Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹30.0 L
EMD Value
₹52,500
Closing Date
19 Sept 2022, 5:00 pmClosed
XEN Elect Division No II
XEN Elect Division NO II HPPWD Shimla-1
Providing pipe line with tubings fittings pressure gauges
2022_PWD_64729_1
ED.II.GA.Tender/22-23-4880-81 dated 07.09.2022
Open Tender
Electrical Works
Item Rate
30 days
Shimla IGMC
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
EE Electrical Division No II
₹52,500
23 Sept 2022
12 Sept 2022
20 Sept 2022
12 Sept 2022
19 Sept 2022
12 Sept 2022
Amount
Medical Grade Copper Pipeline With Tubings, Fittings, Pressure Gauges
The copper pipes shall be copper annealed ASTM B/75/B68 or equivalent standards.
The Diameter of the pipe should be suitable for 1000 LPM average flow and this pipeline will have to be divided into two in the oxygen supply plant and attached to two pipelines systems presently feeding the hospital.
Grossly the diameter should not be less than 38mm X 1.5mm or thicker so as to bear pressure of 10 -12 bar
All pipe work materials shall be manufactured by BS EN ISO 9001:2000 registered companies marking for sizes up to 108 mm, copper pipes shall be permanently and durably marked at regular intervals along its length with the following information
- The harmonised standard number EN 13348;
- Lloyds/BSI Kitemark or equivalent approved to EN 13348:2008
- Nominal dimensions, diameter x wall thickness;
- Temper designation to EN 1173;
- Manufacturer's identification;
- Date of production: year and month (1 to 12)
- Confirmation of degreasing for oxygen
Brazing shall be carried out flame source, temperatures and materials as per HTM/ NFPA recommendations
Brazed Pipeline Joints (Copper to copper) should be made using a silver-copper-phosphorous brazing alloy CP104 (5% Silver Brazing Filler metals Rod) to BS EN 1044-1999, no flux to be used.
Copper Fittings:
Medical Gas Pipeline Fittings shall be end feed type, manufactured from the same grade of copper as the pipes and be in accordance with the requirements of BS EN 1254-1:1998 Part 1. The manufacturing company should comply with BS EN ISO 9001:2000 and should be Kite Marked/Lyods or equivalent to EN 1254-1 (up to 54mm). Fittings should be factory degreased suitable for oxygen use and be supplied individually sealed in protective polythene bags. Fittings should be certified for medical use and accompany with oil analysis certificate and conformity certificate indicating suitability for medical use.
Protection for pipes
The pipelines in the bare area like space between buildings should be suitably protected and covered with fire resistant/ retardant insulation in such a manner that inner copper pipe does not come in contact with outer GI pipe. High Quality GI pipe quality covers which should be welded in such a way that only authorized person can open it using proper tools only. Further these should be of such a material and supported in such a manner so as to take load of monkeys/ langoors. Any such supports required should be quoted in the technical bid in the civil work.
Uncovered Sections of GI pipe will have to be protected with weather resistant stainless steel barbed wire.
The pipeline should be suitable for tolerating temperatures of (–) 10oC to (+) 30oC and high ambient humidity exceeding 90% and ice formation during winters. Given the length of the pipeline and climatic conditions, provision for expansion and shrinkage of metal should be incorporated.
All end connections, pressure gauges, valves and fittings of cascade shall be within tamper proof, see through and wire cage enclosure. These shall be on one side of cascade frame for ease of operation.
Parts of the pipe between the building blocks may have to be supported with columns/ beams of iron angle or concrete if necessary, which will have to be done by the firm laying down the pipeline.
The copper tube used for venting (if any) shall be of ASTM B75, B68.
Sizes of pipeline with above specification to be used.
O.D. 42 mm x 1.2 mm thick
O.D. 35mm x 0.9mm thick
O.D. 28mm x 0.9 mm thick
O.D. 22mm x 0.9mm thick
O.D. 15mm x 0.9mm thick
O.D. 12mm x 0.7 mm Thick
Pipes to be paid as per actual basis. Unused spare lengths will be returned
Alarms and Other Components
MEDICAL GAS AREA LINE PRESSURE ALARM
Area Gas Alarms It should comply with NFPA99 standard with American UL/ETL/ATL listed certificate.
Should be suitable for Oxygen, Air and Vacuum and Nitrous oxide
The medical gas area alarm should fully satisfy the requirement as per NFPA99 and should have American ETL/UL/ATL Listed certificates.
Master alarm for Plant room
2 GAS Services (O2,Vac)
Shut off Valves with Brass Fittings
Valve Box / Area Line isolation valve Box
2 GAS Services (O2,Vac)
Reciver Tank for vacuum 1500 Ltrs.
Single arm Cealing Pendent Anaesthesia
All services integrated in to the pendant system ensuring optimal safety.
Lateral arm -Large effictive field for convenient positionting.
Convenient positioning of gas equipment, electrical ad speciality services.
Service head ergonimics-Shelves/ Monitoring mounting solutions .
Hose connection - Gas specific NIST connectors.
Power supply - low smoke halogen cable through spiral conduit terminating at juction box.
Hygiene - Minimum visible screws, combined with smooth surface for easier cleaning and disinfection.
Configuration can be customized with in the limits of applicable standards.
6 Nos. Pre-piped & Customizable combinations .
DISS,BS,DIN, PB &Ohmeda (any one type) .
Four shutter type multi-standard socket compatiable to 5-6-10-13 A plugs and three 16 amps socket will be provided .
1- RJ 45 DATA Socket, 1 -RJ 11 Telephone Socket .
Horizontal medical Rail 320 mm - 3 nos. with clamp
Optional - Monitor stand with mounting bracket assembly and arm
Optional - Vertical round pole for Syringe Pump cum IV stand with clamps
Optional - Crimped medical gas tube to connect secondary device. Table top, Pole holder extentions, Shelves, Catheter Jar, Bottle holders. Utility basket, Rubbish bag holder, Clamps for medical rail, wire basket
Protective Earth , plug and socket for supplementary equipotential earth bonding
Class 2, IP51
Complete mounting system with NIST connection for gas & vac services and terminals for power connection
Alloy 6063 T6 : Extruded round aluminium profile (T= not less than 3 mm ). To specify length i.e. console 1224mm+Additional boom required
Alloy 6063 T6 : Etruded aluminium profile (T= not less than 2.5mm
Pre-engineered Rust - proof (passivate) Trivalent Zinc plated (8-10 um) steel
Epoxy coating to RAL 7035 (Textured)
ULTIMED SOLUTION
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .