Creation of 1x100KVA, 1x63KVA Sub Station alongwith HT/LT and Street Lighting at Newly Developed Infrastructural facilities at Baltal and adjascent areas-Retender.
2025_PDD_276125_1
EDG/V/029 OF 2025-26
Open Tender
Electrical Works
Lump-sum
20 days
BALTAL
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,000
Ex Engineer ED Ganderbal
₹45,100
13 May 2025
23 Apr 2025
6 May 2025
23 Apr 2025
5 May 2025
23 Apr 2025
23 Apr 2025 - 24 Apr 2025
Supply, Installation, testing & Commissioning of 63 kVA 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound , and with LV Cable Box having detachable Aluminium Gland plate
Supply, Installation, testing & Commissioning of 100 kVA 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound , and with LV Cable Box having detachable Aluminium Gland plate
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 9 Mtr. Long ST Poles with pit excavation [IS 2713 410 SP 33]
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles with pit excavation [IS 2713 410 SP 15]
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and Laying of 0.05 ACSR Conductor
Providing & fixing of GI Channel cross-arm (100 x 50x6mm) / 75x40x40 x6mm including back clamps of 50X8 mm for fixing Cross arm and pole top bracket, Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing Cross arm and pole top bracket . .
Supply,installation, testing and commissioning of Gapless Surge Arrestor, 9kV, 10KA LA with polymer housing, station type.
Supply,installation, testing and commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply,installation, testing and commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole,200 Amp, Vertical Type
Supply,installation, testing and commissioning of 11 KV Polymeric Composit pin with insulator insulator 12 KV, 5 KN,Light Impulse 75 KVPositive and 80 KV Negative ,Creepage distance 320 mm
Supply,installation, testing and commissioning of 11 KV Polymeric Composit disc insulator 12 KV,5KN, light impulse 75 KVPositive and 80 KV Negative ,Creepage distance 320 mm
Supply,installation, testing and commissioning of 185 mm² Single-Core Cable, 1.1kV Grade, XLPE un armoured FRLS type
Supply,installation, testing and commissioning of 35 mm² AB (HT) Cable (3x35+1x35 mm² insulated) mm² XLPE
Supply,installation, testing and commissioning of 240 mm² Single-Core Cable, 1.1kV Grade, XLPE un armoured FRLS type
Providing & Painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint)
Supply,installation, testing and commissioning of Galvanized Nuts and Bolts of sizes.
Providing & Laying of Cement bottoming 1:2:4 mix as per Standards 0.40 cum per pole for ( 8 Mtr)
Providing & Laying of Cement bottoming 1:2:4 mix as per Standards 0.45 cum per pole for ( 9 Mtr)
Providing & fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Providing & Laying of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm No.minal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover
Supply,installation, testing and commissioning of LT Distribution Box for 63 kVA DTR with 100 Amp MCCB 3P 16 kA for incomer & 100 Amp MCCB 3P 16 kA 1 No. and 63 Amp MCCB 3P 16 kA 1 No.s for Outgoing Circuits
Supply,installation, testing and commissioning of LT Distribution Box for 100 kVA DTR with 160 MCCB 3P 16 kA for incomer & 100 Amp MCCB 3P 16 kA 2 No.s for Outgoing Circuits
Supply,installation, testing and commissioning of GI wire
Supply,installation, testing and commissioning of Danger Plates with clamps with writing in English and Regional Language
Supply,installation, testing and commissioning of 16 KN Polymer Shackle Insulators LT
Supply,installation, testing and commissioning of GI Mukey for Shackle Insulator with Bolt of (50x6)mm
Supply,installation, testing and commissioning of GI Barbed Wire for Anticlimbing
Supply,installation, testing and commissioning of Anti Climbing Device with Clamps
Providing & fixing of Wedge Connectors/PG Clamps
Sundry Items like Aluminium Lugs, Jumpers, Binding Tape
Providing & Fixing of 7.0 mtr Long GI (65 micron DFT single dip) Octogonal poles uniformally tappered with thickness of 3mm with bottom/top Dia of 135 mm x 70mm & base plate of 225x225x12mm/pcd 250 mm provided with proper door opened gear box for connections on the bottom side with G.I. Foundation Bolts (J Type) M25x750 mm long (Set of 4 no.’s per pole)
Providing & Laying of RCC foundation for 7.0 mtr. Long Octagonal poles including proper curing. 0.55mX0.55mX0.8m (RCC with concrete ratio 1:1.5:3 with minimum 8 Nos. of 12 mm dia longitudinal MS reinforcement rods with rings of 8 mm dia not more than 200 mm C.C for fixing the pole).
Providing & fixing of Earthing of Octagonal Pole Complete by GI Pipe 40 mm or GI Rod 20mm 3 mtr long through GI Strip (25x3)mm
Providing & Fixing of Pre fabricate galvanized single way top bracket (1000 mm long with 48.3 OD GI Pipe) to be fitted on top of Octogonal pole for holding lighting luminaries.
Providing & fixing of DK thermoplastic cable Junction/ Termination T boxes 8"x10"of class IP55/IP65 fitted with two 2-5 Amp MCB strip,4-way terminal block / connectors Incl. copper lugs, Clamps ,nut & bolts washers etc (Hansel or equivalent make) or poles with two way type bracket to be fitted properly inside the door opened gear box provided on the bottom side of the pole.
Supply, Installation, testing & Commissioning of 200 Watt LED Luminaries of IP 66 protection.
Supply, Installation, testing & Commissioning of Surge Protector for the 200 watt LED type lighting fixture complete.
Supply, Installation, testing & Commissioning of 3x1.5 mm 2 PVC insulated multistrand flexible copper wire for service connections from connection plate to the LED luminary individual circuit including loop & earthings laid properly .
Providing & fixing of HDPE pipe 50 mm O/D and inner diameter 38mm including trench excavation in hard soil (0.3x0.45x1000m) for laying of 25/16 mm² Almunium armored cable . The job further inludes refilling back the same and removal of surplus excavated material to an appropriate place.
Supply, Installation, testing & Commissioning of LT 25 mm² 4 core Aluminium XLPE armoured cable to be carried through conduit/pipe U/G or A/G only in case of site constrains excluding cost of pipe & trench excavation.The cable shall include end termination lugs with its crimping /taping.
Supply, Installation, testing & Commissioning of LT 16 mm² 2 core Aluminium XLPE Armoured cable to be carried through conduit/pipe U/G or A/G only in case of site constrains excluding cost of pipe & trench excavation. The cable shall include end termination lugs with its crimping /taping.
Providing & fixing of Dust/rain/snow-proof canopy type mini-outdoor LT feeder panel of size 450X300mm with front door opening duly powdered colour coated with inbuilt 2No TPN 16-32 Amp MCCB,TPN busbars of same capacity installed on cement concrete block with 4 angle iron legs grouted in the cement concrete of termination of main 25 sqmm cable and outgoing 25/16 sqmm cable circuits
Pre and Post Geo tagged Photographic Evidence consisiting of 5x7 inch Photographs and Autocad Single Line Diagram
AL HASSAN ASSOCIATES (BID ID -2360974)
DREAMS GROUP (BID ID -2360728)
M/S HIBBA ELECTRICALS (BID ID -2366314)
southern (BID ID -2366269)
M/s NEW SUNDAS ENTERPRESIS (BID ID -2365990)
M/S DAR ELECTRICALS (BID ID -2366040)
Powermech Engineering Services (BID ID -2366176)
M/S BHAT ELECTRICAL & ELECTRONICS (BID ID -2365885)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .