| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.7 CrAccepted-AOC 1 SADHANA SOCIETY DEV BAUG DEVBAUG BHAVNAGAR GUJARAT 364001 UDYAM GJ 05 0006749 24AACFK2418A1Z4 B R MSME STATUS AS VERIFIED | BHAVNAGAR | GUJARAT | 364001 | ₹42.7 Cr | L1 | Accepted-AOC Being lowest (L1) and reasonable tender |
| 2 | L2₹42.9 CrRejected-Finance | ₹42.9 Cr | L2 | Rejected-Finance Not being lowest bidder |
| 3 | L3₹43.6 CrRejected-Finance | ₹43.6 Cr | L3 | Rejected-Finance Not being lowest bidder |
| 4 | L4₹43.9 CrRejected-Finance | ₹43.9 Cr | L4 | Rejected-Finance Not being lowest bidder |
| 5 | L5₹53.6 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹53.6 Cr | L5 | Rejected-Finance Not being lowest bidder |
Tender Value
₹37 Cr
EMD Value
₹15 L
Closing Date
20 Mar 2020, 6:00 pmClosed
CE NAVY MUMBAI
CE NAVY MUMBAI, 26 ASSAYE BUILDING COLABA-400005
CONSTRUCTION OF CRITICAL REQUIREMENT DWELLING UNITS OUTSIDE MAP AT INS MANDOVI GOA
2019_MES_293144_1
87776/E8
Open Tender
Civil Works
660 days
GOA
As per tender documents
8 documents required · 8 mandatory
₹3,000
GE(Project) Vasco
₹15 L
Yes
CE NAVY MUMBAI
14 Sept 2020
26 Oct 2019
27 Mar 2020
26 Oct 2019
20 Mar 2020
5 Mar 2020
12 Nov 2019 - 16 Nov 2019
12 Nov 2019
Amount
Total amount of Sch 'A' Part-I (BUILDINGS & STRUCTURES) brought forward from Serial Page No. 28 (R)
Total amount of Sch 'A' Part-II ( EXCAVATION , EARTH WORK & SITE CLEARANCE ) brought forward from Serial Page No. 30(R)
Total amount of Sch 'A' Part-III (INTERNAL WATER SUPPLY & HOT WATER SUPPLY ) brought forward from Serial Page No.31 (R)
Total amount of Sch 'A' Part-IV ( INTERNAL ELECTRIFICATION ) brought forward from Serial Page No.35 (R)
Total amount of Sch 'A' Part-V ( TV & TELEPHONE CONDUITS )brought forward from Serial Page No.36
Total amount of Sch 'A' Part-VI ( INVERTER )brought forward from Serial Page No. 37
Total amount of Sch 'A' Part-VII ( SEWAGE DISPOSAL ) brought forward from Serial Page No. 39(R)
Total amount of Sch 'A' Part-VIII ( AREA DRAINAGE) brought forward from Serial Page No. 41 (R)
Total amount of Sch 'A' Part-IX ( EXTERNAL WATER SUPPLY ) brought forward from Serial Page No.43(R)
Total amount of Sch 'A' Part-X ( EXTERNAL ELECTRIFICATION ) brought forward from Serial Page No.46 (R)
Total amount of Sch 'A' Part-XI ( LIGHTNING PROTECTION ) ) brought forward from Serial Page No. 47
Total amount of Sch 'A' Part-XII ( ROAD, PATH & CULVERT ) brought forward from Serial Page No. 49(R)
Total amount of Sch 'A' Part-XIII ( COMPOUND WALL ) brought forward from Serial Page No.50(R)
Total amount of Sch 'A' Part-XIV ( RETAINING WALL ) brought forward from Serial Page No.51
Total amount of Sch 'A' Part-XV ( CHAIN LINK FENCE & GATE ) brought forward from Serial Page No.53(R)
Total amount of Sch 'A' Part-XVI ( SEWAGE TREATMENT PLANT B&R WORK ) brought forward from Serial Page No.54-B
Total amount of Sch 'A' Part-XVII ( LIFT ) brought forward from Serial Page No.66 (R)
Total amount of Sch 'A' Part-XVIII (FIRE PROTECTION) brought forward from Serial Page No 71
Total amount of Sch 'A' Part-XIX ( RAIN WATER HARVESTING ) brought forward from Serial Page No 71-B
Sch 'A' Part- XX - MISCELLANEOUS ITEMS (Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.-5 signifies this fact only.)
INTERNAL WATER SUPPLY :- S&F Concealed stop cock 20 mm dia regular bodywith adjestable wall flange Make - Jaquar Model No CQT-23089 or equivalent in Crab Tree/Kohler brand as approved.
S&F Over head Shower 120 dia with wall mounted shower arm Make - Jaquar Model No OHS-1789&SHA-477 or equivalent
S&F Long body Bib cock 15 mm dia Make- Jaquar Model No CON-107KN or equivalent
S&F Bib cock with Wall flanged 15 mm dia Make- Jaquar Model No CON- 037KN or equivalent
S&F Shower Wall mixer 15mm 2 in 1 Make - Jaquar Model No CON-273knupr or equivalent
S&F Angular stop cock of 15 mm Bore dia. With wall flange Make- Jaquar Model No CQT-23059 or equivalent
S&F Pressure Reducing Valve 32 mm having direct-weld connections to eliminate leak potential, serviceable function module with V-port design, Low temperature steel body, media range: -76 ºF to +248 ºF and 102 psig rated
Supply, installation, testing and commissioning of PN 1.0 rated 50 mm CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories all complete as specified and directed.
Supply, installation, testing and commissioning of PN 1.0 rated 80 mm CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories all complete as specified and directed.
Supply, installation, testing and commissioning of PN 1.0 rated 65 mm CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories all complete as specified and directed.
S & F of PN 1.0 rated 40 mm CI ball valve, screwed female end and necessary accessories all complete as specified and directed.
S & F of PN 1.0 rated 32 mm CI ball valve, screwed female end and necessary accessories all complete as specified and directed.
S&F Pressure Reducing Valve 50 mm having direct-weld connections to eliminate leak potential, serviceable function module with V-port design, Low temperature steel body, media range: -76 ºF to +248 ºF and 102 psig rated
S&F Pressure Reducing Valve 40 mm having direct-weld connections to eliminate leak potential, serviceable function module with V-port design, Low temperature steel body, media range: -76 ºF to +248 ºF and 102 psig rated
EXTERNAL WATER SUPPLY:- Supply and laying Ductile iron pipes with spigot and socket ends centrifugally cast, Class K-9, in any length laid in trenches of size 100 mm dia Incuding rubbur Tytan joint
Supply install test and commissiong of centrifugal pump set , electric driven complete with all accessories suitable for pumping water 480 LPM discharge at 68 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as , necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for building) Note : For Fresh water G+13 & G+5
Supply install test and commissiong of centrifugal MONOBLOCK pump set , electric driven complete with all accessories suitable for pumping water 180 LPM discharge at 68 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as , necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for building) Note : For flushing water G+13 & G+5
Supply install test and commissiong of centrifugal MONOBLOCK pump set , electric driven complete with all accessories suitable for pumping water 270 LPM discharge at 52 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as , necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for building)(Note - For fresh water G+10)
Supply install test and commissiong of centrifugal MONOBLOCK pump set , electric driven complete with all accessories suitable for pumping water 120 LPM discharge at 52 m head coupled with suitable size of electric motor AC 3 phase ,50Hz including supply and fixing the items, such as , necessary connection from starter to motor terminal using proper size of copper cable including ,connection of suction pipe from pump to foot valve, delivery pipe connected to the raising mains of the over head rservoir by means of suitable joints painting the suction and delivery pipe with super enamel paint over a coat of primer as per standared code of colour including MS base plate complete complete all as specified and directed.Note : Suction and delivery pipes shall be measured and paid under appropriate items ( main water supply pump for building) Note: For fresh water G+10
Note for item nos Item Nos 22.15 to 22.18 - Energy Efficient Motors-Motors shall comply with following a. All permanently wired poly phase motors of 0.375kW or more serving the building and expected to operate more than 1500 hours per year and all permanently wired poly phase motors of 50kW or more serving the building and expected to operate more than 500 hours per year shall have a minimum acceptable nominal full load motor efficiency not less than IS 12615 for energy efficient motors b. Motors of horsepower differing from those listed in the table shall have efficiency greater than that of the next listed kW motor 0.64% c. Motor horse power rating shall not exceed 20% of the calculated maximum load being served, d . Motor nameplate shall list the nominal full- load motor efficiencies and the full load power factor
e. Motor users should insist on proper rewinding practices for any rewound motors. If the proper rewinding practice can not be assured, the damaged motor should be replaced with a new, efficient one rather than suffer the significant efficiency penalty associated with typical rewind practices f. Certificates shall be obtained and kept on record indicating the motor efficiency. Whenever a motor is rewound, Appropriate measures shall be taken so that the core characteristics of the motor is not lost due to thermal and mechanical stress during removal of damaged parts after rewinding a new efficiency test shall be performed and a similar record shall be maintained
Supply, installation, testing and commissioning of PN 1.0 rated CI 'Y' -type strainer 80 mm dia for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps all complete as specified and directed.
Supply, installation, testing and commissioning of PN 1.0 rated CI 'Y' -type strainer 50 mm dia for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps all complete as specified and directed.
Supply and fix CI sluice valve 100 mm dia both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.0 ISI marked complete all as specified and directed. Make : Kirloskar/Upadhyay/L&T
Supply and fix CI sluice valve KIRLOSKAR/UPADHYAY/L&T MAKE both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.6 ISI marked complete all as specified and directed of sizes 100 mm
Supply and fix CI sluice valve 80 mm dia both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.0 ISI marked complete all as specified and directed. Make : Kirloskar/Upadhyay/L&T
Supply and fix CI sluice valve 50 mm dia both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.0 ISI marked complete all as specified and directed. Make : Kirloskar/Upadhyay/L&T
Supply and fix cast iron double ball air release valves of size 20 mm outlet Sutaible for 100 mmDI/CI pipeas per IS 14845, PN rating H-7 ISI marked. MAKE : Kirloskar/Upadhyay/L&T
Supply,& fix rated CI swing check type Gunmetal reflux (non return) valve 80 mm dia with flange drilling standard end connection and necessary accessories all complete as specified and directed. Make: Kirloskar, Leader, Venus
Supply,& fix rated CI swing check type Gunmetal reflux (non return) valve 50 mm dia with flange drilling standard end connection and necessary accessories all complete as specified and directed. Make: Kirloskar, Leader, Venus
Supply,& fix rated CI swing check type Gunmetal reflux (non return) valve 40 mm dia with flange drilling standard end connection and necessary accessories all complete as specified and directed. Make: Kirloskar, Leader, Venus
Supply and fix CI double end flanged and drilled non return valve of size 100 mm dia PN-1.6 ISI MARKED KIRLOSKAR/UPADHYAY/L&T
M & L for Construction of fly-ash brick masonary valve chamber of size 900 mm X 900 mm X 1000 mm (internal dimenssions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in soft rock /hard Dense soil , 6 mm thick MS sheet cover fixed on 25 mm X 25 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC coping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil / rock to a distance not exceeding 50 m etc complete all as specified and directed. [ Ext Water Supply - 04 )
Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type "Water Supply Panel" of suitable size, conforming to IEC 61439-1 & 2, IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 42 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. [Make: Schneider Blokset, Siemens, ABB]
The Water Supply Panel shall comprise of the following:
[a] Busbar Chamber:
[i] Copper busbar of rated capacity 250 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
[b] Incoming:
[i] 100 A, 415 V, Ics = Icu = 25 kA, 50 Hz, FP MCCB with adjustable overload settings (0.36- ` X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 No.
[ii] LED phase indicators (Red, Yellow, Blue)- 01 Set
[iii] Power Measurement Device with Class 1 accuracy, complying to IEC 62053- 22, 64 samples/cycle, 31st harmonic analysis, RS485, calibration LED, third party accuracy test certificate - 01 No.
[c] Outgoing:
[iii] 32 A, 10 kA, 230 V, 50 Hz TPN MCB (c -curve)- 02 Nos. for domestic pump
[iii] 20 A, 10 kA, 230 V, 50 Hz TPN MCB (c -curve)- 02 Nos. for flushing water supply pump
[iv] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 06 Nos.
(V) Single phasing preventer -04 No
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 04 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type "Water Supply Panel" of suitable size, conforming to IEC 61439-1 & 2, IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 42 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. [Make: Schneider Blokset, Siemens, ABB]
The Water Supply Panel shall comprise of the following:
[a] Busbar Chamber:
[i] Copper busbar of rated capacity 125 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
[b] Incoming:
[i] 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz, FP MCCB with adjustable overload settings (0.36- ` X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 Nos.
[ii] LED phase indicators (Red, Yellow, Blue)- 01 Set
[iii] Power Measurement Device with Class 1 accuracy, complying to IEC 62053- 22, 64 samples/cycle, 31st harmonic analysis, RS485, calibration LED, third party accuracy test certificate - 01 No
[c] Outgoing:
[iii] 32 A, 10 kA, 230 V, 50 Hz TPN MCB (c -curve)- 02 Nos. for domestic pump
[iii] 20 A, 10 kA, 230 V, 50 Hz TPN MCB (c -curve)- 02 Nos. for flushing water supply pump
[iv] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
(V) Single phasing preventer -04 No
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 04 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
Supply and laid spigot/flanged/ socketed DI fittings. Such as bends (any type radius and angle), tapers, tees, collars & tail piece socket/flanged/spigot etc of size 80mm to 300mm dia.
INTERNAL ELECTRIC SUPPLY
S & F 20 W surface/wall mounted LED batten, extruded aluminium housing with PC diffuser and integrated electronic driver with high efficiency long life LED chips, CRI ≥ 80, power factor ≥ 0.95, system luminous efficacy > 100, having average life 50000 hrs, operating voltage 140- 270, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the LED batten fitting. [Make: BAJAJ 112785 BCLAB 20W or equivalent in Philips , Wipro as approved.]
S & F 10 W surface/wall mounted LED batten tubelight, including LED tube/module, with PC diffuser and extruded aluminium anodised housing with LEDs as light source having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.98, CCT 6500K, THD < 10%, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the LED batten fitting complete all as specified and directed. [Make: BAJAJ 112407 BCLSB 10 WH or equivalent in Philips , Wipro as approved.]
S & F 9 W mirror light having indirect up-down light for mirror and as wall light application with CCT 6000K, including LED bulb/module and electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the tubelight fitting Make : Philips, Crompton, Bajaj, Wipro as approved
S & F 45 W LED security light having pressure die-cast housing with toughned glass and individual LEDs with secondary optics and IP 66 protection, including necessary electrical connections to security light fittings with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete all as specified and directed. [Make:BAJAJ 169907 BRLEP 45W LED WH or equivalent in Philips , Wipro as approved.]
S & F engery efficient high-speed ceiling fan having 1200 mm blade sweep, speed not less than 370 RPM, air-flow not less than 210 CMM, operating voltage 220-240 V and frequency 50 Hz, including a downroad of suitable size and electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fan complete all as specified and directed. [Make: CROMPTON EMPOWER 50 or equivalent]
S & F engery efficient non-metalic fresh air fan having blade sweep 230 mm, speed not greater than 1760 RPM, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed. [Make: CROMPTON VENTILUS or equivalent in Usha , Havells as approved.]
S & F engery efficient metalic exhaust fan, having blade sweep 300 mm, speed not greater than 1400 RPM, air delivery not less than 1850 CMH, operating voltage 220-240 V and frequency 50 Hz, ncluding electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the exhaust fan complete all as specified and directed. [Make: CROMPTON EXHD300-4-1 or equivalent in Usha , Havells as approved.]
S & F 63 A tap-off units with suitable rating of FP MCB/MCCB
Supply, installation, testing and commissioning of busbar trunking system of sandwich construction conforming to IEC 61439-6: 2012 as specified below.
[A] General
[i] Type of Conductor: Hard drawn aluminum with copper contacts at joints
[ii] Configuration: 3P + N + PE
[iii] Neutral: 100% of phase rating
[iv] Earthing: 50% of phase rating
[v] Earthing Type: Integral
[vi] Rated Current: 800 A
[vii] Rated Operating Voltage: 415 V ±10%
[viii] Operating Frequency: 50 Hz
[ix] Rated short-circuit withstand current for 1 second: 40 kV (Icw of aluminum integral earth should be 60% of phase busbar.)
[x] Impulse Withstand Voltage: 8 kV
[xi] Power Frequency Withstand Voltage: 2.5 kV for 5 s
[xii] Mechanical Impact Resistance: IK 10
[xiii] Degree of Protection: IP 54
[xiv] Type of Cooling: Natural Air Cooled
[B] Certification
[i] Type test certificate of compliance with IEC 61439-6
[ii] Certifying Authority: CPRI/KEMA/ASTA/DEKRA
[iii] Type of Certification: KEMA KEUR/ ASTA DIAMOND
[xi] Power Frequency Withstand Voltage: 2.5 kV for 5 s
[iv] Seismic Compliance: Zone IV
[C] Joint Pack
[i] Single/double bolt joint with shear off nit along with connection of earthing (no separate provision for earthing connection)
[ii] Earthing connection provision shall be in joint pack only.
[D] Material
[i] Conductor: Aluminum with bi-metal silver plated copper-clad
[ii] Earthing Conductor: Aluminum
[iii] Bus Joint: Silver plated bi-metal (Al/Cu) contact
[E] Housing
[i] Construction: Electrogalvanizes steel and aluminum with protective finish of suitable epoxy paint
[ii] The busbar trunking housing shall pass at least 1000 hours salt spray test
[F] Busbars
[i] Busbars shall be of aluminum with copper cladding utilized Molecular Fusion technology
[ii] There shall be no bolts passing through the busbars of the busway.
[iii] Each busbar shall be insulated with two layers of Class B DuPont Mylar insulation
[F] JOINT
[i] The busbar trunking joint shall be of the one-bolt type which utilizes a high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area.
[ii] The bolt shall be two-headed design to indicate when proper torque has been applied and require only a standard long handle wrench to be properly activated
[iii] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.
[I] FIRE RESISTANCE
[i] The busway shall be fire resistant – not create secondary fire outbreak in the event of fire.
[ii] 7.2 The busway shall not generate any toxic emission in the event of fire.
[iii] The busway shall be designed such as to ensure very low smoke and zero halogen in the event of a fire to give better visibility aiding the rescue operation and enabling the EXIT path to be seen clearly for escape.
[J] Plug-in Hole
[i] The connecting jaw of the plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is not allowed.
[ii] All contact on joint and plug-in opening should be silver plated copper.
[iii] Busbar trunking shall be installed so that plugs are side mounted to permit practical use of all plug-in openings.
[iv] It shall be possible to inspect the plug-in opening and busbars prior to the installation of the plug-in units.
[v] Presence of Transparent shield shall be inside to avoid direct contact of human
[vi] The plug-in units shall be equipped with internal barriers to prevent accidental contact of fish tape and conductors with live parts on the line side of the protective device during time of wire pulling
[K] End Feed Unit
End feed unit shall be manufactured as per site condition and space availability. Vendor to get drawing approval from certifying authority before manufacturing.
[L] Confirmation of Spares:
Manufacturer of busway shall give minimum assured written declaration for availability of spares for min 10 Years after product commissioning.
[M] Missing Link Provision
Manufacturer of busway shall keep missing link provision to accommodate probability of minor changes in equipment positioning / adjustment. Manufacturer should be able to deliver missing link within 7 working days.
Straight Length Riser
90° Elbow
Flange End
End Feed Unit with suitable rating of ACB, fabricated as per site conditions
Support Bracket/Hanger for horizontal installation
Spring Hangers for vertical installation
End Cover
Supply, installation, testing and commissioning of busbar trunking system of low impedance and air insulated type technology conforming to IEC 61439-1 & 6: 2012 as specified below.
[A] General
[i] Type of Conductor: Laminated bi-metal aluminum conductor, air-insulated and supported on firberglass reinforced polyester isolators
[ii] Configuration: 3P + N + PE
[iii] Neutral: 100% of phase rating
[iv] Earthing: 50% of phase rating
[v] Earthing Type: Integral
[vi] Rated Current: 250 A
[vii] Rated Operating Voltage: 415 V ±10%
[viii] Operating Frequency: 50 Hz
[ix] Rated short-circuit withstand current for 1 second: 10 kV (Icw of aluminum integral earth should be 60% of phase busbar.)
[xiii] Degree of Protection: IP 54
[ixv] Type of Cooling: Natural Air Cooled
[B] Certification
[i] Type test certificate of compliance with IEC 61439-6
[ii] Certifying Authority: CPRI/KEMA/ASTA/DEKRA
[iii] Type of Certification: KEMA KEUR/ ASTA DIAMOND
[iv] Seismic Compliance: Zone IV
[C] JOINTS
[i] Electrical connection shall be via a joint with spring and silver graphite contacts
[ii] This joint shall absorb the differential conductor/casing expansion of each length equally.
[iii] The joints shall be so designed as to allow removal of any length without disturbing adjacent lengths.
[D] ENCLOSURE
[i] Construction: The metal enclosure of the busbar trunking system shall be of hot dip galvanized steel to provide high protection and mechanical resistance for the phase conductors along the entire length.
[ii] In order to limit magnetic field around the busbar system, aluminium enclosures are not acceptable.
[iii] Enclosure shall be painted with powder coated epoxy paint as per OEM’s standard of suitable shade
[E] TAP-OFF OUTLETS:
[i] Tap-off outlets shall be given at suitable interval as per site requirement. It shall be possible to use them simultaneously.
[ii] Tap-off outlets shall be connected to the isolators to form a block, holding the bars. They shall have a shuttered outlet which is opened and closed automatically when tap-off units are plugged in or remove.
[F] TAP-OFF UNIT
[i] Tap-off units shall be from the same manufacturer as the busbar trunking system and shall be provided with off-load isolator suitable for circuit breakers according to ratings.
[ii] All circuit breakers used shall be able to operate normally when mounted upside down or at any angles.
[iii] Tap-off units shall be of dust and damp proof version, degree of protection IP 54 with silver plated contacts suitable for all ratings of busbar and shall be suitably earthed.
[iv] The earthing contact of the tap-off unit shall always be made before that of the live conductors and the last to break during removal.
[v] The tap-off unit and the busbar trunking system shall be interlocked to ensure that the MCCB is in the ‘OFF’ position prior to installation or removal of the unit.
[vi] The tap-off unit for MCCB shall have an interlock which prevents the cover from being opened while the device is in the ‘ON’ position and to prevent accidental closing of the device when the cover is opened.
Straight Length with plug-in hole arrangement
90° Elbow
End Feed Unit with suitable FP MCCB protection
Flange End
Spring Hangers for vertical installation
End Closure
32 A tap-off units with suitable rating of FP MCB/MCCB
63 A tap-off units with suitable rating of FP MCB/MCCB
Supply, installation, commissioning and testing of "MAIN PANEL" (G+5,G+13) suitable for flush mounting & surface mounting with insulated & shrouded copper busbar for each phase, 2 fully insulated & shrouded neutral bar, 2 earth bar and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for FP MCCB / Isolator / RCCB / RCBO as incomer and TPN MCBs as outgoing complete all as specified and directed.
The DB shall comprise of the following accessories:
Busbar Chamber:
[i] Copper busbar of rated capacity 250 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
Incoming:
[i] 630 A, 415 V, Ics = Icu = 50 kA, 50 Hz MCCB with fixed magnetic settings and adjustable thermal setting (0.7 - 1 X In) TMD trip unit-
Outgoing:
[i] 63 A, 415 V, 10 kA, 50 Hz TPN MCB (C-curve) - 02 Nos.
M & L for fabrication of MS support including application of two coats of red oxide primer and paint finish with epoxy rasin with necessary fittings/ hardwear or threaded rod as per site requirement with complete accessories to fix to the wall/ceiling/floor all as specified and direced.
S & F ISI marked MCB for AC applications till 63 A, having breaking capacity Icn = 10 kA, conforming to IS/IEC 60898-1-2002, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters
6- 32 A, SP MCB C- curve
40- 63 A, FP MCB C- curve
6- 32 A, SPN MCB C- curve
S & F 415 V, 50 Hz, FP RCBO 32 amps suitable for 30 mA earth leakage current sensitivity complete all as specified and directed.
Supply, installation, commissioning and testing of "PANEL" suitable for flush mounting & surface mounting with insulated & shrouded copper busbar for each phase, 2 fully insulated & shrouded neutral bar, 2 earth bar and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for FP MCCB / Isolator / RCCB / RCBO as incomer and TPN MCBs as outgoing complete all as specified and directed. (For G+10) The DB shall comprise of the following accessories: Busbar Chamber: [i] Copper busbar of rated capacity 250 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N) Incoming: [i] 100 A, 415 V, Ics = Icu = 25 kA, 50 Hz MCCB with fixed magnetic settings and adjustable thermal setting (0.7 - 1 X In) TMD trip unit- Outgoing: [i] 63 A, 415 V, 10 kA, 50 Hz TPN MCB (C-curve) - 02 Nos.
Supply, installation, testing and commissioning of DINrail mounted, self-powered direct connect watt-hour meter, conforming to IEC 62053-21, with accuracy Cl 1.0 to provide direct measurement of real energy (kWh) on a single phase network (92 VA to 276 VAC) up to Imax = 63 A, frequencuy range 50/60 Hz, operating temperature range -25° C to 55° C with a 6+2 digit display for measurement up to 999999.99 in kWh and for configuration and equipped with a flashing red indicator to check the accuracy of the meter. The meter shall communicate via a modbus RS-485 protocol and all measured values shall be available via the modbus control. The meter shall be equipped with anti-tamper security feature to ensure the integrity of the measurement complete all as specified and directed.
Supply, installation, testing and commissioning of DINrail mounted, self-powered direct connect watt-hour meter, conforming to IEC 62053-21, with accuracy Cl 1.0 to provide direct measurement of real energy (kWh) on a three phase network up to Imax = 125 A, frequencuy range 50/60 Hz, operating temperature range -25° C to 55° C with a 6+2 digit display for measurement up to 999999.99 in kWh and for configuration and equipped with a flashing red indicator to check the accuracy of the meter. The meter shall communicate via a modbus RS-485 protocol and all measured values shall be available via the modbus control. The meter shall be equipped with anti-tamper security feature to ensure the integrity of the measurement complete all as specified and directed.
M & L for 2.0 mm thick hot-dip galvanized & powder coated perforated cable tray of size 200 mm (W) X 50 mm (H) conforming to IEC 6537, including all accessories, supports etc all as specified and directed.
TELEPHONE & TV CONNECTION S & F modular type 1 module RJ 11 telephone socket with shutter complete all as specified and directed. Make: Legrand Arteor Cart-Part No. 5734 26 or equivalent model of Precision as approved by GE
S & F modular type 1 module TV socket complete all as specified and directed. Make: Legrand Arteor Cat-Part No. 5734 25 or equivalent model of Precision as approved by GE
M & L for 2 pair telephone cable having solid electrolytic annealed bare copper conductor of 0.5 mm nominal diameter with high density polyethylene insulation, paired, polyester taped, nylon rip cord and grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113 C including termination. Make: RR Kabel, Finolex, Polycab
SOLAR STREET LIGHT Supply, installation, testing and commissioning of solar street light system having system voltage 12 V, luminarie wattage 20 W, luminous efficacy > 120 lumen/watt, MPPT solar charge controller, 75 Wp solar PV module, 12.8 V, 30 Ah battery capable of providing 2 days of back-up and hot dip galvanized tubular pole of 5 m above ground height, including necessary civil and earth work complete all as specified and directed.Make: Havells Cat-Part No. LHSTARU7AANI020 or equivalent model of Bajaj, Philips or Wipro as approved by GE.
INVERTER S & F ISI marked MCB for AC applications 6- 32 A, having breaking capacity Icn = 10 kA, conforming to IS/IEC 60898-1-2002, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, all complete as specified and directed. Make: Schneider, Legrand, Havells
EXTERNAL ELECTRIC SUPPLY
Supply,Installation,Testing and commissionbing `11 KV, 630 Amps, 25 KA for 3 Sec , outdoor type HT Vaccum Circuit Breaker for Incommer confirming to the IEC 62271-200,IAC-AFLR-25KA for 3 Sec PM KLSC -2B comprising of the following equipment :-
(a ) 630 Amps continous Bus Bar material shall be of high condiuctiveity electrolytic copper only.All Bus bars shall be insulated with heat shrinkable PVC sleeves and joints shall be covered with bitumen compound followed by HT tape. Phase identification shall be made at the end by coloured tape. Bus bars shall be mounted on integral seal off bushings all inter connection shall be of electrolytic grade copper only with joints silver plated.
(b ) Circuit breaker shall be mounted on a with drawable truck which shall roll out horizontally from service position to isolated position with ease and .MAKE: ANDREWYULE/AREVA/SIEMENS/ABB
(c )Motorised Spring charged Mechanism
(d )Separate eartyhing truck shall be provided for bus earthing and cable earthing.
(e ) Cast Resin Current Transformer, 11 KV, 50/25/5 A, 15 VA, CI 5P 10, CIO 5 Core II PS Class-03 Nos
(f ) Cast Resin Three phase Potentail Transformer 11 KV/ 3/110V/ 3, 200VA, CI 1.0 – 03 Nos with desired capacity PT Fuses.
(h )Multifunction meter, Digital type (Displaying A,V,PF,Hz,KVA,KW,KVAR,KWh,KVARh etc) Class 0.5 with RS 485 port for commuinication of Modbus protocol Make : : L&T, Conzerve.
(j )Three Phase Over Current & Earth Fault Relay, Model-MC-61 CNX, with 3 Phase O/C + E/F + Highest, 50/51 RYBN, Numarical Relay, Lowest O/C-1S, Highest O/C - 1hs, Lowest E/F- 0s, Highest E/F- 0hs, 4 NO . L&T CAT NO-MC61ANX4000
(k ) High Speed Master Trip Relay – 1 No . Make ASHIDA Model No : AVAJH 33/ equivalent in ABB or Siemens.
(m ) Trip Circuit Supervision Relay (VAX) – 1 No Make ASHIDA Model No : ATSR31A/ equivalent in ABB or Siemens.
(n ) Air Insulated rear end Bottom Entry Cable Box suitable for termination of XLPE Cables.
(p ) Panel Must Have additional features
(i) Continous rated closing/tripping coils
(ii) Sprimg Charging Handle
(iii) Fully internal Arc tested for 25 KVA for 3 Sec
(iv) Manual closing /tripping of the CB with compartment door closed
(v) Short time rating for 3 seconds as per IEC 62271-100
(vi) Mechanical endurance test-M2
(q ) Breaker shall be provided with following features
(i) Auxillaty Switch 6 NO + 1 NC Contacts mounted on the draw out portion of the switchgear
(ii) Position Cell Switch with 3 NO + 1 NC Contact on each for test position and Service Position.
(r ) Digital independent Volt meter and ammeter of suitable ratings- 01 each
note: (i)Inbuild Power pack 30 v dc to be provided with panel at lkeast for 30 minuite Back Up.
(ii) Auxiliary Supply Voltage for the Relay/Close/Trip coil 30 Volt DC.
supply & fix battary bank with AGM VRLA batteris 2 volt, 100 AH for operation of VCB including connectors
supply & fix Battary charger 0- 50 amps floating type
Supply, install, testing and commisioning of Distribution transformer mounted on massoniry platform stepdown , 11KV.0.433KV , Three Phase complying with IS: 1180/IEC-76(Part-1) 2014 with latest ammanmendts , Outdoor type double opper wound suitable for 50 Hz system of capacity 400 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5 % in steP of 2.5 %. Losses should be confined to the limits specified as follows: :maximum allowable losses at full load (100 % ) & Half Load ( 50 % )shall not be exceeded 1.12 % & 0 .79 % Respectivlyas per GRAHA RATING, Percentage Impedance: 5%. Losses and Impedance are subjected to tolerance as specified in IS 1180. The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have both side cable end box with neutral brought out complete all as directed by Engineer - in -Charge, and installation of transformer shall be carried out as per IS-10028 and comprising with the following standerd fittings/Technical specifications : -
(a) Lifting lug for transformer and tank.
(b) Earthing terminal rating and diagram plate.
(c ) Air release device.
(d) Oil filling inlet pipe with plug.
(e) Drain outlet pipe with brass gate valve.
(f) Conservator tank with oil level indicator
(g) Silica jel breather
(j) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.
(k) Type of connection Delta/Star
(l) Type of cooling: Oil and Natural Air.
(m) Vector group:DYN 11.
(n) Temperature rise over an ambient of 50 °C maximum.
(o) Cable end box on both side for HT/LT cables of suitable size.
(p) Provision of thermometer with pocket.
(q) Provision of oil and winding temperature gauge.
Supply, install, testing and commisioning of Distribution transformer mounted on massoniry platform stepdown , 11KV.0.433KV , Three Phase complying with IS: 1180/IEC-76(Part-1) 2014 with latest ammanmendts , Outdoor type double opper wound suitable for 50 Hz system of capacity 500 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side ,Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5 % in steP of 2.5 %. Losses should be confined to the limits specified as follows: :maximum allowable losses at full load (100 % ) & Half Load ( 50 % )shall not be exceeded 1.05 % & 0 .75 % Respectivlyas per GRAHA RATING, Percentage Impedance: 5%. Losses and Impedance are subjected to tolerance as specified in IS 1180. The transformers should be supplied with first filling of oil confirming to IS 335 .The transformer should have both side cable end box with neutral brought out complete all as directed by Engineer - in -Charge, and installation of transformer shall be carried out as per IS-10028 and comprising with the following standerd fittings/Technical specifications : -
(a) Lifting lug for transformer and tank.
(b) Earthing terminal rating and diagram plate.
(c ) Air release device.
(d) Oil filling inlet pipe with plug.
(e) Drain outlet pipe with brass gate valve.
(f) Conservator tank with oil level indicator
(g) Silica jel breather
(j) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335.
(k) Type of connection Delta/Star
(l) Type of cooling: Oil and Natural Air.
(m) Vector group:DYN 11.
(n) Temperature rise over an ambient of 50 °C maximum.
(o) Cable end box on both side for HT/LT cables of suitable size.
(p) Provision of thermometer with pocket.
(q) Provision of oil and winding temperature gauge.
Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "Main LT Panel" of suitable size, conforming to IEC 61439-1 &2, IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 65 protection made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. G+10
BUSBAR CHAMBER
[i] Copper busbar of rated capacity 800 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
INCOMING
[ii] LED phase indicators (Yellow, Blue, Red)- 01 Set
[iii] Power Quality analyzer with revenue accuracy of Class 0.2S, complying to IEC 62053- 22, 256 samples/cycle, waveform reading, 512 MB of standard non-volatile memory for data & event logging, up to 63rd harmonics analysis for voltage & current, GPS clock, 01 serial port (Modbus, ION, DNP3), Dual Ethernet port (Modbus/TCP, ION TCP, DNP3 TCP, IEC 61850) and standard digital input, expandable digital IO, analog IO.- 01 Nos.
OUTGOING
[i] 400 A, 415 V, Ics = Icu = 36 kA, 50 Hz 3 Pole MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5- 10 X Ir) and microprocessor based trip unit- 01 Nos. End Feeder Unit
[ii] 250 A, 415 V, Ics = Icu = 36 kA, 50 Hz 3 pole MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5- 10 X Ir) and microprocessor based trip unit- 03 Nos (Utitlity Panel, APFC)
[iv] LED phase indicators (Yellow, Blue, Red)- 03 Set
[v] Power Quality analyzer with revenue accuracy of Class 0.2S, complying to IEC 62053- 22, 256 samples/cycle, waveform reading, 512 MB of standard non-volatile memory for data & event logging, up to 63rd harmonics analysis for voltage & current, GPS clock, 01 serial port (Modbus, ION, DNP3), Dual Ethernet port (Modbus/TCP, ION TCP, DNP3 TCP, IEC 61850) and standard digital input, expandable digital IO, analog IO.- 03 Nos.
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 04 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "Utilities Panel" of suitable size, conforming to IEC 61439-1 &2 having both sides openable with hinged double doors & locking arrangement and IP 65 protection made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. G+10
BUSBAR CHAMBER
[i] Copper busbar of rated capacity 320 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
Incoming:
[i] 250 A, 415 V, Ics = Icu = 25 kA, 50 Hz, FP MCCB with adjustable overload settings (0.36- ` X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 Nos. incomer
[ii] LED phase indicators (Yellow, Blue, Red)- 01 Set
[iii] Power Measurement Device with Class 1 accuracy, complying to IEC 62053- 22, 64 samples/cycle, 31st harmonic analysis, RS485, calibration LED, third party accuracy test certificate - 01 Nos.
Outgoing:
[i] 160 A, 415 V, Ics = Icu = 25 kA, 50 Hz,03 Pole MCCB with adjustable overload settings (0.36- ` X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 Nos. Fire Protection Panel
[ii] 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz, 03 PoleMCCB with adjustable overload settings (0.36- ` X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 02 Nos. Water Supply Panel & g+10 utility panel
[ii] 16 A, 415 V, Ics = Icu = 16 kA, 50 Hz,03 Pole MCCB with adjustable overload settings (0.36- ` X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 Nos. to street light
[iv] LED phase indicators (Yellow, Blue, Red)- 04 Set
[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 05 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
Supply, installation, testing and commissioning of 800 A sandwich type silver flashed, bi-metal copper contact, aluminium busway (3L + N + PE), with original Mylar insulation from Dupont, 100% neutral, 50 kA for 1 second, 50% integral earth, dual housing complete all as specified and directed. Make: Schneider, ABB, Siemens
The busbar trunking system shall conform to the following technical specifications:
[A] General:
[i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tees, flanged ends, cable tap box and circuit breaker, etc.) shall be in accordance with IEC 61439 Part 6 (2012) or UL857 and from the same manufacturer as the busbar trunking system. Degree of protection of the BTS shall be IP 65 in accordance with IEC 60529.
[ii] Rated operation voltage of the BTS shall be 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor. The earth busbar must be one continuous piece without bolting on housing.
[B] Certificate:
[i] The busbar, of full range and each rating, shall pass full type tests specified in IEC 61439-6. The certificate shall be issued by an international independent testing authority (e.g. ASTA, KEMA, UL).
[ii] A product safety mark (e.g. KEMA-KEUR, ASTA DIAMOND, UL) shall be on the product offering a visible assurance to all of full product safety testing, factory inspection and ongoing surveillance under independent authority to ensure the ongoing safety of product.
[iii] The BTS shall pass seismic tests with actual physical product and being certified complying with UBC seismic Zone 4 condition by an international recognized earthquake research body, e.g. Asian Pacific Network of Centers for Earthquake Engineering Research (ANCER).
[C] Short-Circuit Ratings & Tests:
[i] The whole BTS shall be capable of withstanding the short circuit of the electrical installation without undergoing any electrical, mechanical and thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV.
[ii] Minimum certified short circuit ratings shall be 198 kA peak and 90 kA for 1 s for 3200 A BTS.
[D] Housing:
[i] The busbar trunking housing shall be constructed of electro galvanized steel and aluminum to reduce hysteresis and eddy current loses and shall be provided with a suitable protective finish of ANSI 49 grey epoxy paint.
[ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation. And it shall pass at least 2000 hr salt spray test to ensure the anticorrosion ability.
[iii] The totally enclosed housing shall be manufactured by the busbar trunking manufacturer. Modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking manufacturer voids the manufacturer’s warranty. Busbar trunking so modified is unacceptable without the written consent of the manufacturer.
[E] Busbars:
[i] Busbars shall be of aluminum with copper cladding utilized Molecular Fusion technology.
[ii] There shall be no bolts passing through the busbars of the busway.
[iii] Each busbar shall be insulated with Class B (130 ℃) DuPont Mylar insulation. Epoxy insulation is unacceptable.
[iv] The temperature rise at any point of the busbar trunking enclosure shall not exceed 55° C above the ambient temperature of 40° C when operated at rated current.
[F] Joints:
[i] The busbar trunking joint shall be of the one-bolt type which utilizes a high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area.
[ii] The bolt shall be torque indicating and at earth potential.
[iii] The bolt shall be two-headed design to indicate when proper torque has been applied and require only a standard long handle wrench to be properly activated.
[iv] Access shall be required to only one side of the busbar trunking for tightening joint bolts.
[v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.
[G] Plug-in Openings:
[i] The connecting jaw of the plug-in unit shall plug directly on to the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable.
[ii] All contact on joint and plug-in opening should be silver plated copper.
[iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in openings on each side.
[iv] All openings shall be usable simultaneously.
[v] Busbar trunking shall be installed so that plugs are side mounted to permit practical use of all plug-in openings.
[vi] It shall be possible to inspect the plug-in opening and busbars prior to the installation of the plug-in units.
[H] Plug-in Units:
[i] The plug-in jaw shall be spring design composed of different metal to ensure the firm and tight contact with the busbar.
[ii] Plug-in Units shall be type tested in accordance with IEC 61439-6 (Annex D: Part 1-5 and 9-13).
[iii] The earthing contact of the plug-in unit shall always be made before that of the live conductors and the last to break during removal. And it must connect to the earth bar of busway to ensure the safety.
[iv] Covers of all plug-in units must have interlocks to prevent the cover from being opened when the switch is in the ON position.
[v] Plug-in units (circuit breaker type or fusible switch type) shall be operated with visible blade quick-make and quick-break mechanism.
[vi] Presence of transparent shield shall be inside to avoid direct contact of human.
[vii] The plug-in units shall be equipped with internal barriers to prevent accidental contact of fish tape and conductors with live parts on the line side of the protective device during time of wire pulling.
[I] Supporting Structure:
Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 meters for horizontally mounted run and 4.88 meters for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing of up to 1.5 meters for horizontally or vertically mounted runs.
[J] Voltage Drop:
[i] The 3-phase line to line voltage drop 40% power factor concentrated loadshall not exceed 3.4 V per hundred ft.
[ii] The line-to line voltage drop at the load power factor shall not exceed 4.1 V per hundred feet.
Straight feeder
90º elbow
Flange end
Copper flexible (braided)
Adopter box (local item)
Edge-wise hangers
Straight feeder
90º elbow
Flange end
Copper flexible (braided)
Adopter box (local item)
Edge-wise hangers
S & F 45 W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of > 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high effiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete all as specified and directed. [Make: BAJAJ 169799 BRTFG 45W LED I or equivalent model of Havells, Philips or Wipro]
S & F weather- proof PVC junction box of size 250 mm x 200 mm x 100 mm, having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals including 03 Nos. of polymide gland with check nut (M-32- 3 Nos.) fixed on poles with flat aluminium clamps of size 20 mm x 3 mm, nuts, bolts, washers, etc. complete all as specified and as directed. [Make:
Supply, installation, testing and commissioning of intelligent street light control (ATSC) suitable for 6 kW maximum load, wall/pole mounted, having built-in networking support, built-in astronomical timer, 32 A TP contactor, 40 A TPN MCB housed in 3.15 mm thick powder CRCA sheet housing all complete as specified and directed.
Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "Main LT Panel" of suitable size, conforming to IEC 61439-1 &2, IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 65 protection made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. G+5,G+13
BUSBAR CHAMBER
[i] Copper busbar of rated capacity 1000 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
INCOMING
[ii] LED phase indicators (Yellow, Blue, Red)- 01 Set
[iii] Power Quality analyzer with revenue accuracy of Class 0.2S, complying to IEC 62053- 22, 256 samples/cycle, waveform reading, 512 MB of standard non-volatile memory for data & event logging, up to 63rd harmonics analysis for voltage & current, GPS clock, 01 serial port (Modbus, ION, DNP3), Dual Ethernet port (Modbus/TCP, ION TCP, DNP3 TCP, IEC 61850) and standard digital input, expandable digital IO, analog IO.- 01 No.
OUTGOING
[i] 500 A, 415 V, Ics = Icu = 36 kA, 50 Hz 03 Pole MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5- 10 X Ir) and microprocessor based trip unit- 01 No.for utitlity panel
[ii] 320 A, 415 V, Ics = Icu = 36 kA, 50 Hz 03 Pole MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5- 10 X Ir) and microprocessor based trip unit- 01 No. enD FEEDER UNIT
[iii] 250 A, 415 V, Ics = Icu = 25 kA, 50 Hz 03 Pole MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5- 10 X Ir) and microprocessor based trip unit- 01 No.For APFC Panel
[iV] 125 A, 415 V, Ics = Icu = 25 kA, 50 Hz 03 Pole MCCB with adjustable overload settings (0.40- 1 X In), adjustable short-circuit settings (1.5- 10 X Ir) and microprocessor based trip unit- 01 No. D.U LT Panel
[iv] LED phase indicators (Yellow, Blue, Red)- 04 Set
[v] Power Quality analyzer with revenue accuracy of Class 0.2S, complying to IEC 62053- 22, 256 samples/cycle, waveform reading, 512 MB of standard non-volatile memory for data & event logging, up to 63rd harmonics analysis for voltage & current, GPS clock, 01 serial port (Modbus, ION, DNP3), Dual Ethernet port (Modbus/TCP, ION TCP, DNP3 TCP, IEC 61850) and standard digital input, expandable digital IO, analog IO.- 04 Nos.
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 05 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "Utilities Panel" of suitable size, conforming to IEC 61439-1 &2 having both sides openable with hinged double doors & locking arrangement and IP 65 protection made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. G+5,G+13
BUSBAR CHAMBER
[i] Copper busbar of rated capacity 750 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
Incoming:
[i] 500 A, 415 V, Ics = Icu = 36 kA, 50 Hz FP MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 Nos.
[ii] LED phase indicators (Yellow, Blue, Red)- 01 Set
Outgoing:
[i] 320 A, 415 V, Ics = Icu = 36 kA, 50 Hz 03 Pole MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 Nos. Fire Protection Panel
[ii] 100 A, 415 V, Ics = Icu = 25 kA, 50 Hz 03 Pole MCCB MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 Nos. ( water supply panel)
[ii] 63 A, 415 V, Ics = Icu = 25 kA, 50 Hz 03 Pole MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 2 Nos. ( For lift Panel )
[iii] 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz 03 Pole MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 No.( For ST LT)
[iv] LED phase indicators (Yellow, Blue, Red)- 05 Set
[vi] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 05 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "G+5 Utilities Panel" of suitable size, conforming to IEC 61439-1 &2 having both sides openable with hinged double doors & locking arrangement and IP 65 protection made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed.
BUSBAR CHAMBER
[i] Copper busbar of rated capacity 100 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
Incoming:
[i] 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 Nos.
[ii] LED phase indicators (Yellow, Blue, Red)- 01 Set
[iii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.
Outgoing:
[iii] 40 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 Nos. G+5 utility panel
[ii] 6 A, 10 kA, 230 V, 50 Hz SPN MCB (C- curve)- 6 Nos.
[iv] LED phase indicators (Yellow, Blue, Red)- 01 Set
[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 05 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "G+13 Utilities Panel" of suitable size, conforming to IEC 61439-1 &2 having both sides openable with hinged double doors & locking arrangement and IP 65 protection made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed.
BUSBAR CHAMBER
[i] Copper busbar of rated capacity 100 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
Incoming:
[i] 63 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 Nos. g+13 utitlity panel
[ii] LED phase indicators (Yellow, Blue, Red)- 01 Set
[iii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
Outgoing:
[iii] 40 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 No.
[ii] 16 A, 10 kA, 230 V, 50 Hz SPN MCB (C- curve)- 1 Nos.
[ii] 6 A, 10 kA, 230 V, 50 Hz SPN MCB (C- curve)- 13 Nos.
[iv] LED phase indicators (Yellow, Blue, Red)- 01 Set
[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "Elevator Panel" of suitable size, conforming to IEC 61439-1 &2 having both sides openable with hinged double doors & locking arrangement and IP 65 protection made out of 3.15 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed.
BUSBAR CHAMBER
[i] Copper busbar of rated capacity 100 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
Incoming:
[i] 40 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 1 Nos.
[ii] LED phase indicators (Yellow, Blue, Red)- 01 Set
[iii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
Outgoing:
[iii] 32 A, 415 V, Ics = Icu = 16 kA, 50 Hz FP MCCB with adjustable overload settings (0.45- 1 X In), adjustable short-circuit settings (13 X Ir) and microprocessor based trip unit- 2 Nos. 8 pax and 13 pax passaenger
[ii] 20 A, 10 kA, 230 V, 50 Hz SPN MCB (C- curve)- 1 Nos.
[iv] LED phase indicators (Yellow, Blue, Red)- 01 Set
[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
Suppply and Fix cable route indicator made of round ci disc embossed LT cable of size 16 cm dia 6 mm thcik duly reverted with angle of size 15 cm X 15 cm X 15 cm for groutng the same complete all as specified
Suppply and Fix cable route indicator made of round ci disc embossed HT cable of size 16 cm dia 6 mm thcik duly reverted with angle of size 15 cm X 15 cm X 15 cm for groutng the same complete all as specified
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, OUTdoor type, APFC capacitor bank Panel Board of size as recommended by manufactrer 80 KVAR with 8 steps (25+25+12.5+12.5+5) WITH MD-XL CAPACITOR AND MCCB AS INCOMER Automatic Power Factor Correction panel , made out of 3.15 mm thick CRCA Sheet Dust and Vermin Proof, single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System,The enclosure shall be pre-treated as per 11 tanks process and finished with powder coating of shade RAL 7032. , including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified .The panel shall be factory fabricated comprosing of following. Make of pannel L&T/ SCHNEIDER/ABB
Particulars
[ A ] INCOMER
MCCB 250 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM94104OOT1OG /Legrand cat no-025540/schneider cat no-LV540310- 1 no (Thermal Magnetic Release)
ROM+SPDR - 1 no
Auxiliary 1 c/o +TAC 1 c/o- 1 no
[ B ] OUTGOING CAPACITOR FEEDERS : -
25 KVAr Capacitor feeder comprising of:- ( 2 Nos. )
80A, BUSSMANN FUSE 80ET,-6 nos
Thyristor switching module 25kVAR, 440V , TSM,LTTSM-2 nos
7% Detuned Aluminium Reactor 25KVAr 440V-2 NOS
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 30 kVAr,sutable for 480V , LTXL - 2 NOS
Push Button ON/OFF -4nos
Indicating lamps 4 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2
6A DP MCB , C CURVE 2 NOS
12.5 KVAr Capacitor feeder comprising of:- ( 2 Nos. )
40A, BUSSMANN FUSE- 6 NOS
Thyristor switching module 25kVAR, 440V,TSM,LTTSM - 2 NOS
7% Detuned Aluminium Reactor 12.5KVAr 440V LTAL,CAT NO-0712B2- 2 NOS
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 15 kVAr,sutable for 480V - 2 NOS
Push Button ON/OFF -4nos
Indicating lamps 4 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2
6A DP MCB , C CURVE 2 NOS
10 KVAr Capacitor feeder comprising of:- ( 2 Nos. )
40A, BUSSMANN FUSE- 6 NOS
Thyristor switching module 25kVAR, 440V,TSM,LTTSM - 2 NOS
7% Detuned Aluminium Reactor 10 KVAr 440V LTAL,CAT NO-0712B2- 2 NOS
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 12.5 kVAr,sutable for 480V - 2 NOS
Push Button ON/OFF -4nos
Indicating lamps 4 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2
6A DP MCB , C CURVE 2 NOS
5 KVAr Capacitor feeder comprising of:- (1 No )
16A, BUSSMANN FUSE 3 nos
Thyristor switching module 10kVAR, 440V,TSM,LTTSM
7% Detuned Aluminium Reactor 5 KVAr 440V,LTAL,CAT NO-0712B2-1 no
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 7.5 kVAr,sutable for 480V ,LTXL- 1nos
Push Button ON/OFF -2nos
Indicating lamps 1 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 1
6A DP MCB , C CURVE 1NOS
Incomer Metering
APFC relay 8 stage {BLR CM – 06T MB } -1 NO [230/ 110 V, 1/5A, 50 Hz] [Transistor output + Single CT sensing + RS 485 MODBUS]
Digital Voltmeter (3Ph, Class 1) -1 NO
Digital Ameter (3Ph, Class 1, 5A) -1 NO
Metering CT --/5A, Class-1- 3 NOS
SMPS 5A, Input 230V AC Output 24V DC -1 NO
ON Delay Timer 0-10 Sec.,Coil 24V DC -1 NO
Auxiliary Contactor {4NO} with 24V DC}-3 NOS
Indicating Lamp(R,Y,B)-3 NOS
6A SP MCB-3 NOS
6A DP MCB
6A FP MCB -1 NO
8" {EBM NADI} Fan -1 NO
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, OUTdoor type, APFC capacitor bank Panel Board of size as recommended by manufactrer 100 KVAR with 6 steps (25+25+12.5+12.5+10+10+5) WITH MD-XL CAPACITOR AND MCCB AS INCOMER Automatic Power Factor Correction panel , made out of 3.15 mm thick CRCA Sheet Dust and Vermin Proof, single door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System,The enclosure shall be pre-treated as per 11 tanks process and finished with powder coating of shade RAL 7032. , including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20mm Graded Stone Aggregate) and Testing after Installation complete all as specified .The panel shall be factory fabricated comprosing of following. Make of pannel L&T/ SCHNEIDER/ABB
Particulars
INCOMER
MCCB 200 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM94104OOT1OG /Legrand cat no-025540/schneider cat no-LV540310- 1 no (Thermal Magnetic Release)
ROM+SPDR - 1 no
Auxiliary 1 c/o +TAC 1 c/o- 1 no
OUTGOING CAPACITOR FEEDERS : -
25 KVAr Capacitor feeder comprising of:- ( 2 Nos. )
80A, BUSSMANN FUSE 80ET,-6 nos
Thyristor switching module 25kVAR, 440V , TSM,LTTSM-2 nos
7% Detuned Aluminium Reactor 25KVAr 440V-2 NOS
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 30 kVAr,sutable for 480V , LTXL - 2 NOS
Push Button ON/OFF -4nos
Indicating lamps 4 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2
6A DP MCB , C CURVE 2 NOS
12.5 KVAr Capacitor feeder comprising of:- ( 2 Nos. )
40A, BUSSMANN FUSE- 6 NOS
Thyristor switching module 25kVAR, 440V,TSM,LTTSM - 2 NOS
7% Detuned Aluminium Reactor 12.5KVAr 440V LTAL,CAT NO-0712B2- 2 NOS
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 15 kVAr,sutable for 480V - 2 NOS
Push Button ON/OFF -4nos
Indicating lamps 4 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 2
6A DP MCB , C CURVE 2 NOS
5 KVAr Capacitor feeder comprising of:- (1 No )
16A, BUSSMANN FUSE 3 nos
Thyristor switching module 10kVAR, 440V,TSM,LTTSM
7% Detuned Aluminium Reactor 5 KVAr 440V,LTAL,CAT NO-0712B2-1 no
Ultra heavy duty capacior LTXL , BOX type oil Filled Capacitor bank 7.5 kVAr,sutable for 480V ,LTXL- 1nos
Push Button ON/OFF -2nos
Indicating lamps 1 NOS
Auxiliary Contactor {2NO+2NC} 24V DC Coil Voltage MXO- 1
6A DP MCB , C CURVE 1NOS
Incomer Metering
APFC relay 8 stage {BLR CM – 06T MB } -1 NO [230/ 110 V, 1/5A, 50 Hz] [Transistor output + Single CT sensing + RS 485 MODBUS]
Digital Voltmeter (3Ph, Class 1) -1 NO
Digital Ameter (3Ph, Class 1, 5A) -1 NO
Metering CT --/5A, Class-1- 3 NOS
SMPS 5A, Input 230V AC Output 24V DC -1 NO
ON Delay Timer 0-10 Sec.,Coil 24V DC -1 NO
Auxiliary Contactor {4NO} with 24V DC}-3 NOS
Indicating Lamp(R,Y,B)-3 NOS
6A SP MCB-3 NOS
6A DP MCB
6A FP MCB -1 NO
8" {EBM NADI} Fan -1 NO
STANDBY POWER SUPPLY
Supply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002- 1981, complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364- 1992, mounted on a common base frame & coupled through a flexible coupling or close coupled and AMF Panel complete with platform, control panel having meters, sound-proof canopy, etc. of capacity 200 kVA complete all as specified and directed. Make: Kirloskar, Crompton Greves, Cummins as approved by GE
[[a] Engine: 4/6 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude,Inline fuel pump with A1 class mechanical governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 12 V DC battery.
[b] Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength
[c] Control Panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish.
The control panel consists of the following parts:
[i] Controller: Aluminum bus bars with suitable capacity with incoming/outgoing terminals
[ii] Indicating lamps for ‘Load ON’ and ‘Set Running’
[iii] Instrument fuses duly wired and ferruled
[iv] MCCB of suitable rating with overload and short circuit protections tpn 320 amps 4 pole 415 V-2 nos
[d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP
[e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours
[f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency
[g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level
[h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing.
[i] Data Logging: Engine hours, control hours and upto 5 recent fault codes
[j] Configurable glow plug control
[k] 12 V DC operation 02 NOS.
[l] Silencer: Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB
[m] Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads.
[n] Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning
Supply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002- 1981, complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364- 1992, mounted on a common base frame & coupled through a flexible coupling or close coupled and AMF Panel complete with platform, control panel having meters, sound-proof canopy, etc. of capacity 100 KVA complete all as specified and directed.
Make: Kirloskar, Crompton Greves, Cummins as approved by GE
[a] Engine: 4/6 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude,Inline fuel pump with A1 class mechanical governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 12 V DC battery.
[b] Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength
[c] Control Panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish.
The control panel consists of the following parts:
[i] Controller: Aluminum bus bars with suitable capacity with incoming/outgoing terminals
[ii] Indicating lamps for ‘Load ON’ and ‘Set Running’
[iii] Instrument fuses duly wired and ferruled
[iv] MCCB of suitable rating with overload and short circuit protectionsm,160 amps 415 v tp mccb -02 nos
[d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP
[e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours
[f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency
[g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level
[h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing.
[i] Data Logging: Engine hours, control hours and upto 5 recent fault codes
[j] Configurable glow plug control
[k] 12 V DC operation
[l] Silencer: Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB
[m] Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads.
[n] Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning
M & L for Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth 32 x 6mm GI strip by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt,Earthing lead 32x6 up to 7.5m, 20mm dia medium grade GI watering pipe ,PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2014 (part-I) NOTE-: GI earth strip shell be measured and paid for separately under relevant item of schedule .[ 20 Nos External water supply + 44 Nos External Electrification + 22 Nos fire protection + 24 Nos Lightning protection + 12 Nos Lift + 12 Nos DG set ]
Sewage Treatment Plant of 40 KLD for G+10 block
Design, supply, installation, testing and commissioning of compact / package type sewage treatment plant based on principle of aeribuc attached growth non clogging randomly moving bed bio reactor (MBBR) with primary, secondary and tertiary process having capacity 40 KLD along with interconnecting equipment, all piping work, valves, instrumentations, pumping and blower equipment and setting up of in-plant laboratory for physical, chemical andbacteriological analysis including of all instrument / equipment glassware, testing chemicals and culture, providing manuals, registers, logbooks and spare parts along with list required for 5 yrs O & M etc. electrical and mechanical components of works for sewage treatment plant comprising of following accessories / equipment as per the OEM specification all as specified and directed by GE / Engineer-in-Charge. Make: Thermax / Ion- Exchange as approved by GE
NOTES:
[i] All civil works, viz. excavations & earth work, PCC, masnory, foundation platform, plinth, etc. required for installation shall be measured and paid separately.
[ii] Rates quoted shall be deemed to inclusive of following
RAW SEWAGE TRANSFER PUMP
02 Nos. - Submersible pumps sutaible for Sewage water capable of 2.0- 2.5 m3/hr discharge at 20 Meter head and having solid handling capacity of minimum 32 mm size particles complete with all accessories, motor of required capacity: (1 W + 1 S)
PRIMARY TREATMENT SYSTEM
01 Nos. of SS-304 perforated screens with suitable lifting arrangement (size 500 mm X 1000 mm X 3.5 mm (L X W X T) with 10 mm openings
Manual overflow type oil skimmer
SECONDARY TREATMENT SYSTEM
02 Nos. of non clogging type centrifugal Anoxic feed pumps capable of 2.0- 2.5 m3/hr discharge at 12 Meter head and having solid handling capacity of minimum 32 mm size particles having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller (with wiring) to control, etc. (1 W + 1 S)
Package Mild Steel Epoxy painted (MSEP) 40 KLD STP- tank having 02 Nos. of twin lobe Rotary air blowers (1 W + 1 S) capable of delivering 40 m3/hr of atmospheric air at 0.37 kg/cm2 pressure, driven through "V" belt or directly coupled through flexible coupling to a TEFC motor suitable for 415±10% V, 3- Ph, 50 Hz AC supply.
Air piping comprising of pipes droppers / laterals with MS (epoxy coated) header complete with all fittings viz. tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc.
Air dispersion system for equilization tank & anoxic with fine & coarse bubblers
Prefabricated Mild Steel Epoxy painted (MSEP) sewage treatment plant comprising of inbuilt compartments of aeration zone, lamella settling zone with FRP Plates and chlorination zone for disinfaction with all required valves piping.
Sodium Hypochlorite dosing system consisting of one HDPE tank of 200 litres capacity, positive displacement diphragm dosing pump having variable flowrate of 0-6 LPH along with motor suitable for operation at 230 V, 1- Ph, 50 Hz. supply and complete with necessary polypropylene piping, valves, strainers, low level switch and injection fittings. The pump shall have speed & stroke control.
02 Nos. of non clogging type centrifugal Recirculation pumps capable of 7.5 m3/hr discharge at 20 Meter head and having solid handling capacity of minimum 32 mm size particles having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller (with wiring) to control, etc. (1 W + 1 S)
TERTIARY SYSTEM
02 Nos. of centrifugal Filter feed water pumps capable of 2.0 - 2.5 m3/hr discharge at 32 Meter head having solid handling capacity of minimum 5 mm size particles CI casing & impeller complete with all accessories, motor suitable for 415±10% V, 3- Ph, 50 Hz AC supply, pressure gauge with isolation cock, isolation valve, NRV on delivery line, strainer at suction. mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve, etc. (1 W + 1 S)
Mild Steel Epoxy painted (MSEP) vessel filter of ø 500 mm & 1800 mm HOS (shell & dishend thickness 4.0 mm minimum) suitable for test pressure of 5.0 kg/cm² and working pressure of 3.5 kg/cm², including media (pebbles, sand, silex, fine sand, fine silex), standard fittings viz. pressure gauge, sampling cock, backwash including frontal piping & valves, etc.
Mild Steel Epoxy painted (MSEP) vessel filter of ø 600 mm & 1800 mm HOS (shell & dishend thickness 4.0 mm minimum) suitable for test pressure of 5.0 kg/cm² and working pressure of 3.5 kg/cm², including media (activated carbon with supporting media), standard fittings viz. pressure gauge, sampling cock, backwash including frontal piping & valves, etc.
SLUDGE DEWATERING SYSTEM
02 Nos. of non clogging type centrifugal Sludge transfer pumps capable of 3.0 LPM discharge at 10 Meter head having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller (with wiring) to control, etc. (1 W + 1 S)
02 Nos. of Filter press feed pumps capable of 3.0 LPM discharge at 10 Meter head with all accessories. (1 W + 1 S)
Manual type filter press of capacity < 25 kg/day having PPE plats, polyester / PPE / Cotton filter cloth with all accessories.
Control panel & cabling for all electrical items of work
Interconnecting pipe work with PVC pipes and MS pipes with anti-corrosive paint for sewage, treated water and tank overflow / backwash pipeline with valves, fittings and accessories.
Supplying & instalation of ultra filtration system with UF feed pump having 2.5 m3/hr flowrate at 25 Meter head & back wash feed pump having 2.5 m3/hr flowrate at 25 Meter head ,cleaning system, panel PLC based UF skip pipng etc.,
NOTE: PARAMETER OF USAGE OF TREATED SEWAGE WATER SHALL BE AS PER GUIDELINES ISSUED BY E-IN-C FOR PLANNING & DESIGN OF SEWER NETWORK & STP VIDE LETTER NO. 86435/MISC/E4(U3), DATED 19/05/2017 & all as directed & specified
Sewage Treatment Plant of 70 KLD for G+5 & G+13 blocks
Design, supply, installation, testing and commissioning of compact / package type sewage treatment plant based on principle of aeribuc attached growth non clogging randomly moving bed bio reactor (MBBR) with primary, secondary and tertiary process having capacity 70 KLD along with interconnecting equipment, all piping work, valves, instrumentations, pumping and blower equipment and setting up of in-plant laboratory for physical, chemical andbacteriological analysis including of all instrument / equipment glassware, testing chemicals and culture, providing manuals, registers, logbooks and spare parts along with list required for 5 yrs O & M etc. electrical and mechanical components of works for sewage treatment plant comprising of following accessories / equipment as per the OEM specification all as specified and directed by GE / Engineer-in-Charge.Make: Thermax / Ion- Exchange as approved by GE
[i] All civil works, viz. excavations & earth work, PCC, masnory, foundation platform, plinth, etc. required for installation shall be measured and paid separately.
[ii] Rates quoted shall be deemed to inclusive of following (Item No. 1.1 to 1.18):
RAW SEWAGE TRANSFER PUMP
02 Nos. -Submersible pumps suitable for Sewage water capable of 3.5- 4.0 m3/hr discharge at 20 Meter head and having solid handling capacity of minimum 32 mm size particles complete with all accessories, motor of required capacity: (1 W + 1 S)
PRIMARY TREATMENT SYSTEM
01 Nos. of SS-304 perforated screens with suitable lifting arrangement (size 500 mm X 1000 mm X 3.5 mm (L X W X T) with 10 mm openings
Manual overflow type oil skimmer
SECONDARY TREATMENT SYSTEM
02 Nos. of non clogging type centrifugal Anoxic feed pumps capable of 3.5 m3/hr discharge at 20 Meter head and having solid handling capacity of minimum 32 mm size particles having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller (with wiring) to control, etc. (1 W + 1 S)
Package Mild Steel Epoxy painted (MSEP) 70 KLD STP- tank having 02 Nos. of twin lobe rotary air blowers (1 W + 1 S) capable of delivering 92 m3/hr of atmospheric air at 0.40 kg/cm2 pressure, driven through "V" belt or directly coupled through flexible coupling to a TEFC motor suitable for 415±10% V, 3- Ph, 50 Hz AC supply.
Air piping comprising of pipes droppers / laterals with MS (epoxy coated) header complete with all fittings viz. tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc.
Air dispersion system for equilization tank & anoxic with fine & coarse bubblers
Prefabricated Prefabricated Mild Steel Epoxy painted (MSEP) sewage treatment plant comprising of inbuilt compartments of aeration zone, lamella settling zone with FRP Plates and chlorination zone for disinfaction with all required valves piping.
Sodium Hypochlorite dosing system consisting of one HDPE tank of 200 litres capacity, positive displacement diphragm dosing pump having variable flowrate of 0-6 LPH along with motor suitable for operation at 230 V, 1- Ph, 50 Hz. supply and complete with necessary polypropylene piping, valves, strainers, low level switch and injection fittings. The pump shall have speed & stroke control.
02 Nos. of non clogging type centrifugal Recirculation pumps capable of 12 m3/hr discharge at 20 Meter head and having solid handling capacity of minimum 32 mm size particles having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller (with wiring) to control, etc. (1 W + 1 S)
TERTIARY SYSTEM
02 Nos. of centrifugal Filter feed water pumps capable of 3.5 - 4.0 m3/hr discharge at 32 Meter head having solid handling capacity of minimum 5 mm size particles CI casing & impeller complete with all accessories, motor suitable for 415±10% V, 3- Ph, 50 Hz AC supply, pressure gauge with isolation cock, isolation valve, NRV on delivery line, strainer at suction. mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve, etc. (1 W+ 1 S)
Prefabricated Mild Steel Epoxy painted (MSEP) vessel filter of ø 650 mm & 1800 mm HOS (shell & dishend thickness 4.0 mm minimum) suitable for test pressure of 5.0 kg/cm² and working pressure of 3.5 kg/cm², including media (pebbles, sand, silex, fine sand, fine silex), standard fittings viz. pressure gauge, sampling cock, backwash including frontal piping & valves, etc.
Prefabricated Mild Steel Epoxy painted (MSEP) vessel filter of ø 600 mm & 1800 mm HOS (shell & dishend thickness 4.0 mm minimum) suitable for test pressure of 5.0 kg/cm² and working pressure of 3.5 kg/cm², including media (activated carbon with supporting media), standard fittings viz. pressure gauge, sampling cock, backwash including frontal piping & valves, etc.
SLUDGE DEWATERING SYSTEM
02 Nos. of non clogging type centrifugal Sludge transfer pumps capable of 3.0 LPM discharge at 10 Meter head having CI casing & impeller complete with all accessories, motor of required capacity, delivery header with isolation valve, pressure gauge with isolation cock, level controller (with wiring) to control, etc. (1 W + 1 S)
Manual type filter press of capacity < 25 kg/day having PPE plats, polyester / PPE / Cotton filter cloth with all accessories.
Control panel & cabling for all electrical items of work
Interconnecting pipe work with PVC pipes and MS pipes with anti-corrosive paint for sewage, treated water and tank overflow / backwash pipeline with valves, fittings and accessories.
Supplying & instalation of ultra filtration system with UF feed pump having 3.5 m3/hr flowrate at 25 Meter head & back wash feed pump having 3.5 m3/hr flowrate at 25 Meter head ,cleaning system, panel PLC based UF skip pipng etc.,
NOTE: PARAMETER OF USAGE OF TREATED SEWAGE WATER SHALL BE AS PER GUIDELINES ISSUED BY E-IN-C FOR PLANNING & DESIGN OF SEWER NETWORK & STP VIDE LETTER NO. 86435/MISC/E4(U3), DATED 19/05/2017 & all as specified in PS.
Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth wire 4.00 mmdia by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt ,Earthing lead 4.00mm dia up to 7.5m, 20mm dia medium grade GI watering pipe ,G.I. protection pipe 15 mm dia up to 7.5m long,,PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2014 (part-I)
Fire Protection
M & L for 2 core, 2.5 mm² copper conductor, XLPE insulated armoured cables, conforming to IS: BS EN 60228, having annealed copper conductor, PVC inner sheath, single armouring of galvanized round steel wire, one layer of PETP tape wrapping, collective screen of PETP/Aluminum tape over tinned copper drain wire, RED in colour, including clamping, termination and ferruling complete all as specified and directed. Make: RR Kabel, Havells or Polycab
Supply, installation, testing and commissioning of electric motor driven horizontal end-suction & top discharge, back pull-out type centrifugal booster pump, conforming to IS: 12469- 2011, with CI casing, bronze impeller and stainless steel shaft, mechanical seal, etc. to deliver 450 LPM at 30 m head coupled with a spacer coupling to a 2 pole TEFC type squirrel cage induction motor of suitable HP with IP 55 protection of enclosure at 2900 RPM speed, efficiency not less than 55%, suitable for operation on 415 V ±10%, 3-Phase, 50 Hz AC supply, horizontal foot-mounted type with class F insulation, confirming to IS: 325-1978, with DOL starter, coupling guard, foundation as per manufacturer, complete all as specified and directed. Make: Kirloskar, Mather & Platt, Crompton Greves
[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.
[ii] The shut-off head shall not exceed 120% of rated head.
[iii] The coupling guard shall be of zero access type.
Supply, installation, testing and commissioning of electric motor driven horizontal end-suction & top discharge, back pull-out type centrifugal jockey pump, confirming to IS: 12469- 2011, with CI casing, bronze impeller and stainless steel shaft, mechanical seal, etc. to deliver 180 LPM at 90 m head coupled with a spacer coupling to a 2 pole TEFC type squirrel cage induction motor of suitable HP with IP 55 protection of enclosure at 2900 RPM speed, efficiency not less than 55%, suitable for operation on 415 V ±10%, 3-Phase, 50 Hz AC supply, horizontal foot-mounted type with class F insulation, confirming to IS: 325-1978, with coupling guard, foundation as per manufacturer, complete all as specified and directed.Make: Kirloskar, Mather & Platt, Crompton Greves as approved
NOTES :
[i] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head.
[ii] The shut-off head shall not exceed 120% of rated head.
[iii] The coupling guard shall be of zero access type.
Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type "Motor Control Center" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. Make: Schneider Blokset, Siemens - Sivacon, ABB-MNS as approved.
The MCC shall comprise of the following:
[a] Busbar Chamber:
[i] Copper busbar of rated capacity 500 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
[b] Incoming:
[i] 320 A, 415 V, Ics = Icu = 36 kA, 50 Hz, FP MCCB with adjustable overload settings (0.36- 1 X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 Nos.
[ii] LED phase indicators (Red, Yellow, Blue)- 04 Set
[iii] Power Measurement Device with Class 1 accuracy, complying to IEC 62053- 22, 64 samples/cycle, 31st harmonic analysis, RS485, calibration LED, third party accuracy test certificate - 01 Nos.
[c] Outgoing:
[iii] 20 A, 415 V, Ics = Icu = 16 kA, 50 Hz, 03 Pole MCCB with adjustable overload settings (0.36- 1 X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), instanteneous protection and microprocessor based trip unit- 01 Nos.
[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 05 Nos.
[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 05 Nos.
[vi] LED phase indicators (Red, Yellow, Blue)- 05 Set
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 10 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
M & L for ISI marked MS ERW pipes of size 150 mm dia conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe in excavated trenches with painting of one coat primer and 2 or more coats of synthetic enamel paint of and wrapping of 4 mm thick protection coating by thermo fusion process complete all as specified and directed.Make: Tata, Jindal, BST NOTE: [i] Standard MS fittings with welded joint shall be used on the pipes.[ii] All hangers, clamps, brackets etc. shall be of galvenized iron [iii] Welding of any kind on the galvenised support/hanger shall not be permitted.[iv] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded.
All as per item No 28.84 above but of size 100 mm dia
All as per item No 28.84 above but of size 32 mm dia
Supply, installation, testing and commissioning of "Sprinkler Annunciation Panel" compatible for seamless integration with water flow devices with visual display, internal sounder, alarm/fault indications and stand-by 24 V lead-acid batteries with charger all complete as specified and directed. Make: Tyco, Agni, Safex
NOTE: The panel shall be located in the Fire Pump House and connected to flow indicating switches in sprinkler system.
Supply, installation, testing and commissioning of "Sprinkler Control Valve" along with necessary nut, bolt, flange, gasket, welding etc. including making necessary incoming and outgoing connections and all electrical connections along with 100 mm dia sluice valve conforming to IS: 14846- 2000, 100 mm dia non-return valve conforming to IS: 5312 (Part 1)- 2004, water motor gong or flow switch with bell and 100 mm dia alarm all complete as specified and directed. Make: Agni, Safex, Ceasefire
Supplying, installing, testing and commissioning of universal type flow switch on sprinkler distribution header on each floor including connection to "Fire Alarm Control Panel" through cable. Make: Schneider, Honeywell, Danfoss, Siemens NOTE: Rate quoted shall be inclusive of necessary cable work etc.
M & L for Construction of fly-ash brick masonary valve chamber of size 1000 mm X 800 mm X 1000 mm (internal dimenssions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including necessary excavation & earth work in hard/Dense soil / rock , 6 mm thick MS sheet cover fixed on 25 mm X 25 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC coping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc complete all as specified and directed.
Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type "Motor Control Center" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. Make: Schneider Blokset, Siemens - Sivacon, ABB-MNS as approved by GE.
The MCC shall comprise of the following:
[a] Busbar Chamber:
[i] Copper busbar of rated capacity 250 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
[b] Incoming:
[i] 160 A, 415 V, Ics = Icu = 25 kA, 50 Hz, FP MCCB with adjustable overload settings (0.36- 1 X In) & tr = 0.5 - 16 s, adjustable short-circuit settings (1.5 - 10 X Ir), adjustable earth- fault settings (0.2- 1 X In), current limiting type double break roto active type, instanteneous protection and microprocessor based trip unit- 01 Nos.
[ii] LED phase indicators (Red, Yellow, Blue)- 04 Set
[iii] Power Measurement Device with Class 1 accuracy, complying to IEC 62053- 22, 64 samples/cycle, 31st harmonic analysis, RS485, calibration LED, third party accuracy test certificate - 01 No.
[c] Outgoing:
[v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 02 Nos.
[vi] LED phase indicators (Red, Yellow, Blue)- 05 Set
[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.
[ii] 04 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
HOT WATER SUPPLY
S&F Closed Stationary Storage type water heater geyser, 5 star rating, operating on 230 volt AC, inner tank made out of mild steel,outer body made out of PVC ,coil wattage 2000 W , of capacity 25 lit ,including earth leakage circuit breaker, nut bolt & washer , make HAVELLS model no-PURO PLUS or equvivalant of Crompton/RACOLD
Supply & Lay 3 layer PP-R Polypropylene random copolymer concealed pipes SDR 7.4 (PN-16) UV stablized and antimicrobial fusion welded having thermal stability for hot & wold water suply including all PP-R plain & brass threaded polypropylene random fittings fixed complete with fitting of 20 mm outer dia of pipe to walls, ceilings or in floors etc.
M&O and Comprehensive Maintenance of STP
Comprehensive maintenance All as per item No.1 above but for 70 KLD installed Sewage Treatment plant after expiry of defect liability period all as specified as stipulated below:-
1st year after expiry of defect liability period
2nd year after completion of work of serial No 29.14 above
3rd year after completion of work of serial No 29.15 above
Comprehensive maintenance of sewage treatment plant of capacity 40KLD after expiry of defect liability period all as specified as stipulated below:-
1st year after expiry of defect liability period
2nd year after completion of work of serial No 29.18 above
3rd year after completion of work of serial No 29.19 above
Services for Manning and operation of sewage treatment plant of capacity 70KLD for 3 shifts each of 08 hrs duration i.e. 0600 hrs to1400 hrs,1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs for all day including sunday / holiday etc all as specified and directed by engineer-in-charge.
1st year after expiry of defect liability period
2nd year after completion of work of serial No 29.23 above
3rd year after completion of work of serial No 29.24 above
4th year after completion of work of serial No 29.25 above
5th year after completion of work of serial No 29.26 above
6th year after completion of work of serial No 29.27 above
Services for Manning and operation of sewage treatment plant of capacity 40KLD for 3 shifts each of 08 hrs duration i.e. 0600 hrs to1400 hrs,1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs for all day including sunday / holiday etc all as specified and directed by engineer-in-charge.
1st year after expiry of defect liability period
2nd year after completion of work of serial No 29.30 above
3rd year after completion of work of serial No 29.31 above
4th year after completion of work of serial No 29.32 above
5th year after completion of work of serial No 29.33 above
6th year after completion of work of serial No 29.34 above
M&O and Comprehensive Maintenance of LIFT
LIFT: Comprehensive maintenance and repairs of fully automatic electrically operated passenger lifts of any Make and installed capacity of 08/13 passenger to serve G+ 5, G+, G+10 , G+13 floor with AC variable voltage & variable frequency (VVVF drive) complete with all standard accessories, simplex collective automatic & manual dual controlled operation with/without attendant, automatic centre opening doors wth VVVF door drive (electric motor driven mechanism), sliding stainless steel door automatic rescue device (ARD) system , 3D infra red sensor in full height of door) and built in announcing system without hand set (04 Nos, one each in car, Machine room & near Ground floor landing door) comprising of all devices and accessories through 60 months ( including defect liability period of 24 months ) for all days including holidays etc after expiry of defects liability period as shown below and all as specified and dierected to GE. Note : (i)Contractor shall carryout comprehensive maintenance (routine, daily , weekly , monthly , quarterly , half yearly, yearly ) as per attached Performa and maintain all the lifts in serviceable condition 24 hrs X 365 days without any extra cost .(ii) WO for maint of lifts shall be issued by GE after completion of defect liability period for every consequent year for total period of 3 years.(ii) Final bill shall be paid after certified completion of work for each WO seperately.
(a)1st year after expiry of defect liability period ( Total 06 Nos of Lift )
(b) 2nd year after completion of work of serial No 29.40 above ( Total 06 Nos of Lift )
(c) 3rd year after completion of work of serial No 29.41 above ( Total 06 Nos of Lift )
(a) 1st year after completion of work & taking over site by users [ Total 06 Nos of lift and 06 nos of operators per day in two shifts i.e. 1 operator per shift for 2 nos of lifts in each building ]
(b)- Ditto- but for II nd year after completion of work of serial No 29.44 above
(c) - Ditto- but for Third year after completion of work of serial No 29.45 above
(d) - Ditto- but for Fourth year after completion of work of serial No 29.46 above
(e) - Ditto- but for Fifth year after completion of work of serial No 29.47 above
(f)- Ditto- but for Sixth year after completion of work of serial No 29.48 above
SAWHNEY BUILDWELL LLP
Som Projects Pvt Ltd
S.N. Constructions
SOOD ASSOCIATES PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.07 MB
Download all tender documents and submit your bid