Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.6 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹30.0 L+₹5.2 L (20.9%)Rejected-AOC 39 SR LAYOUT MAIN ROAD NAL WING TUNNEL ROAD MURUGESH PALYA BANGALORE 560 017 | BENGALURU URBAN | KARNATAKA | 560017 | L2 | Rejected-AOC Rejected | |
| 3 | L3₹36.5 L+₹11.7 L (47.3%)Rejected-AOC M S RRK PROJECTS D 306 ADG P CHENNAI 11 3RD CROSS SIR MV LAYOUT VIDHYARANYAPURA POST BANGALORE 560097 | BENGALURU URBAN | KARNATAKA | 560097 | L3 | Rejected-AOC Rejected | |
| 4 | L4₹37.7 L+₹12.9 L (52.1%)Rejected-AOC | L4 | Rejected-AOC Rejected | |
| 5 | L5₹40.6 L+₹15.8 L (63.7%)Rejected-AOC | L5 | Rejected-AOC Rejected |
Tender Value
Refer Docs
EMD Value
₹81,000
Closing Date
13 Jun 2024, 6:00 pmClosed
GE (AF) BANGALORE
GE (AF) BANGALORE, HQ TC AIR FORCE , BANGALORE - 560006
REPAIR/ REWINDING OF CEILING FANS, EXHAUST FANS, WALL MOUNTED FANS AND GEYSERS INCLUDING SPARES,OILING, GREASING AND PAINTING AND REPAIR/ REPLACEMENT OF EARTHING SYSTEM AND CONNECTED ITEMS INCL LIGHTENING ARRESTORS AT CHAF BANGALORE
2024_MES_654272_1
8237/E8
Open Tender
Civil Works
Item Rate
270 days
GE (AF) BANGALORE
AS PER NIT
5 documents required · 5 mandatory
₹500
GE (AF) BANGALORE
₹81,000
30 Aug 2024
16 May 2024
20 Jun 2024
16 May 2024
13 Jun 2024
30 May 2024
17 May 2024 - 23 May 2024
Amount
Taking down the ceiling fans 1200/1400mm sweep at site of any make and servicing of ceiling fan complete with greasing incl refixing the same after servicing checking properly by removing and replaced the unsv parts such as nut bolts, split pins rubber reel,necessary threading for rods etc.re-connecting the fans to ceiling rose/connector complete with 23 / 0.0076 " flexible twin core copper conductor cable from fan to ceiling rose/connector and re-assembling the same with proper accessories and testing complete all specified and directed. Note:(rubber reel to be measured and paid against relevant items)
Taking down the exhaust fans 300/380/450 mm sweep at site of any make and servicing of exhaust fan complete with greasing refixing the same after servicing checking properly by removing and replaced the unsv parts such as nut bolts, pins rubber bushes etc.re-connecting the fans to ceiling rose/connector complete with 23 / 0.0076 " flexible twin core copper conductor cable from fan to ceiling rose/connector and re-assembling the same with proper accessories and testing complete all specified and directed.
Taking down the wall mounted fan at site of any make and servicing of wall mounting fan complete with greasing refixing the same after servicing checking properly by removing and replaced the unsv parts such as nut bolts, split pins etc.re-connecting the fans to ceiling rose/connector complete with 23 / 0.0076 " flexible twin core copper conductor cable from fan to ceiling rose/connector and re-assembling the same with proper accessories and testing complete all specified and directed.
S&F ball bearing in replacement as per existing for ceing fan/exhaust fan/wall mounted fan complete all as specified and directed.
S&F in repair capacitor of cap 2.5 MFD paper type for fans complete all as specified and directed.
S&F in repair capacitor of cap 3.15 MFD paper type for fans complete all as specified and directed.
S&F in repair capacitor of cap 4 MFD paper type for fans complete all as specified and directed.
S&F in repair gun metal bush of size suitable for ceiling fan shaft complete all as specified and directed.
Taking down ceiling fan sealing cable end dismantling blades and removing unserviceable fan and blades to store for repair complete all as specified and directed.
Refixing exhaust fan after repairs and connecting up including provision of cable from ceiling rose /connector to fan complete all as specified and directed.
M&L for Rewinding of ceiling fan of size 1200mm sweep with super enamel copper wire as per existing size/gauge to achieve the required RPM as per manufacturers design including proper heating varnishing and provision of insulation etc and testing complete all as specified and directed.
Taking down exhaust fan of any size, sealing cable end, dismantling blades and removing unserviceable fan and blades to store for repair complete all as specified and directed.
Refixing exhaust fan of any size after repairs and connecting up including provision of cable from ceiling rose /connector to fan complete all as specified and directed.
M&L for rewinding of following exhaust fans with super enamel copper wire as per existing size/gauge to achieve the required RPM as per manufacturers design including proper heating varnishing and provision of insulation and testing complete all as specified and directed:-
Exhaust fan of size 300mm to 380mm sweep.
Exhaust fan of size 400mm to 450mm sweep.
Taking down unserviceable wall mounting fan to store for repair complete all as specified and directed
Refixing wall mounted fan after repairs and connecting to socket complete all as specified and directed
M&L for Rewinding of wall mounting fan with super enamel copper wire as per existing size/gauge to achieve the required RPM as per manufacturers design including proper heating varnishing and provision of insulating etc and testing complete all as specified and directed.wall mounting fan of size 400mm/ 450 mm sweep complete all as specified and directed
S&F in repair of exhaust fan blade metal body suitable for 450 mm complete all as specified and directed
S&F in repair of exhaust fan blade metal body suitable for 300 to 380mm complete all as specified and directed
S&F in repair of ceiling fan blade for 1200mm sweep metal body complete all as specified and directed
S&F in repair of fan blade for wall mounting fan 400/450mm acrylic body complete all as specified and directed
M&L for spray painting of ceiling fan complete in situ after necessary preparation of surfaces of ceiling fans of any size make complete and painting with one coat of synthetic enamel paint including filling cavities with filler after cleaning all dust etc and rewriting of MES Number etc complete all as specified and directed.
M&L for detecting faults at site of ceing fan,exhaust fan,wall mounting fan any type and make in CHAF area under AGE E/M CHAF and rectifiying the defects and make functional including replacing of unserviceable defective electrical/spares accessories Notes :- (i) Rate for any item shall be measured and paid under respective item of schedule. (ii) Essential material like, insulation tape,screws and all tools required for carrying out the works and instruments to the detect fault shall be deemed to be included in the quoted rate. (iii) The work is of day to day maintenace, required Electricians and Helper has to be attend daily for carryout the above work. (iv) Non rectification of complaints penal charge of Rs 300/- per complaint shall be imposed.
Taking Down and Refixing incl Painting of water heaters (Geysers) of 25/50 ltrs capacity of any make/model in site with synthetic enamel paint by brush including filling of cavities with fillers one coat after cleaning all dust etc including writing MES numbers etc all as specified and directed.
S&F in repair Heating element 1.5 KW capacity AC 230 V and conforming to IS specifications screw/flange type complete all as specified and directed
S&F in repair Heating element 2.0 KW capacity AC 230 V and conforming to IS specifications screw/flange type complete all as specified and directed
S&F in repair Thermostat suitable for water heater upto 80 litres capacity complete all as specified and directed
S&F in repair Non return valve 15 mm dia size complete all as specified and directed
S&F in repair PVC connection 15mm size with PTMT nuts of length 450 mm for hot water supply complete all as specified and directed
S&F in repair PVC connection 15mm size with PTMT nuts of length 600 mm for cold water supply complete all as specified and directed
S&F in repair PVC connection 15mm size with PTMT nuts of length 900 mm for cold water supply complete all as specified and directed
S&F in repair PVC insulated and FR PVC Round Sheathed, Copper Conductor(flexible) industrial cable, 1100 Volts 3 core flexible copper conductor cable of size 2.5 sqmm complete all as specified and directed
S&F in repair Plug top 3 pin 15 amps complete all as specified and directed.
S&F in repair Pressure release safety valve suitable for geysers upto 80 litres capacity complete all as specified and directed.
S&F in Replacement of old rusted /worn out MS bolts and nuts and grouting 4 nos new MS "T" bolts and nuts in brick walls ( MS bolt size 3/8 " x 6" with washers ) for fixing of Geyser and making good the disturbed surfaces incl plastering , curing etc complete all as specified and directed.
M&L for Replacement of Geysers from building and taking out the inner container(copper) and repairing the cracks by soldering /gas welding/Tinkering and reassembling the inner container, sealing the gap and refixing in same position of the building and testing complete all as specified and directed.
Supply and filling with compact packing of glass wool of suitable thickness for water heater of following capacity Water heater 25/ 50 litres cap complete all as specified and directed.
S&F in repair bottom assembly apparatus plate of copper for water heater of 25/50 litres capacity suitable to accommodate Thermostat, Heating Element as per existing Water heater of 25/ 50 litres capacity complete all as specified and directed.
S&F in repair outer body assembly complete with top and bottom for water heater of 25/ 50 litres capacity complete all as specified and directed.
S&F bib taps cast copper alloy with crutch or butterfly handle screwed for GI pipe 15mm dia chromium plated fancy type complete all as specified and directed.
S&F in repair Stopcock cromium plated screwed down High pressure with crutch or butterfly handle screwed both ends for iron pipe or for union complete for GI pipe 15mm dia complete all as specified and directed.
M&L for detecting faults at site in geysers of any type and make in CHAF area under AGE EM CHAF and rectifiying the defects and make it functional including replacing of unserviceable defective electrical/spares accessories complete all as specified and directed of any spares to be replaced. Note :- (i) Any spares shall be measured and paid under respective item of schedule (ii) Essential material like, insulation tape,screws and all tools required for carrying out the works and instruments to the detect fault shall be deemed to be included in the quoted rate (iii) The work is of day to day maintenace and required Electricians and Helper has to attend daily for carryingout the above work. (iv) For Non rectification of complaints, penal charges of Rs300/- per complaint shall be imposed.
S&F in repair of Single pole and neutral enclosure with a two pin and earth plug and socket complete with single pole 20A MCB ,C curve , 10KA as complete all as specified and directed.
M&L for descaling of geyser any capacity including inner container and bottom apparatus using rod, brush and soda lime and shall be made serviceable complete all as specified and directed.
S&F Ceiling Fan down rod of 450 mm length including fixing with fan Clamp complete all as specified and as directed.
S&F Ceiling Fan down rod of 600 mm length including fixing with fan Clamp complete all as specified and as directed.
S&F Ceiling Fan down rod of 900 mm length including fixing with fan Clamp all as specified and as directed.
S&F LED Bulbs 7 Watts, BEE star rated energy, efficient Retrofit bulb complete all as specified and directed. Make WIPRO, Model : TEJAS BULB, CAT NO : N75001 or Techno commercially Equivalent in BAJAJ/HAVELLS/ PHILPS
S LED Bulbs 9 Watts, BEE star rated energy, efficient Retrofit bulb, Make WIPRO, Model : TEJAS BULB, CAT NO : N95001 or Techno commercially Equivalent in BAJAJ/HAVELLS/ PHILPS
S&F LED Bulbs 12 Watts, BEE star rated energy, efficient Retrofit bulb complete all as specified and directed. Make WIPRO, Model : TEJAS BULB, CAT NO : N12501 or Techno commercially Equivalent in BAJAJ/HAVELLS/ PHILPS
S&F in repair LED lights fitting 1x 10 W, 220V,AC decorative box type with driver, holder including LED tube light connecting up, complete all as specified and directed. Make : BAJAJ, Model : ivora led batten, CAT NO : 830413, or Techno commercially eqivalent in HAVELLS/ CROMPTON, WIPRO
S&F in repair LED lights fitting 1x 20 W, 220V,AC decorative box type with driver, holder including LED tube light connecting up, complete all as specified and directed. Make : BAJAJ, Model : ivora led batten CAT NO : 830481, or Techno commercially eqivalent in HAVELLS/ CROMPTON, WIPRO
S&F in repair LED luminaire 600 mm x 600 mm, 36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cable of suitable size complete all as specified and directed.
S&F in repair LED Retro bar tube rod 20 W with single/double side connection including necessary connection suitable for tuberod all as specified and directed. MAKE : WIPRO, CAT NO: D612065, 20W or Techno commercially Equivalent in Havells/Indo asian/ BAJAJ/ HAVELLS
M&L in replacement of sub main wiring with PVC insulated cable with 2x6 sqmm copper conductor multistranded 1100 volts grade 6.00 sqmm in and including heavy grade PVC casing and capping and its accessories with fixing arrangements on surface, wall, floor or ceiling etc including 6.00 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and directed. Note : One run of earth continuity conductor,one run of PVC casing capping and two run of copper conductor together taken as one length for measuring unit length.
All as per serial item No 55.00 here in before but for 2 x 4 sqmm copper conductor cable with 4 sqmm pvc insulated unsheathed copper conductor cable as earth continuity conductor.
All as per serial No 55.00 here in before but for 2 x 2.5 sqmm copper conductor cable 2.50 sqmm pvc insulated unsheathed copper conductor cable as earth continuity conductor.
Supply, installattion of anti suicide fan rod or smart fan down rod made up of MS white colour including taking down existing ceiling fan and refix the same after installation of rod all as per manufactures instructions, complete all as specified and directed for the following:- Make : Gold life / SAFEHALO or equivalent
For size of 260mm (10'')
For size of 300mm (12'')
For size of 380mm (15'')
For size of 457mm (18'')
For size of 600mm (24'')
S&F in repair MCCBs 415V,, 4 Pole 100 Amps with breaking capacity 16 KA.complete with extension links and connection in panel board all as specified & as directed.
S&F in repair MCCBs 415V,, 4 Pole 125 Amps with breaking capacity 16 KA.complete with extension links and connection in panel board all as specified & as directed.
S&F in repair MCCBs 415V,, 4 Pole 160 Amps with breaking capacity 16 KA.complete with extension links and connection in panel board all as specified & as directed.
M&L in repairs earthing Complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically ( earth pit not less than 2.25 mtrs deep below ground level ) with top edge of the earth plate at a depth not less than 1.5 mtr below ground level, connected to galvanised eath lead wire 4.00 mm dia by means of bolts, nuts ,check nuts & washers of G I or steel all as shown in electrical plate no 3 SSR part I connected to earthing test point complete with all materials required for earthing all as specified or indicated including testing on completion . Note :- The rate qouted shall be inclusive for necessary Earth work excavating returning filling and 7.5m length of Earth lead wire alongwith its protection pipe as specified.
All as per serial item No 62.00 here in before but using copper plate 60x60cmx3.15mm thick electrode and 20x3mm copper strip as earthing lead complete all as specified and as directed .
S&F in repair earth continuity conductor GI wire 4.00 mm dia fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator etc complete all as specified and directed .
S&F in repair earth continuity conductor GI Strip 25 x 4mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator etc complete all as specified and directed .
S&F in repair earth continuity conductor copper Strip 20 x 3 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for direct/loop earthing with proper PVC/Porcelain insulator complete all as specified and directed.
S&F in repair 25x3.15mm aluminium strip earth continuity conductor or main earthing lead fixed with porcelain /PVC insulator on wall or roof top floor or recess or chases or buried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc complete all as directed
S&F in repair of PVC Polymer/Porcelain insulator for existing GI/Aluminium/copper strip support complete all as specified and directed .
S & F in repair for Test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25mm, drilled and screwed including 3 Nos. 8mm dia 25mm long hexagonal head screw complete fixed on wall in and including sheet steel enclosure of thickness 2 mm thickness with locking arrangement complete all as specified and directed.
S&F in repair air termination single pointed copper rod 12mm dia and 300mm long fixed on GI pipe 15mm approx 1mtr hight with base firmly on the roof top using PCC of size 30x30x30 cm and necessary screws,saddles complete all as specified and directed .
M&L for Repair/Reconditiong of exisitng earth pit by removing damaged Earth PCC chambers and excavate pit soil upto 25% of earth plate/electrode and adding alternate layers of charcoal, mixture of salt and copper sulphate up to 15cm above the earth plate/electrode and moist the mixture using water , cleaning/replacing of funnel with wire mesh where ever necessary ,testing the earthing after reconditioning that the earth resistance value should not be morethan 1.5 Ohms , making good to distrubed surface and complete all as specified and directed. Notes:- 1. Rate inclusive of including excavation, returning filling and connected items. 2. Salt , charcoal , copper Sulphate, pit chamber , Testing will be measured and paid seperatly
Supply only pure charcoal granular/aggregate type having Ash content < 5% , stone free for earthing complete all as specified and directed.
Supply only iodine free pure common salt crystal ( NaCl) for earthing complete all as specified and directed.
Supply only copper sulphate crystal (CuSO4) for earthing complete all as specified and directed.
M&L for Testing of earth resistance of existing earthing using calibrated 3/4 wire digital Earth resistance tester and recording the earth resistance value in register , obtaining the signature of user and MES executive after verification complete all as specified and directed. Note:- contractor has to provide digital earth resistance tester and should be available all the time during the contract period.
GKR and CO
RRK PROJECTS
Auromirra Enterprises
RAMSON TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .