.0 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹27.4 L+₹1.5 L (5.69%)Rejected-Finance PO BUD BUD DIST BURDWAN WEST BENGAL PIN 713 403 | BUD BUD | BURDWAN | WEST BENGAL | 713403 | L2 | Rejected-Finance Due to L2 |
Tender Value
₹29.3 L
EMD Value
₹58,600
Closing Date
23 Jul 2020, 6:00 pmClosed
Maj Narvekar Rohan GE
GARRISON ENGINEER AIR FORCE PANAGARH MES AIR FORCE STATION PANAGARH POST BIRUDIHA DIST BURDWAN WEST BENGAL 713148
PROVISION OF AIR CONDITIONER (02 TON) AND DEEP FREEZER AT CERTAIN LOCATION OF 31 WING, EARTHING PIT/ LIGHTINING ARRESTER AT VARIOUS LOCATION, PROVISION OF 3 PHASE POWER SUPPLY WITH INDEPENDENT MCB FOR INDIVIDUAL MACHINES ALONGWITH INDUSTRIAL SOCKE
2020_MES_355312_1
8586/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF STATION ARJAN SINGH
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (AF) PANAGARH
₹58,600
Yes
31 Jul 2020
24 Jun 2020
27 Jul 2020
24 Jun 2020
23 Jul 2020
8 Jul 2020
Amount
Supply, installation, commissioning and testing LT Panel Board factory made CPRI approved, IP 54 protection, weather, dust & vermin proof outdoor cubical compartmental type of size 800mm X 800mm X 400mm (over all dimension), double door, front and back side openable,with providing rubber/PVC gasket of suitable size all sides of door, panel made out of 2 mm thick mild steel CRCA sheet and shall be housed in separate outdoor enclosure of 2 mm with 50 x 50 x 6 mm size angle iron supporting frame and MC 75 channel base including applying two coats of Powder coated paint over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade with copper busbar wrapped with PVC tape/sleeves with maintained the colour code and copper strip busbar of size 20X3 mm or suitable amps coppper wire to MCCB input from main busbar and MCCB output of suitable length for connection of cable, including complete internal wiring with 1.5 sqmm copper wire and connections of all outgoing /incomming existing cable of any size drawing / digging out cable from loops in trenches inclusive of necessary excavation and earthwork as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size of aluminium luggs and cable gland for terminal connections of cables and fixed with suitable size nuts and botls of size as directed and embedded in PCC foundation (1:2:4 type B1 using 20 mm graded crushed stone aggregates) of size in cement mortar 1:6 and plastering the same in cement mortar 1:6 finished even and smooth without using extra cement complete all as specified and as directed comprising of the following fitment accessories :- Note: (a) Contractor shall be submit panel drawing before placing order and approved from GE. (b) Panel shall comply to IEC61439-Part I and II, Panel shall have certificate of salt mist test as per IEC-60068-2-11(anti corrosion) and damp heat cycling test as per IEC-60068-2-30, glass door IK 10 and 9 fold structure shall be design verified type and manufactured from OEM franchisee panel fabricator and fabricator shall sbmit franchisee cerificate from OEM. OEM Make: Schneider/ Siemens/ ABB/Legrand
INCOMMING
(a) Copper strip busbar of rating 300 amps wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 nos.
(b) MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Ics = 100% Icu, Lcu = 36 KA breaking capacity, rating 250 Amps including all fixing accessories with both ends spreader links - 01 No. Make :- ABB, Cat No: 1SDA068111R1 / Legrand Type DPX3 250 Cat No: 4202 49/ Schneider, Cat No: LV431640
(c) Supply and fixing changeover switch C-line type 200 Amps open execution type ,415 volt,50 cycles complete with operation handle. Make :- ABB / Legrand / Schneider
(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts,AC -01 set (set of three) Make :- Legrand/L&T/C&S.
OUTGOING
(b) MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Ics = 100% Icu, Lcu = 36 KA breaking capacity, rating 200 Amps including all fixing accessories with both ends spreader links - 01 No. Make :- ABB, Cat No: 1SDA068109R1 / Legrand Type DPX3 250 Cat No: 4202 48/ Schneider, Cat No: LV431641
(c) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No.
(d) Spare pocket for 01 Nos MCCB.
Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured, electric power cables (heavy duty) 1100 Volts grade conforming to IS 7098 with aluminium conductor multi-strand of cross-sectional area 300 Sqmm 3.5 Core laid in trenches / ducts/ inside protection pipeincluding cable glands, lugs and suitable size of MS saddle clips etc. all as directed by Engr-In-Charge. Make: Polycab(ISI Marked)/ Finolex(ISI Marked)/ KEI(ISI Marked) Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately
Supply and spread sand in trenches as sand cushioning to under ground cable for protection with fine river sand(dry) and provide reqd cover after punning down complete all as specified and directed. Note : (a) Thickness of sand cushion after punning down shall be 18 cm. (b) Thickness of sand cushioning shall be measured after punning down.
Material and labour for Plain precast concrete cable cover, class LV, type I, size 250 mm x 150 mm x40 mm to underground cables laid dry and flat abutting each other with gaps not exceeding 10 mm complete all as directed.
Excavating in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 sqm on plan and not exceeding 1.5 mtr in depth and getting out soft/loose soil complete all as specified.
Removing of surplus soil to a distance not exceeding 50 metre and deposited where directed at a level not exceeding 1.50 metre above the starting point all as directed by Engr-In-Charge.
Returning, filling in, trenches including Spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick all as specified.
Supply and fix GI Tubing 80 mm bore, light grade (ISI Marked) with all fittings (ISI marked) and fixed complete to wall and ceiling or laid in floor complete all as specified and directed Make:- Jindal/ TATA/ Prakash
Supply and fix GI Tubing 40 mm bore, light grade (ISI Marked) with all fittings (ISI marked) and fixed complete to wall and ceiling or laid in floor complete all as specified and directed Make:- Jindal/ TATA/ Prakash
Supply and fix triple pole and earth enclosure with three pin and earth plug and socket with one triple pole MCB of capacity 63 Amps,415 volts complete all as specified and directed. Make: L&T/ ABB/ Schneider/Legrand
Supply and fix triple pole and earth enclosure with three pin and earth plug and socket with one triple pole MCB of capacity 20 Amps,415 volts complete all as specified and directed. Make: L&T/ ABB/ Schneider/Legrand
Supply and fix single pole and earth enclosure with two pin and earth plug and socket with one single pole MCB of capacity 20 Amps,230-240 volts complete all as specified and directed. Make: L&T/ ABB/ Schneider/Legrand
Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured, electric power cables (heavy duty) 1100 Volts grade conforming to IS 7098 with aluminium conductor multi-strand of cross-sectional area 70 Sqmm 3.50 Core laid in trenches / ducts/ inside protection pipeincluding cable glands, lugs and suitable size of MS saddle clips etc. all as directed by Engr-In-Charge. Make: Polycab(ISI Marked)/ Finolex(ISI Marked)/ KEI(ISI Marked) Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately
Supply and fixing sub-main wiring with PVC insulated & sheathed four run of 4 Sqmm single core multistrand copper conductor cable (FRLSH), 1100 Volt grade alongwith two run of 2.50 Sqmm PVC insulated & sheathed copper conductor cable (FRLSH) 1100 Volt grade, connected to common earth dolly as earth continuity conductor, drawn through minimum 25 mm PVC conduit complete all as specified. Note:- (a) PVC conduit including accessories shall be measured and paid including the item. (b) 4 Run of line conductor and 2 Run of earth continuity conductor shall be measured as one unit length. (c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate. (d) Rate shall be included for cutting, pinning in, making good to facings where required for pointing in cement mortar 1:3 and cutting chases for concealed conduit wiring and making good, and cutting not exceeding 10 cm girth. Make:Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked)
Supply and fixing sub-main wiring with PVC insulated & sheathed four run of 6 Sqmm single core multistrand copper conductor cable (FRLSH), 1100 Volt grade alongwith two run of 4.00 Sqmm PVC insulated & sheathed copper conductor cable (FRLSH) 1100 Volt grade, connected to common earth dolly as earth continuity conductor, drawn through minimum 25 mm PVC conduit complete all as specified. Note:- (a) PVC conduit including accessories shall be measured and paid including the item. (b) 4 Run of line conductor and 2 Run of earth continuity conductor shall be measured as one unit length. (c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate. (d) Rate shall be included for cutting, pinning in, making good to facings where required for pointing in cement mortar 1:3 and cutting chases for concealed conduit wiring and making good, and cutting not exceeding 10 cm girth. Make:Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked)
Supply and fixing sub-main wiring with PVC insulated & unsheathed four run of 10 Sqmm single core multistrand copper conductor cable (FRLSH), 1100 Volt grade alongwith two run of 6.00 Sqmm PVC insulated & unsheathed copper conductor cable (FRLSH) 1100 Volt grade, connected to common earth dolly as earth continuity conductor, drawn through minimum 25 mm PVC conduit complete all as specified. Note:- (a) PVC conduit including accessories shall be measured and paid including the item. (b) 4 Run of line conductor and 2 Run of earth continuity conductor shall be measured as one unit length. (c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate. (d) Rate shall be included for cutting, pinning in, making good to facings where required for pointing in cement mortar 1:3 and cutting chases for concealed conduit wiring and making good, and cutting not exceeding 10 cm girth. Make:Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked)
Supply and fixing sub-main wiring with PVC insulated & sheathed two run of 2.50 Sqmm single core multistrand copper conductor cable (FRLSH), 1100 Volt grade alongwith one run of 1.5.00 Sqmm PVC insulated & sheathed copper conductor cable (FRLSH) 1100 Volt grade, connected to common earth dolly as earth continuity conductor, drawn through minimum 20 mm PVC conduit complete all as specified. Note:- (a) PVC conduit including accessories shall be measured and paid including the item. (b) 2 Run of line conductor and 1 Run of earth continuity conductor shall be measured as one unit length. (c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate. (d) Rate shall be included for cutting, pinning in, making good to facings where required for pointing in cement mortar 1:3 and cutting chases for concealed conduit wiring and making good, and cutting not exceeding 10 cm girth. Make:Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked)
Supply and fix SMDB-TN250D, O/G 100A 8 ways IP 43 with bus bar including fixing on the wall by means of screws and rawl plugs and making good disturbed surfaces to match with existing colour of wall completed all as directed. Note: (a) I/C MCCB's and O/G MCCB's will be measured and paid separately. Make: L&T/ ISI marked
Supply and fix DN1-250N 3 pole MCCB 200A, 16 KA SMDB type TN250D*, 415 V complete all as directed. Make: L&T/ ISI marked
Supply and fix DN0-100D 3 pole MCCB 100A, 16 KA SMDB, 415 V complete all as directed. Make: L&T/ ISI marked
All as per Item No 20 but 63A.
All as per Item No 20 but 32A.
Material and labour for GI strip 32 mm x 6 mm (conform to IS) as earth continuity conductor for mesh earthing or connection upto test point complete all as specified.
Material and labour for earthing with galvanised steel earth plate electrode 60 cm X 60 cm X 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below ground level connected to 32 mm x 6 mm thick GI strip protected by 40 mm bore light grade galvanised iron pipe and other end connected to test point as directed including funnel with wire mesh and watering pipe 20 mm bore medium grade galvanised iron pipe with charcoal and common salt in alternaterlayers of 15 cm thickness all around the GI plate electrode with concrete pit in PCC 1:3:6 type C-1 with cast iron frame including cast iron cover10mm thick hinged to CI frame and 8mm MS rod for handle, necessary excavation and earth wok in hard/dense soil and disposal of spoil to a distance n exc 50 m and necessary testing complete all as shown in electrical plate No 3 of SSR part-I all as specified. Note: (a)The earthing pit should be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed in AF station. (b) Excavation/earthwork is deemed to be included in the quoted rate.
Material and labour for earthing with galvanised steel earth plate electrode 60cmX60cmX 6mm thick,buried directly in ground(earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts,check nuts and washers of galvanised iron or steel, earth strip protected by and including GI Pipe 40 mm dia bore(light grade) and connected to main test point as directed and including Concrete Pit in PCC (1:3:6) type C1 precast RCC (1:1.5:3) type A1 cover slab 54 X 54 X 5 Cm reinforced with 8mm dia TMT bars@150mmC/C both ways with one handle for lifting made of 8mm dia TMT bar embeded in precast cover slab,funnel,wire mesh , 20 mm bore GI Pipe (medium grade) for watering charcoal and salt in alternate layers, incl necessary excavation and earth work in any type of soil complete all as shown on electrical plate no 3 of SSR part I complete all as specified. Note: (a)The earthing pit should be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed in AF station. (b) Excavation/earthwork is deemed to be included in the quoted rate.
Supply, installation, commissioning and testing hi wall split inverter air conditioner (outdoor and indoor unit), electric driven single phase, AC, 220 Vvolts complete with cordless remote control unit and with in-built air ioniser and plasma filter for better indoor quality with R410A refrigerant, minimum 3 star rating and EER 3.2 of capacity 2 TR complete all as manufacturer instruction. Make: Bluestar/Hitachi/Voltas/O-General/Carriers/LG/Samsung
Supply, installation, testing of electronic wall mounting AC voltage stabilizer 5 KVA capacity for fully automatic operation, single phase naturally air cooled indoor type and designed for working range between 70 volt to 280 volt time delay 3mts+/-20 sec ITDS. Make: V-Guard /Volina/ Blue Bird/Voltas
Supply and fix modular plug and socket 25 Amps, 3 pin 3 pole having 6 modules having motor starter modular type 25A, MCB mini SPN 25A 3KA, suitable for air conditioner 240V, 50Hz. Make:L&T/ ABB/ Schneider/Legrand
Supply and fixing sub-main wiring with PVC insulated & unsheathed two run of 4 Sqmm single core multistrand copper conductor cable (FRLSH), 1100 Volt grade alongwith one run of 2.50 Sqmm PVC insulated & unsheathed copper conductor cable (FRLSH) 1100 Volt grade, connected to common earth dolly as earth continuity conductor, drawn through minimum 25 mm PVC conduit complete all as specified. Note:- (a) PVC conduit including accessories shall be measured and paid including the item. (b) 2 Run of line conductor and 1 Run of earth continuity conductor shall be measured as one unit length. (c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate. (d) Rate shall be included for cutting, pinning in, making good to facings where required for pointing in cement mortar 1:3 and cutting chases for concealed conduit wiring and making good, and cutting not exceeding 10 cm girth. Make:Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked)
Supply and installed 401 ltr capacity deep freezer of minimum 30% power saving with minimum tempareture range (-)20 degree centigrade to (+) 8 degree centigrade and PUF thickness is 70-75 mm ,230V capacity lockable system. Make:Godrej / Blue Star/ Voltas
Supply and fix sheet metal enclosure MCB DB SPN with 100 Amp rated bus bar 6 way 240 V (double door type) with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/ stone masonry etc. and making good of disturbed surface to match with existing colour of wall complete all as specified. Make: ABB/ Siemens/ Schneider Note: (a) Quoted rates shall be deemed for brick wall / concrete wall cutting and making good as per existing surfaces.
Supply and fix MCB SPN 240 volts, 50 Hz capacity 6-32 Amps 'C' curve all as specified. Make: ABB/ Siemens/ Schneider/Legrand
Supply and fix MCB SP 240 volts, 50 Hz capacity 6-32 Amps 'C' curve all as specified. Make: ABB/ Siemens/ Schneider/Legrand
Supply, installation, testing of electronic voltage stabilizer 1 KVA capacity for fully automatic operation, single phase naturally air cooled indoor type and designed for working range between 170 volt to 280 volt time delay 3mts+/-20 sec ITDS. Make: V-Guard /Volina/ Blue Bird/Voltas
Supply & installation of advance encapsulated compound based CPRI tested maintenance free, pipe-in-pie technology upgraded (Zinc & Alloy coated), Zinc coated (80-100) microns with pure zinc (99.9%) & alloy coating (200-250) microns. Earthing system conforming IS 3034. The dia of pipe shall be 76.2 mm, 3 mtrs length, zinc coated with additional special alloy coating 300mm on th etop side for additional protection of the terminal. The angular space between the pipes being filled up with COMPACT FILL(CF) (Crystalline Conductive Compound). The COMPACT FILL (CF) mixture which is machine pressed in the pipes should not disintegrate or collapse when outer pipe corrodes. The inner pipe should be extended with terminals for connectivity. Digging the pits and refilling the same by Conductolite Back Fill compound (Ground Enhancer), In areas where soil condition is bad, good earth is to be arranged to fill the excavated pits. Mixing the good earth(replaced/same) with BFC 2 bags (Each bags should be 25 Kgs) per pit/unit. The BFC should be eco friendly, it should not contain environmental hazardous material/metal having RoHS Certification from NABL accredited lab. The earth pit should be provided with a FRP earth pit cover for protection and safe guard of terminals. As the earth electrode is the main component of the earthing system which is in direct contact with the ground and thus provided a means of releasing or collecting earth leakage currents. The materials should have good electrical conductivity and anti corrosion property in wide range of soil conditions. Make: ASHLOK/ ABB/ Smart Solution/True Power Note:(a) Earth Resistance should be less than 01 Ohms. (b)The manufacturer shall provide minimum 10 years warranty on each earth pit interms of ohmic value. (c) The excavation,removing excavated material shall be measured and paid separately. (b) The Payment shall only be allowed after production of original GST purchase vouchers (duly defaced by Engr- In -Charge) from Manufacturer and independent test certificate for earth resistance.
Supply only BFC electrolide 25 kg per bag
Supply and fix GI or steel wire 4 mm buried in ground including connecting at ends and jointing etc.
Supply and fix GI Tubing 15 mm bore, light grade (ISI Marked) with all fittings (ISI marked) and fixed complete to wall and ceiling or laid in floor or in cable protection complete all as specified and directed Make:- Jindal/ TATA/ Prakash
Excavating in trenches, not exceeding 1.5 mtr wide and exceeding 1.5 mtr but not exceeding 3 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 sqm on plan and and getting out soft/loose soil complete all as specified.
Supply and fix lightining arrestor rod set (copper bonded) 1 mtr height, 12 mm thick fixed on aluminium strip for earth conuctivity to ground complete all as directed.
Material and labour for aluminium strip 25 mm x 3.15 mm with saddles and fixing screws porcelain clit/ post insulators with hole fast screws etc. for roof conductors and down conductors above ground and burried in ground all as directed.
ROY ENTERPRISE
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .