Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.3 LAccepted-AOC | ₹20.3 L | L1 | Accepted-AOC Work Completed. EMD Release |
| 2 | L2₹21.3 L+₹1.1 L (5.20%)Rejected-Finance RAR 107A GROUND FLOOR RAJENDRA ARIHANT TOWER B 1 COMMUNITY CENTRE JANAKPURI NEW DELHI 110058 | NEW DELHI | WEST DELHI | DELHI | 110058 | ₹21.3 L+₹1.1 L (5.20%) | L2 | Rejected-Finance Quoted Amount is More then L1 High |
| 3 | L3₹24.2 L+₹4.0 L (19.5%)Rejected-Finance S 79 OKHLA INDUSTRIAL AREA PHASE II NEW DELHI 110020 | SOUTH EAST | DELHI | 110020 | ₹24.2 L+₹4.0 L (19.5%) | L3 | Rejected-Finance Quoted Amount is More then L1 High |
| 4 | L4₹25.8 L+₹5.5 L (27.0%)Rejected-Finance 13 BANDAL COMPLEX PAUD ROAD PUNE PUNE MAHARASHTRA 411038 | PUNE | MAHARASHTRA | 411038 | ₹25.8 L+₹5.5 L (27.0%) | L4 | Rejected-Finance Quoted Amount is More then L1 High |
| 5 | L5₹25.8 L+₹5.5 L (27.3%)Rejected-Finance Y 51 GROUND FLOOR OKHLA INDUSTRIAL AREA PHASE 2 OKHLA NEW DELHI DELHI 110020 | SOUTH EAST DELHI | DELHI | 110020 | ₹25.8 L+₹5.5 L (27.3%) | L5 | Rejected-Finance Quoted Amount is More then L1 High |
Tender Value
₹36.5 L
EMD Value
₹73,075
Closing Date
23 Dec 2024, 6:00 pmClosed
AGM (Engg-E), AAI, Kolhapur Airport
O/o AGM (Engg-E) AAI, Kolhapur Airport, Kolhapur
Provision of Fire Suppression System for CNS/ATM facilities at Kolhapur Airport
2024_AAI_217248_1
AAI/KOP/CW/NIT/GS-1/2024-25/
Open Tender
Electrical Works
Item Rate
60 days
Kolhapur Airport
5 documents required · 5 mandatory
₹1,180
₹73,075
8 Jul 2025
3 Dec 2024
25 Dec 2024
3 Dec 2024
23 Dec 2024
3 Dec 2024
3 Dec 2024 - 9 Dec 2024
Amount
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) (Individual system) - Equipment room , GF, DVOR Building Surface area:- 21.25 Sqmtr (Approx.) Total volume:- 72.25 cubic mtr. (Approx.)
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) (Individual system) - Battery room , GF, DVOR Building Surface area:-8.5 Sqmtr (Approx.) Total volume:- 28.75 cubic mtr (Approx.)
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) (Individual system) - CCTV Equipment room, GF, ATC Building Surface area:-16.5 Sqmtr (Approx) Total volume:- 57.75 cubic mtr (Approx.)
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) (Individual system) - Battery room, FF, ATC Building Surface area:-13.5 (Approx.) Total volume:- 47.60 cubic mtr (Approx.)
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) (Individual system) - UPS Room, FF, ATC Building Surface area:-12 Sqmtr. (Approx.) Total volume:- 42.00 cubic mtr (Approx.)
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) (Individual system) - Equipment room, FF, ATC Building Surface area:-53.5 Sqmtr (Approx.) Total volume:-186.5 cubic mtr (Approx.)
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) Providing, Fixing,Testing and commissioning ISI marked portable type fire extinguishers of 6 Kg capacity ABC Dry Powder type as per IS‐ 15683 complete as per specification and fixed / install as per site condition, as required.
Design, Supply, Installation, Testing & Commissioning of Clean Agent Gas Flooding System for following areas, complete using Gas Agent as per NFPA 2001. Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement for supervisory switch connection for monitoring cylinder pressure. A pressure gauge with a safety burst disc,electronic control head/Solenoid, pressure operated control, head, flexible hose, strap, NRV and safety cap. Gas-Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System with all cylinders, gas, manifold, Master Cylinder Accessories for above including Electrical Control Head, Discharge Hoseand Gas discharge Warning sign, Nozzles including providing, installing, testing and commissioning of Gas Release Panel complete with timer, battery backup, Gas Release/Gas Abort Switch etc. complete system as required. item also includes Fire alarm system for crosszoning and supply & laying of Fire survival cable, detector & panels. Note: The Individual system will be provided in specified areas only. The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the works. (Area, Volume mentioned here are approx. values and given for indicative purpose, agency has to design for actual measurments at site and as per drawings) Providing, Fixing,Testing and commissioning ISI marked portable type fire extinguishers of CO2 type 4.5 kg capacity as per IS‐ 15683 complete as perspecification and fixed / install as per site condition, as required.
Nexus Fire And Security Systems (BID ID -792791)
PYROGUARD ENGINEERS PRIVATE LIMITED (BID ID -793243)
Vasu Infosec Pvt Ltd (BID ID -794287)
advent electric technologies pvt. ltd. (BID ID -780679)
CENTRE TAP ENGINEERING (BID ID -792663)
RAPID CITY SALES AND SERVICES (BID ID -793278)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .