Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.3 CrAccepted-AOC | ₹31.3 Cr | L1 | Accepted-AOC Accepted |
| 2 | L2₹34.1 CrRejected-Finance | ₹34.1 Cr | L2 | Rejected-Finance Rejected |
| 3 | L3₹36.2 CrRejected-Finance | ₹36.2 Cr | L3 | Rejected-Finance Rejected |
| 4 | L4₹36.2 CrRejected-Finance | ₹36.2 Cr | L4 | Rejected-Finance Rejected |
| 5 | L5₹37.6 CrRejected-Finance | ₹37.6 Cr | L5 | Rejected-Finance Rejected |
Tender Value
₹33.4 Cr
EMD Value
₹43.4 L
Closing Date
28 Dec 2021, 3:00 pmClosed
CCERNDS
The Chief Construction Engineer (RND)S, PB No. 1569, Akbar Road, Secunderabad 500003
Provision of Infrastructure for Establishment of ETF at CAS near Secunderabad
2021_DRDO_659393_1
83629/CIV/ETF/CAS/Con
Limited
Civil Works
720 days
Near Secunderabad
As per NIT
2 documents required · 2 mandatory
₹10,000
Yes
CCERND SECUNDERABAD
₹43.4 L
Yes
27 May 2022
24 Nov 2021
29 Dec 2021
24 Nov 2021
28 Dec 2021
15 Dec 2021
25 Nov 2021 - 14 Dec 2021
Amount
SUBHEAD-I : EARTH WORK & EXCAVATION :
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 Sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.
a)All kinds of Soils
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 Sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m.
a)Ordinary Rock
b)Hard Rock (Blasting Prohibited)
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.
a)All kinds of Soils
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge.
a)Ordinary Rock
b)Hard Rock (Blasting Prohibited)
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.
a) obtained from within MOD Land
a) obtained from outside MOD Land from all leads at contractors own arrangements
Credit for Hard rock Obtained from above
Deduct for Using M-Sand instead of River Sand for filling / Concrete / masonry works at all levels and locations wherever approved by engineer-in-charge.
SUBHEAD-II :ANTI TERMITE TREATMENT :
Supplying chemical emulsion in sealed containers including delivery as specified.
a)Chlorpyriphos/ Lindane emulsifiable concentrate of 20%
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :
a)Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc., with Chlorpyriphos/ Lindane E.C. 20% with 1% concentration.
b) Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor, with Chlorpyriphos/ Lindane E.C. 20% with 1% concentration.
c) Treatment of existing masonry using chemical emulsion @ one litre per hole at 300 mm interval including drilling holes at 45 degree and plugging them with cement mortar 1:2 (1 cement : 2 coarse sand) to the full depth of the hole, with Chlorpyriphos/ Lindane E.C. 20% with 1% concentration.
SUBHEAD-III : PLAIN & REINFORCED CEMENT CONCRETE :
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
a) 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to floor five level, excluding the cost of centering, shuttering and finishing:
a) 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size)
Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth.
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using cement content as per approved design mix, manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement, including cost of admixtures in recommended proportions as per IS:9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge.
(Note :- Cement content considered in this item is @ 330 kg/cum.Excess/less cement used as per design mix is payable/recoverable separately).
a)All works upto plinth level
b) All works above plinth level upto floor v level
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in Recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge.
(Note :- Cement content considered in this item is @ 330 kg/Cum. Excess/ less cement used as per design mix is payable/ recoverable separately).
a) All works above plinth level upto floor v level
Add/ Deduct for using extra/ less cement in the items of design mix over and above the specified cement content therein.
Supplying, fabricating and fixing in position reinforcement bars at all levels and positions including the cost of steel, straightening, cutting, bending, binding and placing in position etc., as per drawings and specifications including the cost of binding wire, labour etc., all complete for reinforced concrete.
a) Thermo-Mechanically Treated bars (Fe 500 Grade)
Centering and shuttering including strutting, propping etc. and removal of form for :
a) Foundations, footings, bases of columns, etc. for mass concrete
b) Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
c) Suspended floors, roofs, landings, balconies and access platform
d) Lintels, beams, plinth beams, girders, bressumers and cantilevers
e) Columns, Pillars, Piers, Abutments, Posts and Struts
f) Small surfaces such as cantilever ends, brackets and ends of steps, caps and bases to pilasters and columns and the like.
g) Weather shade, Chajjas, corbels etc., including edges
i) Extra for shuttering in circular work
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured).
Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Encasing rolled steel sections, in beams and columns, with cement concrete 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size), including centering and shuttering complete but , excluding cost of reinforcement.
SUBHEAD-IV : STONE & BRICK MASONRY :
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with, Cement mortar 1:6 (1 cement : 6 coarse sand).
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:4 (1 cement : 4 coarse sand).
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in Cement mortar 1:3 (1 cement : 3 coarse sand).
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry.
SUBHEAD-V : PLASTERING & SURFACE TREATMENT :
Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) :
a) Flush/ Ruled Pointing
6 mm cement plaster of mix cement mortar 1:3 (1 Cement : 3 fine sand).
12 mm cement plaster finished with a floating coat of neat cement of mix 1:4 (1 cement: 4 fine sand).
15 mm cement plaster on the rough side of single or half brick wall of mix 1:6 (1 cement: 6 fine sand).
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand).
Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers.
Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof
Providing and fixing 22 gauge chicken mesh wire at the junction of RCC and brick work with overlapping of 100mm on both sides, etc., complete.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface.
Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour (Two or more coats on new work) complete, as per manufacturer’s specification.
Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives.
a) New work (Two or more coats applied @ 1.43 litre/ 10 Sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 Sqm
Applying priming coat
a) With ready mixed pink or Grey primer of approved brand and manufacture on wood work (hard and soft wood)
b) With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works.
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade, Two or more coats on new work
Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm.
Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using
galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-incharge.
Providing & fixing false ceiling at all heights with GRG (Glass Fibre Reinforced Gypsum) false ceiling tiles of Size 595x595 mm of approved texture, design and patterns having moisture content less than 2%, humidity resistance of 99%, NRC0.50 to 0.75 as per IS 8225:1987 Non combustible as per BS 476 (part 4)-1970 and light reflectance of 85% (minimum) to be laid in true horizontal level suspended on inter locking metal T-Grid of hot dipped galvanised iron section of 0.33mm thick (galvanized @ 120 grams per sqm including both sides) comprising of main-T runners of size 15x32 mm of length 3000 mm, cross - T of size 15x32 mm of length 1200 mm and secondary intermediate cross-T of size 15x32 mm of length 600mm to form grid module of size 600 x 600 mm, suspended from ceiling using galvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 50 mm long, 8 mm outer diameter M-6 dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 85x25x2 mm. Galvanised iron perimeter wall angle of size 24x24x0.40 mm of length 3000 mm to be fixed on periphery wall / partition with the help of plastic rawl plugs at 450 mm center to center and 40 mm long dry wall wood screws. The work shall be carried out as per specifications, drawing and as per directions of the Engineer-in-Charge. With semi perforated 12 mm thick micro tegular edged GRG false ceiling tiles.
SUBHEAD-VI : FLOORING :
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work shall be paid for separately).
(Note:- Cement content considered in this item is @ 330 kg/Cum. Excess/ less cement used as per design mix is payable/ recoverable separately).
Deduct for using of M-20 grade concrete instead of M-25 grade concrete in C.C. pavement.
Making provision for contraction, expansion, construction and longitudinal joints (size 5x20mm) by groove cutting machine.
Providing and filling in position at expansion joints with poly sulphate sealants of approved brand.
Providing and application of Solvent free self levelling epoxy flooring system of MYK Arment at 5mm thickness. The system comprised of 3mm epoxy modified cementitious underlayment FloArm Cempo2 (Product Conforms to the requirements of EN13813:2002as CT – C40 - F15 – B1.5) along with 2mm self levelling epoxy resin floor topping with 100% solid content of FloArm Top SL2 of MYK Arment. Surface Preparation: Concrete substrates must be prepared mechanically using abrasive blast cleaning, scarifying or grinding equipment to remove cement laitance and achieve an open textured surface. Weak concrete must be removed and surfaced effects such as blow holes and voids must be fully exposed. Repairs to the substrate, filling of blow holes/voids and surface leveling must be carried out using appropriate products from the MYKA Repair & Restoration range of material
A. Primer Application Primer to the concrete substrate:- application of FloArm Primer EPW44 is for each of these substrates: Green concrete (<2 days old) Damp fresh concrete (< 7 days old) Aged concrete (with rising moisture) Dry Concrete (without moisture) B.Underlayment screed:- Application of FloArm Cempo2 at 3mm. C. Priming underlayment screed:- Application of FloArm Primer 1260/1290 D. Topping:- Finally application of Solvent free, Epoxy resin-based Self Leveling floor topping FloArm Top SL2 of MYK Arment at 2mm thickness. Floor Topping must meet the following technical parameters
Mixed Density: Approx. 1.65 gm/cc Shore D hardness After 7 Days at 30'C (ASTM D 2240) :70 - 80 Pot Life : Approx.20 Mins at 30'C Approx.45 Mins at 20'C Abrasion resistance (IS 1237) : 0.35 mm loss Chemical Resistance(ASTM C 722 spot) : 7 Days at 30'C Compressive strength After 7days (IS 9162) > 50N/mm2 @ 30'C Flexural Strength After 7 days (IS 9162) >25N/mm2 @ 30'C Tensile Strength After 14 days (IS 9162) >16 N/mm2 Bond strength at 7 days (ASTM D4541-95):1.5 N/mm2 (concrete failure) Gloss at 60 Deg,1 Day(ASTM D 2457) :85 Skid Resistance on a clean dry surface(ASTM E303) : 50 Note: For more details on work application procedure kindly refer manufactuer detailed methodology before commencement of work.
52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc., complete.
Providing cement skirting in CM (1:3) 18mm thick finished with a floating coat of neat cement etc., complete.
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete.
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per Sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and laying rectified Glazed Ceramic floor tiles of size 300x300mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), including grouting the joints with white cement and matching pigments etc., complete.
Same as above item No.F-93 but in skirting using tiles of suitable size over and including 12mm thick base layer in cement mortar 1: 4 (1 cement : 4 coarse sand) etc., all complete as directed.
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.
a) Size of Tile 600x600 mm
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.
a) Size of Tile 600x600 mm
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab of all colour and texture except Black, Cherry/Ruby Red
Providing and mixing 100% virgin Polypropylene fibers (confirming to EN 14889-2, IS:17161-2020 ASTM C 1116,IRC:SP:46-2013,MoRTH Standard Specifications) for crack and fire control in concrete pavements, PQC , Industrial Floors,concrete slabs,shotcrete etc . Fiber Length : 12mm as per manufacturer Specfications
SUBHEAD-VII : STEEL & WOOD WORKS :
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.
a) In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete.
b)In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete Fixed to openings /wooden frames with rawl plugs screws etc.
Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including MS pressed blet hinges 2.50mm thick with morter guards, lock strike plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:
a) Profile B, fixing with adjustable lugs with split end tail to each jamb
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:
a) 35 mm thick
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
Providing and fixing the following hardware fittings of approved make:
a) 200mm long SS Tower Bolts
b) SS Aldrop 300mm long
Providing and fixing bright /matt finished Stainless Steel handles of approved quality & make with necessary screws etc all complete.
125mm long
Providing and fixing aluminium hanging floor door stopper (Single rubber stopper), ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
Providing and fixing to existing door frames, 30 mm thick Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames.
Providing & Fixing in position windows fabricated from roll formed sections made of colour coated G.I with a combination of specially designed components made up of crca with zinc phosphating nylon or high grade aluminum with powder coating of M/s NCL Seccolor 'Ajanta series' or equivalent make using sections for shutter of 46mm x 46mm and external frame of size 46mm x 52mm, section for glass beading of 18mmx 25mm and centre mullion of size 46mm x 70mm including 5mm thick glass panes with Grill made of 10mm sq. MS Bars welded to at 150mm center-to-center, 6mm x 12mm MS flat and painted with Primer Coat of Epoxy Primer of 5-7 microns thick, finish painted with a Polyester Paint of 12-16 microns thick and back coated with Alkyd backer of 5-7 microns, or Powder Coated with pure Polyester Powder up to 50-60 microns thick all as per specifications of manufacturer and instructions of Engineer-in- charge.
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters.
80x1.25 mm M.S. laths with 1.25 mm thick top cover
Providing and fixing ball bearing for rolling shutters
Supplying, Fabrication, Transportation, and Fixing in position of MS Doors of sizes upto 5m x 5m (Each shutter not exceeding 2.5m x 5m size) made up of ISMC 125mm frame alround, medium grade MS frame work with 125mm x 65mm @ 1250mm c/c (max) in both vertical and horizontal directions, medium grade 40mm x 40mm MS Frame work in diagonal bracings for each panel od 1250 x 1250 (max), covered with 2mm thick MS sheet on both sides duly bent onto the external frame work on sides, top & bottom, hinges with ball bearings/ thrust bearings (fixed to insert plates in the walls) minimum 5 Nos for each shutter finished with two coats of epoxy paint (spray type) of approved brand and shade including priming coat and surface prepared, hardware fittings like 450mm x 25mm aldrop on both sides, 300mm MS handles, Tower bolts of length upto 4m long on top and 450mm long on bottom all including all necessary fittings and fixtures complete as per standard design and instructions of Engineer - in - charge
Supplying, installion, Testing& Commmissioning of Motorised rolling shutter, curtain made of single skinned galvalume sheet laths with natural finish, preesed galvalume sheet hood & motor cover with natural finish, CE Certified CRS Compact Gear PRC, external safty brake three station push button eith deadmen control all including complete. ( Make Gandhi automation or Equivalent)
Providing and fixing frameless 12mm thick toughened glass door with necessary patch fittings like hydraulic floor springs (With stainless steel cover plate minimum 1.25 mm thickness double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates), 25mm dia 450mm long ' H ' Handles, Floor locks etc of as shown in drawing etc. complete as per the direction of Engineer-in-charge.
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & Stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per Sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
Design, manufacture, supply, fixing of Radiography room door made out of lead with M.S Linning including hard ware fittings and Epoxy Painting( Mild Steel and Lead will be Measured and paid under following items) of Apoox size 1000x2100mm
a) Mild Steel
b) Lead
Design, Manufacture, Loading, Supply, Asseembly, Hoisting / Erection Testing and Commissioning of RCC door for clear opening size 4000mm (W) x 4000mm (H) with 1700mm thickness and an overlap of 500mm on three sides of the door including below mentioned items :
a) Wheel assembly-02 Nos. suitable for 120 tonne(Max) carrying capacity(over all) with self aligned mechnaism consisting of : EN-9 forged wheel-08 Nos, "L" brackets-16 Nos, shafts-08 Nos, bearings-16 Nos, covers-16 Nos, wheel connecting shaft-01 No, fasteners, geared coupling etc. b) Top wheel assembly-04 Nos, eccentric roller assembly with bearings, shaft and covers to resist toppling of the door. c) Control panel consisting of MCBs, 16A contractors-03 Nos, overload relay-01 No., pulsh button station, limit switches-02 Nos., cabling etc.
d) Bus bar arrangement (spring action cable releasing drum system / festooning system / shrouded bus bar system). e) Drive assembly including high torque output gearbox, crane duty sq. cage motor, brake coupling, rail cleaners etc. f) Wheel boggies to carry 60 tonne load with uniform load distribution system for wheel assembly including fabrication and machining. g) Limit switch-02 Nos. at open and close positions of the door and over travel limit switches. h) Rail CR-80 with fixing plates and bolts with ISMC 100 @ 2000mm c/c stiffners
i) Top guide rail with ISMC 200 stiffners @ 1000mm c/c. j) Two coats of epoxy paint over a suitable coat of primer for all exposed steel surfaces. k) Providing and casting form finish RCC M-40 cement concrete for doors including providing of reinforcement, shuttering, curing et c,at site complete. l) Erection, testing and commissioning of the motorised concrete door
SUBHEAD- VIII: MISCELLANEOUS:
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations:
a) Applying a slurry coat of neat cement using 2.75 kg/Sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.
b) Laying brick bats with mortar using broken bricks/brick bats 25mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.
c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ Sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge.
d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement : 4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300mm square 3 mm deep.
e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge, with average thickness of 120 mm and minimum thickness at khurra as 65 mm.
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.
Single socketed pipes of 110mm diameter
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.
110mm Bend 87.5°
110mm Shoe (Plain)
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete.
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage For vertical surface two coats @ 0.70 kg per sqm.
SUBHEAD-IX : SANITARY SERVICES:
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :
White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests.
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :
W.C. pan with ISI marked white solid plastic seat and lid.
Providing and fixing floor mounted, white vitreous china single piece, double traps syphonic water closet of approved brand/make, shape, size and pattern including integrated white vitreous china cistern of capacity 10 litres with dual flushing system, including all fittings and fixtures with seat cover, cistern fittings, nuts, bolts and gasket etc., including making connection with the existing P/S trap, complete in all respect as per directions of Engineer-in-Charge.
Providing and fixing G.I. inlet connection for flush pipe connecting with W.C. pan.
Providing and fixing white vitreous china flat back urinal basin of 430x260x350 mm size.
Providing and fixing C.P 15 mm Urinal spreader size 95x69x100 mm with 1/2" BSP thread and shapes, weighing not less than 60 gms.
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required :
White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar taps.
Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings.
Providing and fixing toilet paper holder, C.P. Brass.
Supply and fixing of 15 mm CP Health faucet Cum bib tap with 1.25 mts long tube with end nuts and hook and 1 no 15 mm CP brass angular stop cock with wall flange, Hook to be fixed with CP brass with suitable counter sunk screws, all of approved make etc., complete.
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.
Granite of any colour and shade.
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc., complete as per design approved by Engineer-in-Charge.
Granite Work
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/Granite/stone work, including necessary holes for pillar taps etc., including moulding, rubbing and polishing of cut edges etc. complete.
Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth.
a) Granite Stone of approved shade
Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.
32mm dia Flexible pipe
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing cp towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms.
Providing and fixing PVC/SWG Pipes conform to IS:13592-1992 of Type-A for sewage Disposal and Vent pipes Inclduing fixing of Clamps For every 1.5mt interval all necessary fittings likes bends, door bends, couplers, o Rings ,Pasting solvent etc., complete.
a)100mm dia PVC/SWG Single socket
b)75mm dia PVC/SWG Single socket
Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete for PVC SWG Pipes conform to is 13592-1992.
a)100mm dia PVC/SWG Single socket
b)75mm dia PVC/SWG Single socket
Providing and fixing PVC door bends as per IS - 13592-1992 single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete.
a)100x100x100 mm
b) 75x75x75 mm
Providing and fixing terminal guard, Sand cast iron S&S as per IS - 3989.
a) 100mm dia.
b) 75mm dia.
Providing and fixing M.S. stays and clamps for pvc pipes of diameter.
a) 100mm dia.
b) 75mm dia.
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors, Sand cast iron S&S as per IS: 3989.
a) 100 mm inlet and 100 mm outlet
Cutting chases in brick masonry walls for following diameter sand cast iron/ centrifugally cast (spun) iron pipes and making good the same with cement concrete 1:3:6 ( 1 cement : 3 coarse sand :6 graded stone aggregate 12.5 mm nominal size), including necessary plaster and pointing in cement mortar 1:4 (1 cement : 4 coarse sand) :
a) 100mm dia.
b) 75mm dia.
Supply and fixing in position best quality and approved make CP brass coat hooks with flanges fixed to wall/door shutters with necessary screws washers etc., complete.
SUBHEAD-X : WATER SUPPLY SERVICES :
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. - External Work.
a) 25 mm dia nominal bore
b)32 mm dia nominal bore
c)40 mm dia nominal bore
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.,
a)15 mm dia nominal bore
b)20 mm dia nominal bore
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :
a)25 mm dia nominal bore
b)32 mm dia nominal bore
c)40 mm dia nominal bore
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :
a) 25 mm nominal bore
Providing and fixing CP brass bib cock of approved quality :
a) 15 mm nominal bore
Providing and fixing CP brass stop cock of approved quality :
a) 15 mm nominal bore
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931.
a) 15 mm nominal bore
Making chases up to 7.5x7.5 cm in walls including making good and finishing with matching surface after housing G.I. pipe etc.
SUBHEAD-XI : INTERNAL ELECTRIFICATION :
Point Wiring for Light/ Fan/ exhaust fan with 2 runs of 1100V grade 1.5 Sq.mm & 1 run of 1.5 Sq.mm PVC insulated multistrand , FRLS , Copper conductor wires , run in and including 25mm dia heavy gauge PVC conduits concealed in wall / ceiling conforming to IS 732 including all accessories such as junction boxes, conduit bends elbows and anodised GI Switch box with modular switch and the box covered with front plate including connections to Earth terminal.
a) One Light point controlled by one 6 A switch.
b) Two Light point controlled by one 6 A switch.
Ceiling fan point controlled by one 6 A switch and electronic fan regulator of 100 W step type with concealed MS fan hook box.
Exhaust fan point controlled by one 6 A switch.
Supply and fixing of 6A, 3Pin Socket outlet with 6A switch in Lighting switch boards. (Dependant).
Supply and fixing of 6A, 3Pin Socket outlet with switch of 6A rating with wiring of 2 Runs of 2.5 Sqmm and 1 Run of 2.5 Sqmm FRLS, PVC insulated multistranded Copper conductor wires run in and including 25 mm Dia, 2 mm thick PVC conduit. (Independant).
Supply and Wiring with the following size 1100V grade PVC insulated multistrand FRLS Copper conductor wires in and including suitable size heavy gauge PVC conduit concealed in wall / Ceiling including all accessories such as junction boxes, bends, elbows including end terminated with suitable lugs.
a) 2 runs of 2.5 Sq.mm wires with 1run of 2.5 Sq.mm wire in and including 25 mm Dia PVC Conduit (For Lighting Circuit)
b) 4 runs of 6 Sq.mm wires with 2 runS of 6 Sq.mm wires in and including 32 mm Dia PVC Conduit (For Lighting Sub Mains)
Supply of the following type Fluorescent/ Compact fluorescent light fixtures on wall/ Ceiling including all fixing accesssories such as leads, etc complete as required. The Fluorescent/CFL fixtures shall be complete with Low loss copper ballast PF improvement capacitor, Bipin Rotor type lamp holder,starter, starter base, all prewired upto the terminal block. All fixtures shall be supplied with lamps. The Catalogue Numbers refers to Philips Make.
a) 40 W Surface mounted LED 4 Feet Length Luminaire
(Philips : BN308C LED40S-6500 L120 PSU WH )
b) 1 x 12 W Surface Mounted LED Luminaire
(Philips Cat No : SM250C LED 12S-6500PSU WH)
c) 40 W Recess Mounted LED Light Fixture
(Philips Cat No :RC 380 B LED 40S-6500 G4L60W60 PSU OD )
d) 20W Recess mounted Down Light Fixture
(Philips Cat No DN195B LED20S-6500 PSU WH S2 )
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Supply of ceiling fan of 1200mm sweep ( white colour) suitable for operation on 230/240V, 50Hz, single phase, AC Supply complete with double ball bearing motor, required down rod, capacitor, three MS blades etc complete. (5 Star Rating)
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Supply of 305 mm sweep Exhaust fans with Metallic blades and MS gravity louvers including all accessories / Installation materials required.
Supply of 380 mm sweep Exhaust fans with Metallic blades and MS gravity louvers including all accessories / Installation materials required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. a) Upto 450 mm sweep
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
a) 6 way (8 + 18), Double door
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of 6A to 32A rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.
a) Single Pole
SUBHEAD-XII : POWER WIRING :
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
a) 6 way (8 + 18), Double door
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCBO), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of 6A to 32A rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.
a) Single Pole
MODULAR POWER SOCKETS
Supply,erection,testing and commissioning of the following switch sockets with anodised G.I. Box, front plate and fixing screws etc .
a) 6/16 Amps, 5-pin (250 Volts) single phase modular type socket controlled by 16 Amps SP Switch.
b) Supply and fixing of factory made 25A, 1Ph Metalclad socket with plug top & 25A SPMCB in MS box including all fixing accessories
c) Supplying and fixing 32A, 415V, TPN industrial type socket outlet with 4 pole and earth metal enclosed plug top alongwith 32A C Curve, TP MCB in sheet metal enclosure on surface/recess with chained metal cover for the socket outlet and complete with connections ,testing and commissionining etc complete as required.
d) Supplying and fixing 63A, 415V, TPN industrial type socket outlet with 4 pole and earth metal enclosed plug top alongwith 63A C Curve, TP MCB in sheet metal enclosure on surface/recess with chained metal cover for the socket outlet and complete with connections, testing and commissionining etc complete as required.
Wiring
Supply and Wiring with the following size 1100V grade PVC insulated multistrand, FRLS Copper conductor wires in and including suitable size heavy gauge PVC conduit concealed in wall / Ceiling including all accessories such as junction boxes, bends, elbows including end terminated with suitable lugs.
a) 2runs of 4Sq.mm wires with 1run of 4 Sq.mm wire in and including 25mm dia PVC Conduit(For 16A Sockets).
b) 2runs of 6Sq.mm wires with 1run of 6 Sq.mm wire in and including 25mm dia PVC Conduit(For AC Sockets).
c) 4 runs of 6 Sq.mm wires with 2 runS of 6 Sq.mm wires in and including 32 mm Dia PVC Conduit (For Lighting Sub Mains)
d) 4runs of 10Sq.mm wires with 2run of 6 Sq.mm wire in and including 25mm dia PVC Conduit
MAIN BUILDING PANELS
Supply, installation, Testing and Commissioning of 3 phase and Neutral 415V, 4 wire Free Standing Floor mounted MV panel made out of 14 SWG MS sheet after seven tankprocess and painting with Epoxy powder coating. The panel shall consist of suitable rating TPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and color coded with Heat shrinkable sleeves.The Metering shall be provided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below. The panel shall be got fabricated from manufacturers with CPRI Test certificate only. The size of all Panel Mounting Meters shall be 96X96mm. The Panels shall be mounted on U channels including supply and fixing of the same. Each panel is to be provided with minimum of two numbers of spare Cubicles.
a) MAIN PCC (INDOOR) - DYNAMIC TEST FCAILITY
LIGHTING & POWER PANEL
Incomer
1600 A, 70KA, TPN ACB, Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No
2A, control MCB - 3 Nos.
Outgoings :
1250A ,50KA TPN, MCCBs - 2 Nos
800A ,50KA TPN, ACBs - 2 Nos
100A ,25KA TPN, MCCBs - 2 Nos
63A ,16KA TPN, MCCBs - 5 Nos
32A ,10KA TPN, MCBs -25 Nos
Bus Bar : 1600 A TPN Alluminium Bus Bar-1 Set
Metering Incomer :
CT Operated Load Manager (similar to EM-6400) - 1 No
LED phase indication lamps with toggle switch -1set
b)USER EQUIPMENT PANEL- ( INDOOR ) DYNAMIC TEST FCAILITY
Incomer
1250 A, 50KA, TPN ACB, Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No
2A, control MCB - 3 Nos.
Outgoings :
250A ,35KA TPN, MCCBs - 2 Nos
100A ,25KA TPN, MCCBs - 4 Nos
800A ,50KA TPN, ACBs - 2 Nos
63A ,16KA TPN, MCCBs - 2 Nos
Bus Bar : 1250 A TPN Alluminium Bus Bar-1 Set
Metering Incomer :
CT Operated Load Manager (similar to EM-6400) - 1 No
LED phase indication lamps with toggle switch -1set
c) MAIN PCC (INDOOR) - CLIMATIC TEST FACILITY
LIGHTING & POWER PANEL
Incomer
1000 A, 50KA, TPN ACB, Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No
2A, control MCB - 3 Nos.
Outgoings :
1000A ,50KA TPN, ACBs - 2 Nos
100A ,35KA TPN, MCCBs - 2 Nos
63A ,16KA TPN, MCCBs - 3 Nos
32A ,10KA TPN, MCBs - 25 Nos
Bus Bar : 1000 A TPN Alluminium Bus Bar-1 Set
Metering Incomer :
CT Operated Load Manager (similar to EM-6400) - 1 No
LED phase indication lamps with toggle switch -1set
d) USER EQUIPMENT PANEL- ( INDOOR ) CLIMATIC TEST FCAILITY
Incomer
1000 A, 50KA, TPN ACB, Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No
2A, control MCB - 3 Nos.
Outgoings :
400A ,50KA TPN, MCCBs - 2 Nos
200A ,35KA TPN, MCCBs - 3 Nos
100A ,25KA TPN, MCCBs - 4 Nos
63A ,16KA TPN, MCCBs - 2 Nos
Bus Bar : 1000 A TPN Alluminium Bus Bar-1 Set
Metering Incomer :
CT Operated Load Manager (similar to EM-6400) - 1 No
LED phase indication lamps with toggle switch -1set
e) MAIN PCC (INDOOR) - RADIOGRAPHY FACILITY
LIGHTING & POWER PANEL
Incomer
250 A, 35KA, TPN MCCB, Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No
2A, control MCB - 3 Nos.
Outgoings :
160A ,35KA TPN, MCCBs - 2 Nos
100A ,25KA TPN, MCCBs - 2 Nos
63A ,16KA TPN, MCCBs - 5 Nos
Bus Bar : 250 A TPN Alluminium Bus Bar-1 Set
Metering Incomer :
CT Operated Load Manager (similar to EM-6400) - 1 No
LED phase indication lamps with toggle switch -1set
f) MAIN PCC (INDOOR) - REMOTE CONTROL ROOM
LIGHTING & POWER PANEL
Incomer
400 A, 50KA, 4P, MCCB, Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No
2A, control MCB - 3 Nos.
Outgoings :
200A ,35KA TPN, MCCBs - 3 Nos
100A ,25KA TPN, MCCBs - 1 Nos
63A ,16KA TPN, MCCBs - 6 Nos
Bus Bar : 400 A TPN Alluminium Bus Bar-1 Set
Metering Incomer :
CT Operated Load Manager (similar to EM-6400) - 1 No
LED phase indication lamps with toggle switch -1set
Providing and fixing of maintenance free earthing which consists of 40mm Dia, standrad length (as per Equipment Supplier) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Earth enhancing compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.
Supply and laying of following size strips including all necessary inter connections with earth station and equipments.
a) 50 X 5 mm Hot dip GI strip
b) 25 X 5 mm Hot dip GI strip
c)Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
Cable Trays
Supply and fixing of following size GI Perforated type cable tray made out of 2mm thick G.I sheet including MS supports for fixing the tray, anchor fasteners etc., laid including 2runs of 25x5 GI strip etc including with 2 mm thick GI covers.
a)300 mm wide x 50 mm Height
b)150 mm wide x 50 mm Height
c) 100 mm wide x 50 mm Height
Supply, laying, jointing GI pipes of medium quality including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.
a) 50mm Dia
SUBHEAD-XIII : TELEPHONE CONDUITS :
Supply and laying of 25mm dia, 16 SWG black enamelled M.S. conduit concealed in wall/ ceiling/ floor including all accessories such as junction boxes, conduit bends, etc., complete as required for Telephone etc.,
Supply and laying of 25mm dia, heavy gauge PVC . conduit concealed in wall/ ceiling/ floor including all accessories such as junction boxes, conduit bends, etc., complete as required for Telephone etc.,
Supply and laying of 25mm dia, heavy gauge PVC . conduit concealed in wall/ ceiling/ floor and drawing of 12 SWG GI Wire as fish wire for laying of LAN Cables at a later stage and supply of all fixing accessories such as junction boxes, conduit bends, etc., complete as required.
Supply and fixing of Telephone outlet (RJ11) with anodised GI box with front plate and fixing screws.
Supply,Installation,Testing and commissioning of RJ 45 socket(FOR LAN) with flush mounting G.I. box, with front plate and fixing screws etc complete.
Supply and laying of 2pair 0.5mm dia PVC insulated Copper conductor Telephone wire conforming to DOT Specifications in already laid PVC Conduit including necessary interconnections.
Supply and laying of Cat 6 LAN cable conforming to DOT Specifications in already laid PVC Conduit including necessary interconnections.
Supply and installation of 10 pair Krone connectors in MS junction box complete as required.
Supply and installation of 20 pair Krone connectors in MS junction box complete as required.
Supply, laying, jointing GI pipes of medium quality including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.
50mm Dia
SUBHEAD-XIV : LIGHTNING PROTECTION :
Providing and fixing of maintenance free earthing which consists of 40mm Dia ,standrad length (as per Equipment Supplier ) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Earth enhancing compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.
Supply and laying of following size strips including all necessary inter connections between earth station and equipment. supports for strips as applicable and directed by engineer in charge.
a) 32 X 6 mm Aluminium strip conductor with DMC Insulator Supports.
b) 50 X 5 mm GI strip conductor including excvation and back filling.
Supply and installation of vertical air termination with 100mm dia copper hollow sphere with spikes, fixed on 1500mm length 50mm dia Class C GI pipe including all fixing accessories.
Providing and fixing of Test links for Lightning protection system.
SUBHEAD-XV : SPECIAL EARTHING :
Providing and fixing of maintenance free earthing which consists of 65 MM Dia ,2.5 mtr long electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Earth enhancing compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.
Supply and laying under ground/above ground of following size strips including all necessary interconnections between earth station and equipments including earth excavation, back filling, intermediate supports for strips as applicable and directed by engineer in charge.
a) 25 x 3 mm copper strip on DMC insulators
b)25 x 3 mm copper strip below ground.
Supply and fixing of Static Discharge Handles made out of 40 mm dia Copper rod 600 mm Long fixed on wall with brass spacers and connected to 25 x 3 mm copper strip by brazing.
Supply, laying, jointing GI pipes of medium quality including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.
50mm Dia
SUBHEAD-XVI : EOT CRANES:
Design,manufacture and supply of Flameproof Double Girder Crab type EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revisions as shown below complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores / building, where to be installed etc., movement of material to work spot including the cost of consumables paint etc. as required. The crane shall be designed for earthquake and sesmic qualification. Span to be measured by the the Bidder at Site and it shall be its sole responsibility to provided Span Suitable.
PART- I : SUPPLY
Supply of Flameproof 10Ton capacity Double Girder EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. a) Dynamic Test Facility – 1No Span-22m,Bay Length –25m,Lift- 08m
Crane operating speeds
Main speed Micro speed
Main hoist : 2.5m/min 0.25m/min
Cross travel : 10m/min 1.0m/min
Long travel : 15m/min 1.5m/min
Micro speed for all motions : 10% of main speed through VVVF drives.
Provision of inching is to be incorporated in the drives.
Supply of Flameproof 10Ton capacity Double Girder EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. a) Clymatic Test Facility – 1No Span-20m,Bay Length – 25m,Lift- 08m
Crane operating speeds
Main speed Micro speed
Main hoist : 2.5m/min 0.25m/min
Cross travel : 10m/min 1.0m/min
Long travel : 15m/min 1.5m/min
Micro speed for all motions : 10% of main speed through VVVF drives.
Provision of inching is to be incorporated in the drives.
Supply of Flameproof 5Ton capacity Double Girder EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. a) Radio Graphic Test Facility, Span: 10.00 mts. Bay length: 12.00 mts.Lift: 5.00 mts
Crane operating speeds
Main speed Micro speed
Main hoist : 2.5m/min 0.25m/min
Cross travel : 10m/min 1.0m/min
Long travel : 15m/min 1.5m/min
Micro speed for all motions : 10% of main speed through VVVF drives.
Provision of inching is to be incorporated in the drives.
Supply of shrouded bus bar system with double shoe copper current collections system complete with support tracks, cable loops, junction boxes and cable from main supply point to crane festoons with all necessary fixtures etc complete.
Supply of material for Gantry Rails section 60 Lb of prime material in length of 10 mts and above complete with mounting arrangement at the building over the crane girder including painting of rails with approximate colour code as approved by the dept.
Supply of material for Gantry Rails section 105 Lb of prime material in length of 10 mts and above complete with mounting arrangement at the building over the crane girder including painting of rails with approximate colour code as approved by the dept.
Part-II: - ERECTION, TESTING AND COMMISSIONING
Erection, testing and commissioning of EOT cranes and others mentioned in item S.No.409 to 431 of Part-I as per the relevant IS standards and approved drawings
Erection, testing and commissioning of Flameproof 10, Ton capacity Double Girder Flame Proof EOT Crane mentioned in Item S. No.409 of Part-I with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. Location:Dynamic Test Facility – 1No Span: 22m ±0.5mtrs,Bay Length –25m,Lift- 08m
Erection, testing and commissioning of Flameproof 10, Ton capacity Double Girder Flame Proof EOT Crane mentioned in Item S. No.417 of Part-I with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. Location: Clymatic Test Facility – 1No Span: 20mtrs± 0.5mtrs,Bay Length – 25m,Lift- 08m
Erection, testing and commissioning of Flameproof 5, Ton capacity Double Girder Flame Proof EOT Crane mentioned in Item S. No.425 of Part-I with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. Location: Radio Graphic Test Facility, Span: 10.00 mts. ±0.5mtrs Bay length: 12.00 mts.Lift: 5.00 mt
Erection testing and commissioning of shrouded type current collection system complete as per the item Sl No.433of Part I over the crane bay including tapping of supply for electrical panel testing & handing over the crane as per the approved QA plan etc complete.
Erection, testing & commissioning of Gantry rail section 60 Lb mentioned in item Sl No.434 of Part -I with mounting arrangement and fixing hardware etc., complete over the bay length to match the span of the crane within the permissible accuracy levels for span in height variation as per the QA Plan etc complete.
Erection, testing & commissioning of Gantry rail section 105 Lb mentioned in item Sl No.435 of Part -I with mounting arrangement and fixing hardware etc., complete over the bay length to match the span of the crane within the permissible accuracy levels for span in height variation as per the QA Plan etc complete.
SUBHEAD-XVII : AIR CONDITIONING;
Supply, Installation, Testing, commissioning and handing over of Air cooled Scroll chilled water plant of Capacity 48 TR chillers at hyderabad abmient condition , each unit comprising of :
a) Air cooled Condenser with other accessories
b) DX type shell and tube Chiller with accessories having entering/leaving conditions of water 52 Deg F/43Deg F with maximum pressure drop of 7M.
c) Steel structure for assembling/mounting the equipment, finished with powder coated painting, spring type vibration isolators for installing the equipment on foundation
d) Control panel incorporating all safety functions including HP & LP cutouts, single phase preventor, internal control wiring for sequential operation, contactors for sensing flow through leaving chilled water control, compressor & Thermostatic expansion valve modulation with automatic load limiting devices
e) Inter connected refrigerant piping with safety controls viz. Liquid line solenoid valves, HP/LP controls
f) Full charge of refrigerant R407C / R 410a
g) Unit mounted starter panel comprising of disconnect switches, DOL starters, 3 Phase current Transformers and other essential compressor motor protecting devices
h)Insulation of shell & Tube chiller with Nitrile rubber
Supply, Installation, Testing, Commissioning and handing over of Centrifual End Suction Top discharge Pump of following capacities .MOC (body : Cast Iron; Shaft : SS ; Impeller : Bronze , RPM : 1450, Meachnical Seal ) including necessary drive assebembly , base frame and civil foundation as required complete
a) 120 US GPM @ 30 mt head with suitable rating motor (EFF1) and drive arrangement,Mechanical seal, base frame etc
Supply, Installation and Commissioning of Double Skin AHU. The panels made out of 45 +/- 2 mm thick fabricated out of pre coated 0.6 mm thick GI on outer side and 0.6 mm thick plan GI on inner side with PUF insulation density of 38+/-2 Kg/Cu.m. The framework shall be of internally coved extruded aluminum and thermal break hollow sections. AHU shall comprising of mixing box section with aluminum airfoil blade low leakage type F/A dampers suitable for manual operation. Filter secction with Pre filter section with flange type 10 & 5 micron filters on universal frame, Coil section with 6 row chilled water cooling coils ,2 Row hot water coil insulated SS 304 stainless steel drain pan, fan section with PLUG fans DIDW Limit Load centrifugal fan , spark proof & flame proof EFF1 motor, LED lamps for filter sections, fan section with on / off switches for operation from outside, limit switch for the fan section access door with a view port,belt drive with taper lock bush pulleys. fire retardant flexible canvas connection between fan & AHU panel, internal vibration mounts under the fan & motor frame, supply outlet will be aluminum airfoil blade low leakage type S/A damper suitable for manual operation. All the internal wiring of the unit for lamps & door interlock etc shall be in the scope of the AHU vendor(All the dampers shall be low leakage aluminium aerofoil design and suitable for manual / motorised operation.
All the internal wiring of the unit for lamps & door interlock etc shall be in the scope of the AHU vendor. An UV generator with Watmiser shall be installed at the cooling coil section to prevent the formation of Bacteria etc. Scope includes temperature controller etc and control cable & wirning from VFD starter to AHU motor and field intruments, required controls, power supply and cables for UV generator etc complete (VFD in Electrical Scope)
a) AHU:1&2 10000 CFM Cap, 50 mmwg St. Pr Coil Capacity 25 TR , 6 row chilled water coil , 2 row Hot water coil
b) AHU:3 20000 CFM Cap, 65 mmwg St. Pr Coil Capacity 50 TR , 6 row chilled water coil , 2 row Hot water coil
Supply, erection, testing and commissioning of Under Ground Pre Insulated MS class 'C'( Heavy duty) conforming to BIS 1239 ERW insulated Chilled water piping complete with civil brick pedestals / MS supports wherever necessary, fittings and pressure testing of pipes including excavation of 1000mm below ground , civil pedastals as per tender specificatons , refilling, .Insulation shall be of PUF thickness below 100mm 32mm thick & above 100mm 50mm thick with density 36 kg/cum, min. compressive stength 40 PSI and HDPE cladded.for the following sizes:
Supply, erection, testing and commissioning of Above Ground Pre Insulated MS class 'C'( Heavy duty) conforming to BIS 1239 ERW insulated Chilled water piping complete with civil brick pedestals / MS supports wherever necessary, fittings and pressure testing of pipes including excavation of 1000mm below ground , civil pedastals as per tender specificatons , refilling, .Insulation shall be of PUF thickness below 100mm 32mm thick & above 100mm 50mm thick with density 36 kg/cum, min. compressive stength 40 PSI and GI spiral outer jacket for the following sizes:
(ii) 3" dia
(iii) 2 1/2" dia
(iv) 2" dia
Supply, fixing, testing and commissioning of the following valves PN 10 rating as per engineering standards and specifications PUF insulation with GI Cladding .
(a) Butterfly valves
(ii) 2 1/2" dia
b) Globe valve
(c) Balancing Valves
(ii) 2 1/2 " Dia
Supply, Installation, Testing and commissioning of 3 way Motorised valves with Actuator for operating at 0-10V DC supply for chilled water as per specification along with Thermostat control including PUF insulation with GI Cladding.
a) 80mm dia
b) 65mm dia
c) Non Return Valves
d) Y- Strainers
e) Pressure gauges
f) Thermometers
g) Water flow switch
h) Auto Air Vents - 20mm Dia
Supply,Installation,Testing and Comissioning of 500 Lit expansion tank with float vavle and other accessories etc complete
Supply,Installation,Testing and comissioning of Microbubler Air & Dirt separator with matching flanges bolts,Nuts gaskets, Insulation, valves and airvent. For the size of 100 mm Dia PN10
Supply, Installation, Testing, Commissioning and handing over of Vertical Hotwater generator M S poweder coated along with all safties and protections with LED/Jewel lamp indication and relief valves complete generating hot water of minimum temp 55 Deg C and max of 65 Deg C suitable for recirculation of water including safety items as per specification
a) 55 KW Capacity
b) 30 KW Capacity
Supply, Installation, Testing, Commissioning and handling over of End Suction Top discharge Pump of following capacities with required head as per the following Hotwater pumps including necessary stuffing box and suitable for operation to withstand temperature of upto 90 Deg C etc., complete
a)28 US GPM @ 15 mt head and required rating motor along with Mecchanical seal, drive transmission accessories and base frame etc
b)15 US GPM @ 15 mt head and required rating motor along with Mecchanical seal, drive transmission accessories and base frame etc
Supply, erection, testing and commissioning of MS class 'C' ERW insulated Hot water piping complete with civil / MS supports wherever necessary, fittings and pressure testing of pipes including civil pedastals , M S supports , Insulation of piping shall be 75mm thick rock wool covered with vapour barrier, Chicken wire mesh and 26 G Al.cladding as per tender specifications for the following:
a) 1 1/2" dia (40mm)
b) 1 1/4" dia (32mm)
c) 1 " dia (25mm)
Supply, fixing, testing and commissioning of the following valves PN 10 Rating as per engineering standards and including insulation of rock wool and Al cladding specifications.(For Hot water system)
i)Butterfly Valves
a) 1 1/2" dia (40mm)
ii) Y Strainers
a) 1 1/2" dia (40mm)
b) 1 1/4" dia (32mm)
iii)NRV
a) 1 1/2" dia (40mm)
b) 1 1/4" dia (32mm)
iv) Ball valves
a) 1" dia (25mm)
b) 1 1/4" dia ( 32mm)
v) Pressure gauges
vi) Dial type Thermometers
vii) Balancing valves
a) 1 1/2 " dia ( 40mm)
b) 1 1/4 " dia ( 32mm)
viii) Supply,Installtion,Testing and commissiosing of 3 way Solonide valves of rating PN 10 with Actuator for operating at 0-10V DC supply for Hot water as per specification along with Thermostat control. Including insulation of the valve.
a) 1" Dia (25mm)
b)1 1/4" Dia (32mm)
Supply, Installation,Testing,Commissioning of Out door type Double skin construction Air handling unit made out of extruded Aluminum structural frame work and casted polyemide/Aluminum corner / inter-mediate connecting pieces. Panels shall be made of 43mm PUF injected panels in galvanized sheet casings having scratch free plastisol coating on galvanized sheet.
The Air handling unit shall comprise of fan section with Forward curved Centrifugal fan & fan motor and motor drive assembly along with flame proof motor , bearings of the fan mounted on the scroll and not on the casing, coil section comprising of 6 row DX coil INTERLACED/INTERWINTED design DX Cooling coil to make multi distributers for multiple circuits as per requirement. drain pan made of stainless steel 1mm thick sheet under the fan and coil sections, Filter section comprising of pre filters & Fine filter etc complete, including weather proof canopy including all accessorie .
AHU 1 - 16TR 6400 cfm, 14 Sqft of Coil area 6 row coil with 3" static pressure,DX Coil in multiple circuits Suitable for 3 nos 8.5 TR CDU etc complete.
Supply,Installation, testing, commissioning of Scroll type compressor Condenser units of following capacity including Thermostatic Expansion valves one per each circuit, saftey control and thermostat and PLC control panel , inter connected control / power cables and other accessories etc. The unit shall be precharged and included with any topup charging at the time of commisioning .the controls , vavles and accessories along with the equalisation timer , seqencitial controller and the expansion devices and its safities shall be included in the cost of the unit. only refrigerant piping between the units shall be measureable.
b)8.5 TR Condenser units
Supply, Installation, Testing and commissioning of following size hard copper piping for Condenser units with insulation of 6mm thick Nitrile Rubber pre formed sections including supporting fixtures and accessories etc., complete.( 8.5TR condenser units 6Nos )
Supply,Erection,Testing and Commissioning of Drain piping with HDPE PVC Pipe 1 1/2" dia as per specification.
Supply, installation, testing and commissioning of Flange type, Flame proof FLP duct heaters with Mineral Filled AISI SS304/SS321 Sheathed Tubular Heater with GI Helical fins, Tube dia 8.2mm min and Helical Finn dia 25mm min,enclosed in the frame, FLP Terminal box etc,Nickel Chromium Inner Element, Silicon Sealing to Restrict Moisture pickup,Silver brazed mounting plate etc, and heters shall be controlled with PID thyrestor controller based on the humidstat. And this should have saftey thermostat and cutouts & air stat etc all safety controles. The capacities as follows and sizes of the heaters shall be as per the duct sizes and approved drawing.
a) 12 kW Capacity
Air Distribution
Supply, Installation, testing and commissioning of Factory fabricated and boxed GI ducting using class VIII sheets / coil as per IS655, should be fabricated as per IS275 , galvanised hardware & supports, at all longitudinal joints, Two coated painted (Red Oxide & Black Paint( Asian) M.S.Iron angle flanges for all the joints, bracing angles and minimum 5mm thick neoprene balck foam rubber gasket.
Supply & Fixing of Nitrile rubber class-`O` the following thickness with aluminium foil faced density 40-60 Kg/cum- for inside supply air ducts. HERA( Aero Foam & A-Flex) Turbo Fix-SR-E-10 Synthetic Rubber Adhesive as per the specifications .
a) 19mm thickness
b) 13mm thickness
Supply and fixing of Acoustic Insulation with 10mm Open cell nitrile rubber material density 110 to 140 kg/cum for Ducting.
Dampers
Supply, erection,testing and commissioning of Aluminum low leakage aerofoil design volume control dampers suitable for manual operation.
Supply , erection, testing and commissioning of CBRI approved 16G GI Spring return actuated fire dampers rated for 120 minutes including Fusible linkage mechanism with limit switch.
Supply , erection, testing and commissioning of Aluminum powder coated collar dampers
Supply , erection, testing and commissioning of Aluminium powdercoated intake louvers with bird screen and insect screen for the fresh air intake.
Supply , erection, testing and commissioning of Aluminium powdercoated Contiounus /Districet Grills
Supply, Installation of Extruded Aluminium powder caoted removable core type 4 way diffusers for supply and return
Supply and fixing of Alluminium High flow Jet Nozzles (310 mm Dia ) with round collar damper
MS structural works including anchor bolts wherever necessary (Hilti / Fischer make) one coat of red oxide and two coats of approved color enamel paint to suspend AHU and for other related requirements
Providing Acoustic Insulation of AHU Rooms with 50mm thick Fibreglass rigid boards and covered with RP Tissue and Aluminium perforated sheet with 25mm wide GI strip as per specifications.
Supply, Installation, Testing and Commissioning Gypsum board boxing work on the side walls for distribution and return air. The boxing shall be with heavy Gauge Channel frame work along with Gypsum board and finished with 3 coat of Painting as per the room finish. as per the engineer in charge instructions
Supply, Installation, Testing and commissisioning of Factory Fabricated 25mm thick Sandwitch panel plenums as per the drawings at 750 FPM velocity as per site conditions ( 3 nos )
Condensing units - VRF/VRV System
Supply, installation, testing and commissioning of High COP VRV type condensing units (ODU) of minimum COP of Inverter Compressor to be as per the technical specifications. The outdoor unit shall have the multi-step of capacity control to meet load fluctuation and indoor unit individual control. Unit shall be equipped with an oil recovery system to ensure stable operation with long refrigerant piping. System suitable for Cooling with R-410A . Outdoor condensing unit comprising of Hermetic Scroll compressor, Heat Exchanger, propeller / axial fans, refrigerant Circuit, filter driers, sight glass, liquid receivers, accumulators, Safety Devices, Oil Recovery System with complete charge of gas and recommended oil. The outdoor unit shall be fully capable of working in conjunction with multiple indoor units of various capacities as per list of IDUs mentioned in the equipment summary. including Class room units including Refnut joints , outdoor units to be mounted on MS platform with suitable Vibration Isolation pads to avoid vibrations. All the supports and angle base frame structure to be duly black painted with synthetic epoxy paint. This includes required integration kits to inter conncet copper & communication with the AHUs mentioned above & VRF indoor units refnut joints included.
Supply, Installation, Testing and Commissioning of suction & liquid pipe Hard copper REFRIGERANT PIPING including required refnet Joints of 16swg various sizes with necessary supports, fittings, interconnecting the liquid and suction lines between the aircooled outdoor units and the indoor units. The piping shall be carried out of Hard drawn copper pipes of type 'K with soldered / brazed socket fittings. Isolating valves shall be provided to isolate each compressor, strainers, sight glass and any other component requiring proper operation and maintenance. Both the suction and liquid lines shall be insulated with 19mm thick closed cell insulation density 70-80Kg/m3 for above 25mm dia , 13mm thick for pipes below 25mm dia . The insulation finished with treated woven glass fiber reinforced covering for inside Piping and including making required holes in the wall and re finishing and water tight of holes after laying holes as per the specifications and approved drawings.
VRF Indoor units
Supply, Installation Tessting and commissioning of Decorative Hi- Wall Type Indoor Units : The units shall be wall mounted type, the housing of the unit shall have heavy duty powder coated plastic or galvanized steel. Unit shall include synthetic filter, fan section, coil section, with inbuilt Condensate drain pump kit, etc. The body shall be light in weight and shall be suitable for wall mounting. The fan shall be Aerodynamically designed Centrifugal type.The fan motor shall be PSC type. The fan shall be direct driven type. The cooling coil shall be of seamless copper tubes, and shall have continuous aluminium fins. The tubes shall be staggered in the direction of airflow. The fins shall be uniformly bonded to the tubes by mechanical expansion of the tubes.The coils shall be tested against leaks. Each unit shall have set of regulating and control valve, electronic expansion kits and other accessories. The computerized PID control shall be used to maintain a correct room temperature. Each unit to be provided with wire less remote controller LCD type. Power cable, socket and plug top from unit to MCB to be included & othe accessories like card less remote etc complete of the folloiwng ratings
a)1.5TR Capacity
b)2.0TR Capacity
Supply, testing & commisioning of Cassette type indoor units comprisisng with pre-filter,fan section with low noise fan multispeed motor, coil section with DX coil, outer cabinet, decorative panel for cassette units,drain water lift-up meachanism, insulation, pipe connections including card less remote , fresh air intake etc. of various capacities as per specifications and drawings.Including Lifting,Shifting, Positioning & Commissioning of the Units
a) 2 TR Capacity
b) 3 TR Capacity
c) 3.5 TR Capacity
Supply & Installation of control cum transmission wiring of size 2C x 1.5 Sqmm copper wire to be laid in heavy grade 25mm dia PVC conduit including all fixing & accessories as per the approved routing.
Supply & Installation of cabling of size 2C x 1 Sqmm copper wire to be laid in heavy grade 25mm diaPVC conduit including all fixing & accessories as per the approved routing.
Supply,Installation,Testing of Drain piping with PVC 6Kg/Cm2 the following sizes
a) 32mm dia
b) 25mm dia
Supply ,Installation , testing and commissioning of the following capacity Hi wall split unit Inverter type ( Indoor and out door units) equipped with Power Saving Imported Scroll Compressors, Suitable expansion device for optimal refrigerant feed, constructed with lightweight Galvanized sheet steel etc This unit is equipped with Microprocessor based controller having unique features to ensure that system operates at optimum efficiency levels etc. the price includes power and control cables, copper piping with insulation for indoor to outdoor, card less remote controller etc complete and aslo scope includes required supports & brackets for outdoor & indoor units installation
a) 1.5 TR Hi wall Unit
ELECTRICAL
MV Panels
a) Supply,Installation,testing,commissioning of 3 phase and neutral 415V 4wire free standing floor mounted MV panel made out of 14 SWG MS sheet and painting with epoxy powder coating the panel shall consist of suitable rating TPN aluminium busbar supported with DMC/SMC barriers and color coded with heat shinkable sleeves the metering shall be provided the pane shall have short circuit withstanding capacity of minimum 36KA and consist of switch gear as mentioned below the panel shall be got fabricated from manufactured with CPRI test certificate only The size of all panel mounting meters shall be 96mm*96mm The panels shall be mounted on 75mm U channels including supply and fixing the same Every MCCB shall be provided with with ON/OFF/TRIP,indicating lamps of LED type .The panel is to be installed in inddor.
a) HVAC CHILLER PANEL
Incoming:
500A,50KA 4P MCCB with Thermal Magnetic Based Release-1No
6A SP MCB control for RYB indication lamps
Busbars:
630A TPN Aluminium Busbar-1Sset
Metering:
OutGoings:
160A,25KA TPN MCCB with Thermal Magnetic Based Release- 4Nos
16A,10KA SP MCB with indication lamps -3 Nos
10A,40KA 3P MPCB With indication lamps-4 nos ( 3 Nos for Pumps, 1 no spares )
Surge Protection Device (SPD Class B) Type-1
2A 24V DC Power for SMPS –1Nos
b) AHU PANEL-1 &2
Incoming:
100A,35KA 4P MCCB with Thermal Magnetic Based Release-1No
6A SP MCB control for RYB indication lamps
Busbars:
125A TPN Aluminium Busbar-1Sset
Metering:
OutGoings:
80A,25KA TPN MCCB with Thermal Magnetic Based Release- 1Nos
40A,10KA FP MCB with indication lamps -2 Nos
16A,10KA SP MCB with indication lamps -3 Nos
2A,100KA 3P MPCB With indication lamps-2 nos ( 2 Nos for Pumps)
13A,100KA 3P MPCB With indication lamps-2 nos ( 1 Nos for AHUs & 1 Spare)
Surge Protection Device (SPD Class B) Type-1
2A 24V DC Power for SMPS –1Nos
c) AHU PANEL-3
Incoming:
160A,35KA 4P MCCB with Thermal Magnetic Based Release-1No
6A SP MCB control for RYB indication lamps
Busbars:
250A TPN Aluminium Busbar-1Sset
Metering:
OutGoings:
125A,25KA TPN MCCB with Thermal Magnetic Based Release- 1Nos
40A,10KA FP MCB with indication lamps -2 Nos
16A,10KA SP MCB-3 Nos
2A,100KA 3P MPCB With indication lamps-2 nos ( 2 Nos for Pumps)
13A,100KA 3P MPCB With indication lamps-32 nos ( 2 Nos for AHUs & 1Spare)
Surge Protection Device (SPD Class B) Type-1
2A 24V DC Power for SMPS –1Nos
d) AHU PANEL For RC building
Incoming:
125A,35KA 4P MCCB with Thermal Magnetic Based Release-1No
6A SP MCB control for RYB indication lamps
Busbars:
160A TPN Aluminium Busbar-1Sset
Metering:
OutGoings:
40A,10KA TPN MCCB with Thermal Magnetic Based Release- 1Nos
63A,10KA FP MCB with indication lamps -3 Nos
40A,10KA FP MCB with indication lamps -6 Nos
16A,10KA SP MCB with indication lamps -3 Nos
Surge Protection Device (SPD Class B) Type-1
2A 24V DC Power for SMPS –1Nos
e) Supply, installation , testing and commissioning of the following Outdoor type Isolators including all accessories etc complete
a) 63A ELCB
MV CABLES
Supply of following size 1.1KVgrade XLPE insulated armoured aluminium conductor underground cable, The cable shall conform to IS 7098 Part-1.
a) 3.5C X 50 SQMM PVC CU.Armoued Cable
b) 4C X 16 SQMM PVC CU.Armoued Cable
c) 4C X 10 SQMM PVC CU.Armoued Cable
d) 4C X 6 SQMM PVC CU.Armoued Cable
e) 4C X 4 SQMM PVC CU.Armoued Cable
f) 4C X 2.5 SQMM PVC CU.Armoued Cable
MV CABLES LAYING IN CABLE TRAY
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
a) Upto 35 sq. mm (clamped with 1mm thick saddle)
b) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
MV CABLES LAYING IN WALL
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.
a) Upto 35 sq. mm (clamped with 1mm thick saddle)
b) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
MV CABLE TERMINATIONS:
Provinding indoor ordinary end terminations for the cable secified above with compression type steel gland bi-meatallic lugs uisng crimping tool,insualtion tape identification tags etc including end termination and earthing of glands with 8SWG GI Wire.
a) 3.5C X 50 SQMM PVC CU.Armoued Cable
b) 4C X 16 SQMM PVC CU.Armoued Cable
c) 4C X 10 SQMM PVC CU.Armoued Cable
d) 4C X 6 SQMM PVC CU.Armoued Cable
e) 4C X 4 SQMM PVC CU.Armoued Cable
f) 4C X 2.5 SQMM PVC CU.Armoued Cable
CABLE TRAY
Supply,installation of following size of 2mm thick GI preforated type cable tray with couplers plates,elbows,bends,tees etc as required the scope also includes suitable cable tray supported arrangement on waills/cealing/trench with ms structural steel threaded rods anchor bolt and nuts where ever required as per the conditions
a )300mm wide X 50mm deep X 2mm thick
b)200mm wide X 50mm deep X 2mm thick
c) 100mm wide X 50mm deep X 2mm thick
EARTHING
a) Provinding G.I earth station,with with 40mm dia 2500mm long GI pipe including construction of brick pedastal prividing meshed funnel ci cover and other civil engineering works spreading a homogenous mixture of salt,charcoal around the pipe etc etc,completely as per IS3043 1987 or latest version.
b)Supply and laying of the following earth strips/conductors
c)Supply and fixing of 50 X 6mm GI flat
d)Supply and fixing of 25 X 3mm GI flat
e) Supply and fixing of 1C X 6SQMM PVC insulated flexible copper cable(Green)
SUBHEAD-XVIII : UPS WIRING
Supply and fixing of 2 Nos of 6/16A, 5Pin Socket outlet with 2Nos of switch of 16A rating including Modular G.I Box, Front Plate and also including all fixing accessories etc complete. ( For UPS Socket)
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required
a) 125 A, 16 KA,TPMCCB
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
a) 6 way (8 + 18), Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
a) 4 way (4 + 12), Double door
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing of 6A to 32A rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.
Single Pole
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
a)2 X 4 sq. mm + 1 X 4 sq. mm earth wire
b)4 X 10 sq. mm + 2 X 6 sq. mm earth wire
c)4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required including excavation in all types of soil.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets(Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
SUBHEAD-XIX : FLAMEPROOF FIXTURES
Supply, erection, testing and commissioning of the following Flame proof light fixtures including necessory fixing accessories
a) 100W Flame proof Well Glass LED Light Fixture with fixing accessories.
b) 2 X 20W , LED Flameproof Light Fixture with fixing accessories.
c) 1 x 40W, LED Flameproof Bulkhead Light Fixture with fixing accessories etc complete.
d)Supply, Installation, Testing and commissioning of 8 way Flame proof DB with one number 63A, 4pole MCB as incomer and 24Nos of 10A & 16A SPMCB as outgoing with fixing supports.
Cables for lighting fixtures
Supply, testing and commissioning of 1.1 KV grade PVC insulated armoured Copper Conductor cable as per specification.
a)3 Core X 4 Sqmm Cu
b)3 Core X 2.5 Sqmm Cu
CABLE END TERMINATIONS :
Supplying and providing flameproof end terminations for the following 1.1 kv grade armoured copper conductor cables with Copper lugs, double compressed brass cable glands, taping, crimping, glanding and armour earthing, etc.complete as required.
a)3 Core X 4 Sqmm
b)3 Core X 2.5 Sqmm
Flame proof sockets
a) Supply and fixing of factory made flame proof 32A, 1Ph , 3 Pin Plug and socket including fixing accessories.
b) Supply and fixing of factory made flame proof 63 A, 3Ph , 3 Pin Plug and socket including fixing accessories.
Flame proof sockets / SFU`s
a)Supply and fixing of 800 A Flame proof TPN SFU with Encloser including all fixing accessories and including HRC fuses..
b)Supply and fixing of 400 A Flame proof TPN SFU with Encloser including all fixing accessories and including HRC fuses..
c)Supply and fixing of 250 A Flame proof TPN SFU with Encloser including all fixing accessories and including HRC fuses..
d) Supply and fixing of 200 A Flame proof TPN SFU with Encloser including all fixing accessories and including HRC fuses..
e)Supply and fixing of 150 A Flame proof TPN SFU with Encloser including all fixing accessories and including HRC fuses..
`f)Supply and fixing of 100 A Flame proof TPN SFU with Encloser including all fixing accessories and including HRC fuses..
g) Supply and fixing of 63 A Flame proof TPN SFU with Encloser including all fixing accessories and including HRC fuses..
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor underground cable, in built up cable trench/ already laid RCChume pipe or on cable tray with all installation materials. . The cable shall conform to IS 7098/ PartII.
a) 4C X 16 Sq.mm
b)3.5C X 25 Sq.mm
c) 3.5C X 150 Sq.mm
d)3.5C X 185 Sq.mm
e)3.5C X 240 Sq.mm
f)3.5C X 300 Sq.mm
Supplying and making Flame proof end terminations end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
a) 4C X 16 Sq.mm
b)3.5C X 25 Sq.mm
c) 3.5C X 150 Sq.mm
d)3.5C X 185 Sq.mm
e)3.5C X 240 Sq.mm
f)3.5C X 300 Sq.mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
a) Upto 35 Sqmm
b) Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
c) Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Cable Trays
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc.as required.
a) 450 mm width X 50 mm depth X 2.0 mm thickness
b) 300 mm width X 50 mm depth X 1.6 mm thickness
SUBHEAD-XX : FIRE ALARM SYSTEM
Supply, erection, testing and commissioning of Intelligent Addressable Fire Alarm Control Panel (a minimum of 159 detectors/ 159 modules per loop )with Network Communication Module expandable to 1 loop, to monitor loop Devices located in all floor with dual stage alarm facilities,built in buzzer,built in NAC Circuits & RS 485 port on CPU board with optional net work software connectivity, fire/fault indicators, audio-visual signals, battery, battery charger, central processing unit,80 character display unit, fibre optic converter and networking card etc complete in all respects .
a) 1 - Loop Panel ( One Loop for Integration )
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches etc complete.
Supply, Installation, Testing and commissioning of Online UPS of 1 KVA capacity with built-in SMF Batteries (12V 7Ah X 3nos) for battery back up and regulated AC supply to the FAS.
Supply, Installation, Testing and Commissioning of UV - IR Flame proof Sensors with a range of 4mtr -15mtr and view angle of 90 deg with Addressable monitor module which shall be addressed by rotary Switch setting.
COMIBINATION/MULTI SENSOR DETECTORS (Photoelectric + Heat Sensing)
Supply,fixing,testing and commissioning of Addressable anlogue type multi sensor detectors (Photo electric + Heat sensing) with dual chamber, solid state design,Rotatable DIP Switch Setting indicating lamp, mounting base etc.
Supply, installation, testing & commissioning of response indicator.
MANUAL CALL POINTS:
Supply, erection, testing and commissioning of Addressable analogue type manual call point for indoor installtion.
Supply, Installation, Testing and Commissioning of Flame proof Manual call point with Addressable Monitor Module .
Supply,Installation,Testing and commissining of Addressable analogue type manual call point stations weather proof with 1500 mm Length ISMC 100 standing Post.
FAULT ISOLATION MODULE:
Supply ,fixing ,testing and commissioning of Fault Isolation module.
Supply installation, testing & commissioning of addressable fire control module complete as required.
Supply, Installation, Testing and Commissioning of Addressable Relay Module to control AHU Controller Control Signals.
Supply installation, testing & commissioning of addressable fire Loop Sounder module complete as required.
CABLE:
Supply, laying , testing and commissioning of 1100 V grade FIRE RESITANCE LOW SMOKE PVC insulated copper conductor control cables as per specification.
a) Armoured Twisted pair 2C x 1.5 sq. mm. shielded FRLS insulated copper conductor cable to be laid on cable tray /to be clamped to wall including supply and fixing of clamps etc complete.
b)Armoured Twisted pair 2C x 1.5 sq. mm. shielded FRLS insulated copper conductor cable to be laid in cable trench including excavation and backfilling.
c) Unarmored Twisted pair 2C x 1.5 sq. mm. shielded FRLS insulated copper conductor cable to be laid on cable tray /to be clamped to wall including supply and fixing of clamps etc complete.
Supply and laying of 25mm dia, heavy gauge PVC . conduit concealed in wall/ ceiling/ floor including all accessories such as junction boxes, conduit bends, etc., complete as required for Telephone etc.,
3 core x 2.5 Sq.mm armoured sheilded twisted pair copper conductor cable on cable tray/on wall including clamping etc complete and including cable end termination with double compression weather proof cable glands and copper lugs.
Supply and Installtion of 12 Way Elmex terminal powder Coated junction Box including all terminations and Necessary Glands
Supply ,Installation,Testing and commissioning of Weather proof siren to be operated on Single Phase 230 V, 50 Hz ,A.C.Supply with a range of 2/3 km distance including fixing clamps and accessories.complete.
Supply, laying of 50mm dia, class-B GI pipe including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.
Supply and laying of of 6 core 9/125 micro meters armored single mode optical fiber cable with suitable dia HDPE pipe (1300nm wave length) including splicing & terminations and laid in ground at 750 mm below ground including excavation and sand, brick protection and refilling of earth and cable route markers at every 50 meters intervals. 6C SM ARM-OFC - 6 C Armoured Single Mode Optical Fiber Cable networking card and fibre optic converter etc., complete.
Supply, Installation of following Fire extinguishers & accessories:
a)CO2 4.5 kg capacity trolley mounted
b) CO2 22.5 kg capacity trolley mounted
c) DCP 5 kg capacity (potassium bi-carbonate Uria reaction)
d) Water buckets with stand
e) Sand buckets with stand
f)Showels
g)Fire Beater
h) Fire gong/ hand siren
i) Ceiling Hook
SUBHEAD-XXI : WATER COOLERS
Supply and flxing of 40 (cooling)/ 80 (storage) ltrs water cooler with water purifier (RO system) and voltage stabiliser etc. complete.
SUBHEAD-XXII : FIRE HYDRANT SYSTEM
Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :
Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration pads.
a) 2850 lpm at 88 m Head
Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)
Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft,mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.
a) 2850 lpm at 88 m Head
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.
a) 180 lpm at 88 m Head
Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification.
Incomings
400A, 50kA 4 Pole MCCB, Ics=100% Icu Rating
LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps
Set of Copper Bus Bar 500Amps
Outgoings
Main Fire Pumps
Jockey Pump
Diesel Engine Control
Control for diesel engine comprising -
Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons,
start/stop in manual mode
Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication
20 A DC Ammeter
All standard relays and accessories for automatic operation of diesel engine System Controller
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
a) 25 mm dia
b)32 mm dia
c)40 mm dia
d)50 mm dia
e)65 mm dia
f)80 mm dia
g)100 mm dia
h)150 mm dia
i)200 mm dia (wall thickness 6.3 mm)
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :
a) Single headed Gunmetal
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
a)40 mm dia
b)50mm dia
c)65 mm dia
d)80 mm dia
e)100 mm dia
f)150 mm dia
g)200 mm dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :
a)40 mm dia
b)50mm dia
c)65 mm dia
d)80 mm dia
e)100 mm dia
f)150 mm dia
g)200 mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts,washers etc.as required :
a)40 mm dia
b)50mm dia
c)65 mm dia
d)80 mm dia
e)100 mm dia
f)125 mm dia
g)150 mm dia
h)200mm dia
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia
holes with stainless steel flange.
a)80 mm dia
b)100mm dia
c)150mm dia
d)200mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :
a) Gun Metal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :
a) Gun metal
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
a) 4 way - 150 mm dia M.S. Pipe
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.
a) 150mm dia
Providing and laying Double Flanged (Screwed/ Welded) Centrifugally(Spun) Ductile Iron Pipes of Class K - 9 conforming to IS : 8329 :
a) 150mm dia
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :
a) 300 mm dia. R.C.C. pipe
SUBHEAD-XXIII : EXTERNAL ELECRIFICATION
11 KV HT SWITCHGEAR
Supply,Installation,Testing and commissioning of the following indoor floor mounted 11 kv Rated VCB Panel in Metal Enclosure fabricated out of 14 swg sheet steel to be operated on 11KV,Three phase,50HZ A.C Power supply .The panel is to be compartmentalised with individual compartments for Bus bars, Cable and CTs and Instrument and relay control Panel. The VCB shall be horizontal draw out single break as per IS 13118.The short circuit fault level of the system shall be 350MVA.
a) 11 kv VCB panel with one no of 800 A vcb -Indoor at Tapping Point.
11 KV H.T Switch Gear Panel (INDOOR TYPE) With 1 No. OF 800 A Vaccum Circuir breaker as Outgoing.
CONSTRUCTION - The Switch Gear Panel shall be compartmentalised Designed with cubicles fabricated out of High Quality Sheet Steel . The panels shall be designed having the Following Segregations separately.
a) Busbar compartment
b) Cable and CT compartment
c)) Instrument and Relay Compartment
The clearances between phase to phase and phase to earth shall be provided in accordance with the relevant standards. The bus bars shall be supported by bus support insulators placed at regular intervals.
The panels shall be powder coated with epoxy base paint to give an aesthetically pleasing appearance. The paint shade shall be as per the requirement.
SAFETY FEATURES:
a) Mechanical Interlock and earth switch for out goings
b) Door interlock in service position.
OUTGOING VCB PANEL
CURRENT TRANSFORMER: (3 No’s) Cast Resin
Ratio 200-100 - 5/5 A , Core 1: 15 VA, CI – 0.2 for Metering and 5P10 for protection.
METERING: ( 1set)
Digital Multi function Meter for KW,KWH,KVA, KVAR , COS PHI Parameters reading.
INDICATION LAMPS:
1) TCH, Battery failure , Spring charge, discharge, ON, OFF and Trip Indication Lamps, Phase indication Lamps for RYB. - (1 set)
CONTROL SWITCHES/PUSH BUTTON
Bus Bar with 800 Amps Copper - (1 set)
COMMON FOR SWITCHGEAR:
Heater ON and OFF Switch with Space heater, single Phase switch socket and cubicle lamp for panel illumination, MCB's for AC/DC Control - (1 set)
MS sheet enclosure suitable for Indoor installation with outgoing cable entry. - (1 set)
Relays Incomer ; Undervoltage relays 2 nos,IDMT relay ,TCH and Master trip relay and also with 12 window annunciator
The scope includes the extension of busbars in the existing panel and coupling of these busbars to the new switchgear vcb panel including earth connection.
Power Pack - 1 No with necessary Interconnections.
b)11 kv VCB panel with one no of 800 A vcb - outdoor at Sub Station.
11 KV H.T Switch Gear Panel (INDOOR TYPE) With 1 No. OF 800 A Vaccum Circuir breakers as Incomer and Outgoing 800 A Vaccum Circuit Breaker.
CONSTRUCTION - The Switch Gear Panel shall be compartmentalised Designed with cubicles fabricated out of High Quality Sheet Steel . The panels shall be designed having the Following Segregations separately.
a) Busbar compartment
b) Cable and CT compartment
c)) Instrument and Relay Compartment
The clearances between phase to phase and phase to earth shall be provided in accordance with the relevant standards. The bus bars shall be supported by bus support insulators placed at regular intervals.
The panels shall be powder coated with epoxy base paint to give an aesthetically pleasing appearance. The paint shade shall be as per the requirement.
SAFETY FEATURES:
a) Mechanical Interlock and earth switch for Incomer and out goings
b) Door interlock in service position.
INCOMING/ OUTGOING VCB PANEL
CURRENT TRANSFORMER: (3 No’s) Cast Resin
Ratio 200-100 - 5/5 A - 5 A, Core 1: 15 VA, CI – 0.2 for Metering and 5P10 for protection.
POTENTIAL TRANSFORMER : (3 No’s) Cast Resin
Ratio 11000 V/ rt 3 / 110 v / rt 3 , 100 VA, CI – 0.2 for Metering and 3 P for Protection and also with 2 numbers of Under Volage relays.
METERING: ( 1set)
Digital Multi function Meter for KW,KWH,KVA, KVAR , COS PHI Parameters reading.
INDICATION LAMPS:
1) TCH, Battery failure , Spring charge, discharge, ON, OFF and Trip Indication Lamps, Phase indication Lamps for RYB. - (1 set)
CONTROL SWITCHES/PUSH BUTTON
Bus Bar with 800 Amps Cooper - (1 set)
COMMON FOR SWITCHGEAR:
Heater ON and OFF Switch with Space heater, single Phase switch socket and cubicle lamp for panel illumination, MCB's for AC/DC Control - (1 set)
MS sheet enclosure suitable for Indoor installation with incoming and outgoing cable entry. - (1 set)
Relays Incomer ; Undervoltage relays 2 nos,IDMT relay ,TCH and Master trip relay and also with 12 window annunciator
Power Pack - 1 No with necessary Interconnections.
Supply and commissioning of 11 kv earthed HT cable of size 3 c x 185 sqmm XLPE insulated armoured alluminium conductor cable as per IS 7098 - Part 2 - 1983
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
a) Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
a) Above 120 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size on cable tray as required.
a) Above 120 sq. mm and upto 400 sq. mm
Supply,Installation,Testing and commissioning of 11 KV earthed heat shrinkable end termination kit of 11 KV earthed XLPE insulated armoured alluminium conductor HT Cable of size 3 c x 185 sqmm
Supply and Installation ,Commissioning of HT Straight through Joint Kit for 3 C x 185 Sqmm Earthed XLPE insulated armoured alluminium conductor cable.
Supply, Installation, Testing and commissioning of 1500 KVA, 11kv / 433 v, 3 PHASE, 50 Hz, Dyn 11 OUTDOOR ONAN Transformer with on load tap changer, RTCC panel, AVR and HT Side marshalling box for termination of 11 kv grade , 3 c x 240 sqmm XLPE insulated alluminium conductor screeened cable and LT side provision for connecting sandwich type of Alluminium bus trunking system of 1600 A capacity as per IS 1180 ( Level 3 ) with radiators etc.
LT SANDWICH TYPE BUS DUCT
Supply, Installation, Testing and commissioning of 415 V, 50 Hz, A.C, 1600 A, Three phase and neutral Sandwhich type Alluminium bus bars Bus trunking system with necessary fixing Clamps and Jointing accessories including all required horizontal and vertical bends, tees for outdoor Application Ip -54 ( Transformer feeder Incomer ) .As p-er IS ; 8623 Part 1 & 2
M.V.PANELS
MAIN LT PANEL - 1 - Indoor
Incomer 1 : 1 No of 2500 A, 4P. EDO ACB, 70KA, shall be supplied with S/C,E/F,O/C AND INSTANTANEOUS TRIP RELAY UNIS WITH TIME DELAY SETTINGS.
2A, control fuse - 3 Nos.
RYB indicating lamps - 1 set
2500/5A, CL-1, 15VA CT's with resin cast- 3 nos.
A Single CT with ratio of 2500 / 5 A , 15 VA, 5 P 10 ,CT for feeding APFC relay of APFC panel.
Incomer 2 : 1 No of 1000 A, 4P. EDO ACB, 70KA, shall be supplied with S/C,E/F,O/C AND INSTANTANEOUS TRIP RELAY UNIS WITH TIME DELAY SETTINGS.
2A, control fuse - 3 Nos.
RYB indicating lamps - 1 set
1000/5A, CL-1, 15VA CT's with resin cast- 3 nos.
Bus Coupler : 1 No of 2500 A, 4P. EDO ACB,70KA, shall be supplied with S/C,E/F,O/C AND INSTANTANEOUS TRIP RELAY UNIS WITH TIME DELAY SETTINGS.
The Panel shall be supplied with Electrical and Mechanical Interlocking for both Incomers and Bus coupler.
Outgoing
1000A, 3P, 50KA, ACB, - = 2 No
630A, 3P, 50KA, ACB, - = 3 No
250A, 3P, 35KA, MCCB, - = 4No
160A, 3P, 35KA, MCCB, - = 1No
63A, 3P, 16KA, MCCB, - = 2No
63 A, 3P, 16KA, MCCB, - = 1 No and also with 20 A TPMCB as outgoings 4 Nos with timer circuit for controlling of street lights and the timer should be with required 24 hors clock settings.
Bus Bars : 2500A, 3Ph, 4 wire TPN, 50Hz, aluminium bus bars,70ka
Metering Instruments ; Load Manager in the Incomer and ACB/ MCCB on , off , Trip Indication Lamps and with Breaker Status indication Lamps and also with Phase indication Lamps.
Earth Bus; To be provided at the bottom of the Panel of copper
Out door Feeder Pillar Panel - 1
1 No of 160 A, 4P. MCCB, 35KA, shall be supplied with S/C,E/F,O/C Protection.
2A, control fuse - 3 Nos.
RYB indicating lamps - 1 set
160/5A, CL-1, 15VA CT's with resin cast- 3 nos.
Outgoing
63A, 3P, 16KA, MCCB, - = 5No
Bus Bars : 160A, 3Ph, 4 wire TPN, 50Hz, aluminium bus bars
Metering Instruments ; Multi Function Meter in the Incomer and MCCB on , off , Trip Indication Lamps and with Breaker Status indication Lamps and also with Phase indication Lamps.
Earth Bus; To be provided at the bottom of the Panel of copper
APFC PANEL 630 KVAR - Indoor
Supply,Installation,Testing and Commissioning of APFC PANEL with Automatic power factor control relay and with 10 nos of 50 kvar capacitor banks and 25 kvar capacitor banks 5 nos and 4 Nos 10KVAR with the following incoming and out goings.. The Panel is to be installed in Indoor. The panel is to be supplied with necessary power and control wiring required for the automatic operation of Power factor control.
INCOMER
1000 A, 4 P , ACB with O/c, S/c,E/f Protection Microprocessore Relay Unit
2A, control fuse - 3 Nos.
RYB indicating lamps - 1 set
1000/5A, CL-1, 15VA CT's with resin cast- 3 nos.
Outgoing
125 A, 3P, SDF , - 8 No
63 A, 3P, SDF , - 8 No
Bus Bars : 1000A, 3Ph, TPN, 50Hz, aluminium bus bars
Metering Instruments ; Multi Function Meter in the Incomer and SDF on , off , TRIP Indication Lamps and with Breaker Status indication Lamps and also with Phase indication Lamps
Earth Bus; To be provided at the bottom of the Panel of copper
The panel is to be supplied with Required capacity Capacitor Banks as per BOQ quantity and also with required capacity over load relays,contactors ,Switch disconnecting fuses and also with APFC relay control wiring for manual and Auto operation.The Panel Shall be provided with 16 Stage APFC Relay and also including 2 nos Spare Compartments in the APFC panel.
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor underground cable. The cable shall conform to IS 7098/ Part-II.
a) 3.5C X400 Sq.mm
b) 3.5C X300 Sq.mm
c) 3.5C X240 Sq.mm
d) 3.5 C X185 Sq.mm
e) 3.5 C X150Sq.mm
f) 3.5 C X120Sq.mm
g) 3.5 C X 70 Sqmm
h) 4 C X 25 Sqmm
i) 4 C X 16 Sqmm
j) Copper armoured control cables
k)4C X 2.5 Sq.mm
l) 7C X 2.5 Sq.mm
m)19C X 2.5 Sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
a) upto 35 sq. mm
b) Above 35 sq. mm and upto 95 sq. mm
c) Above 95 sq. mm and upto 185 sq. mm
d)Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
a) upto 35 sq. mm
b) Above 35 sq. mm and upto 95 sq. mm
c) Above 95 sq. mm and upto 185 sq. mm
d)Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
a) upto 35 sq. mm
b) Above 35 sq. mm and upto 95 sq. mm
c) Above 95 sq. mm and upto 185 sq. mm
d) Above 185 sq. mm and upto 400 sq. mm
Providing Indoor ordinary end terminations for the foollwing 1.1 KV grade XLPE insulated armoured alluminium conductor cables with compression type steel gland, Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland with 8SWG GI Wire.
a) 3.5C X400 Sq.mm
a) 3.5C X300 Sq.mm
b) 3.5C X240 Sq.mm
c) 3.5C X185 Sq.mm
d) 3.5C X150Sq.mm
e) 3.5 C X120Sq.mm
f) 3.5 C X 70 Sqmm
g) 4 C X 50 Sqmm
g) 4 C X 25 Sqmm
g) 4 C X 16 Sqmm
End terminations of Copper armoured control cables including supply and fixing of crimping type copper lugs.
i) 4C X 2.5 Sq.mm
ii) 7C X 2.5 Sq.mm
iii) 19C X 2.5 Sq.mm
EARTHING
Providing and fixing of maintenance free earthing which consists of 40 mm Dia, 3 mtr length (as per Equipment Supplier) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Bentonite compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.
Supply and fixing of following earth strips/ conductors. The scope incudes supply and fixing of copper lugs wherever found necessary, brass bolts, nuts and washers for fixing arrangement etc., (from earth station to main panel).
a) 50 x 5 MM G.I. Flat
b) 25 x 6 MM GI Flat
c) 50 x 6 MM Copper Flat
d) 6SWG G.I.Wire
Cable Trays
Supply and fixing of following size GI Perforated type cable tray made out of 2mm thick sheet including MS supports for fixing the tray, anchor fasteners etc complete as required.Including with GI covers.
a) 600mm wide
b)300mm wide
CHAIN LINK FENCING
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia 4 mm
Supplying at site Angle iron post & strut of required size including bottom to be split and bent at right angle in opposite direction for 10 cm length and drilling holes upto 10 mm dia. etc. complete.
Supplying and stacking at site. 90 mm to 45 mm size stone aggregate
SAFETY ITEMS
Supply,Installation,Testing and commissioning of the Follwing Safety items as per standrads and specification
a)Fire Extinguishers -4.5 KG CAPACITY CO 2 Confirming to IS 2878 fitted with discharge bend pipe and horn
b) Rubber Mats 415 V , 2 Mtr x 1 Mtr
c) Shock treatment Chart with frame and glass
d) First Aid Box
e) Sand Bucket with stand with 3 Nos of buckets and also with canaopy.
f) 415 V Danger Boards
g) 11 kv Danger Boards
h)Single Line Diagram with frame and glass.
SUBHEAD-XXIV : AREA LIGHTING
Supply and erection of steel stepped and swaged tubular poles of 9 mtr long (410 SP25) (1.5 mtr below ground) with base plate earthing studs 1.5 mtr out reach single /Double arm , FRP terminal Box 2 Nos of 40 mm Dia Class B G.I Pipe ,0.5 mtr Long for incoming and outgoing cables including excavation in all types of soil ,PCC 1:2:4 ,PCC Pedestal with painting with black bitumen paint inside the coping for embedded portion and two coats of Zinc chromite primer and two coats of Alluminium paint externally for length above the ground.The pole shall be with FRP junction box consisting of 10A MCB.The wiring from Junction box to Light fixture shall be carried out with 3 Core 2.5 Sqmm Copper conductor flexible cable.
The Street Light Pole shall be fixed with 90W LED street Light fixture including supply of controlgear / driver and lamp(Make : Cat No.LR02-102-XXX-57-G2,WIPRO MAKE / CAT NO - Greenline V2 (BRP410) Philips make.)
Supply and erection of 65 mm Dia, Class B GI Pipe of 3 mtr. long with base plate, earthing studs, 3 phase and neutral loop-in and loop-out box as per specifications, 2nos 50mm dia,1.5mtr. long GI bent pipes for incoming and outgoing cables, including excavation , 1 :2 : 4 PCC Pedestal etc complete. The pole shall be with Junction box consisting of MCB. The Junction box shall be of weather proof. The wiring from Junction box to Light fixture shall be carried out with 3core 2.5sq.mm flexible copper conductor cable. The Pole shall be fixed with weather proof 72W LED ( Philips Cat No :BRP046 LED 30 CW MR S1 PSU GR ) Light fixture including supply of driver and fixing clamps etc complete.
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor underground cable. The cable shall conform to IS 7098/ Part-II.
a) 4Core 10sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required
a) Upto 35 Sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
a) Upto 35 Sqmm
Providing End terminations for the following size of 1.1 KV grade XLPE insulated armoured alluminium conductor cable with compression type steel gland, alluminum lugs using crimping tool, Insulation tape, Identification tags etc.,complete
a) 4Core 10 sq.mm
Providing Spiral coil earthing with 8 SWG GI wire including spreading of salt and charcoal as per IS 3043/87 with latest amendments.
Supply and laying of NP2 class hume pipes including necessary earth work excavation in all types of soil / rock, PCC bed concrete and encasing etc., complete all as specified of following sizes.
a) 150mm dia.
b) 300mm dia.
SUBHEAD-XXV : EXTERNAL WATER SUPPLY :
Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.
a) 40 mm dia nominal bore
b)50 mm dia nominal bore
c) 80 mm dia nominal bore
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :
Making connection of G.I distribution branch with G.I main of folloeing size by providing and fixing tee, inclding cutting and threading the pipe etc. complete:
a) 25 to 40 mm nominal bore
b) 50 to 80 mm nominal bore
Providing and fixing gun metal non- return valve of approved quality (screwed end) :
a)25 mm nominal bore
b) 40 mm nominal bore
c) 50 mm nominal bore
Supply,erection, testing and commissiong of C.I Air release valves flanged end type with bolts,nuts and rubber insertions etc., complete and of following sizes:
a)25 mm nominal bore
b) 50 mm nominal bore
Supply and Fixing of cast iron pipe line Route Marker for water supply Network system
SUBHEAD-XXVI : SEWAGE DISPOSAL :
Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m in All kinds of soils.
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.
PVC SWR PIPES
Providing, laying and jointing PVC/ SWR Pipes conform to IS:13592-1992 of Type-B on sand cushion at bottom and around the pipw and testing of joints etc. complete :
a) 100 mm dia PVC/SWR Single Socket
b) 150 mm dia PVC/SWR Single Socket
Providing and fixing square-mouth PVC gully trap conform to IS:13592-1992 complete with brick masonry chamber around as per standard design :
a) 100x100 mm PVC Gully trap with Sewer bricks conforming to IS : 13592-1992.
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :
Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), With Sewer bricks conforming to IS : 4885.
Extra for depth for manholes :
Size 90x80 cm, With Sewer bricks conforming to IS : 4885
Providing M.S. foot rests including fixing in manholes with 20x20x10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) as per standard design, With 20x20 mm square bar.
Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design, With common burnt clay F.P.S. (non modular) bricks of class designation 3.5.
Supply and positioning of ready made polyethylene septic tank of size 2.3M long 1.3M dia 16mm shell thickness with 2/3 chambers and 2Nos manholes of size 550mm dia and 100mm/160mm dia inlet outlet pipe and airvent pipe 50mm dia of make United Septic tank Design Reg.No 173352 Type-4
SUBHEAD-XXVII : ROADS/HARDSTANDING & DRAINS :
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.
Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller, or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up, in embankments for roads, flood banks, marginal banks, and guide banks etc., lead upto 50 m and lift upto 1.5 m in all kinds of soils.
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge.
Providing and laying Bituminous concrete using crushed stone aggregates of specified grading, premixed with bituminous binder and filler, transporting the hot mix to work site by tippers, laying with paver finisher equiped with electronic sensor to the required grade, level and alignment and rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction and density as per specification, complete and as per directions of Engineer-in-Charge.
40/50 mm compacted thickness with bitumen of grade VG-30 @ 5.5% (percentage by weight of total mix) and lime filler @ 3% (percentage by weight of Aggregate) prepared in Batch Type Hot Mix Plant of 100-120 TPH capacity.
Providing and applying tack coat using bitumen emulsion conforming to IS:8887, using emulsion pressure distributer including preparing the surface & cleaning with mechanical broom.With rapid setting bitumen emulsion. On W.B.M / W.M.M. @ 0.4kg/Sqm.
Providing and laying seal coat of premixed fine aggregate ( passing 2.36 mm and retained on 180 micron sieve) with bitumen using 128 kg of bitumen of grade VG - 10 bitumen per cum of fine aggregate and 0.60 cum of fine aggregate per 100 sqm of road surface, including rolling and finishing with road roller all complete.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
Dry stone pitching 22.5 cm thick laid in courses and required profile with hammer dressed stones having no side less than 15 cm, with minimum depth of 20 cm including preparing the bedding surface etc. all complete.
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc., complete.
a) 150 mm dia. R.C.C. pipe
b) 300 mm dia. R.C.C. pipe
c) 450 mm dia. R.C.C. pipe
SUBHEAD-XXVIII : DG SET
Supply,Installation,Testing and commissioning of 625 KVA ,415 Volts at 1500 RPM,0.8 lagging Power factorat 415 V suitable for 50Hz ,3 Phase system and for 0.85 Load factor and consisting the followings
Diesel Engine 4 stroke water cooled electric start of suitable BHP at 1500 rpm suitable for above alternator output at 40Deg centigrade ,50% RH & at 1000 m MSLand confirming to BS 5514 , BS 649 , IS 10000 capable of taking 10% overload ing for one hour after 12 hours of continuous operation.
The DG Set shall be supplied with Alternator,Engine Control Panel,Base Frame, 990 Litres Fuel tank,Exhaust system,Statrting system including Batteries,Exhaust system, Weather proof Accoustic Enclosure , anti vibration pads etc complete.
The DG Set shall be supplied with AMF relay and also necessary control wiring.
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor underground cable. The cable shall conform to IS 7098/ Part-II.
a) 3.5C X 240 Sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
a) Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
a) Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
a) Above 185 sq. mm and upto 400 sq. mm
Providing Indoor ordinary end terminations for the foollwing 1.1 KV grade XLPE insulated armoured alluminium conductor cables with compression type steel gland, Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland with 8SWG GI Wire.
a) 3.5C X 240 Sq.mm
EARTHING
Providing and fixing of maintenance free earthing which consists of 40 mm Dia , 3 mtr length (as per Equipment Supplier ) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Bentonite compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.
Providing and fixing of maintenance free earthing which consists of 65 mm Dia , 3 mtr length (as per Equipment Supplier ) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Bentonite compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.
Supply and laying under ground/above ground of following size strips including all necessary interconnections between earth station and equipments including earth excavation, back filling, intermediate supports for strips as applicable and directed by engineer in charge.
a)50 x 5 MM G.I. Flat
b)50 x 6 MM Copper Flat
SUBHEAD-XXIX : ARBORICULTURE
TREE PLANTATION
a) Digging pits in all type of soils and refilling the same with the good earth (excavated / imported) & manure (organic manure/cow dung/sludge) in the ratio of 3:1 (03 part of stacked volume of manure). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth &8% stacked volume of manure. Each pit to be mixed with antitermite chemical / granules, Thimet 10G @100-200 am/pit
(I) AVENUE / FLOWERING TREES / Palms
a) 1mts x 1mts x 1mts (L X W x D )
b) Each pit to be added with 100gms of Thimet 10 g granule, to control termite attack. (Repeat the treatment after 06 months, if termite persists). Flooding the pit basin with water, dressing including removal of rubbish & surplus earth, if any, with all lead & lifts
c)Supply and plantation of approved varieties of healthy, disease free, stout stem & well developed root system tree sapling of, 5'-6' height, with a clear minimum height of 4'-5' from basin / ground level, after plantation. Staking the tree sapling upto 3/4 height with appropriate strength of bamboo stick. Lower 1 feet of stake portion should be treated with antitermite chemical
i) Phonix Palm
ii) Red Palm
iii) Golden Palm
iv) Fox Tail Palm
v) Areca Palm
d) Maintenance of tree sapling, after plantation for 30 days or more as minimum guarantee period, for well establishment of tree sapling. Stacking to be continued till tree sapling attains the stem strength. Replacement of saplings casualties immediately
LAWM PLANTATION
a)Preparation of ground by trenching in all type of soils upto a depth of 30cm including removal & stacking of serviceable material than disposing the surplus soil with all lead & lifts, by spreading and leveling neatly. Making up the trenched area well leveled by filling with additionally supplied earth (if needed)
b)Now rough dressing of trenched ground including breaking clods & flooding with water
c)After 10-15 days removal of weeds / unwanted grass (motha etc) with roots & disposal of uprooted material, stone rubbish etc., with all lead & lifts
d)Then fine dressing of ground. Spreading and mixing with the good earth (excavated / imported) & manure (organic manure / cow dung / sludge) in the ratio of 8:1 (08 part of stacked volume of good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth & 8% stacked volume of manure. The area to be mixed with antitermite chemical / granules, Thimet 10G @ 100-200gm / sqmts. If termite persists repeat the treatment after 06 months by surface spreading the chemical
e) Supply of grass and planting by dibbling the area including watering & maintenance of lawn for 30 days or more till grass forms a thick lawn cushion free from weeds
i) With Bermunda grass (15cm x 15cm apart)
ii) Carpet of grass turfing
iii) Supply & turfing of artificial lawn
f)After ward maintenance of lawn area, green & weed free for 01 year with standard specification
SHRUB PLANTATION (SOLO)
Digging pits in all type of soils and refilling the same the good earth (excavated / imported) & manure (organic manure / cow dung / sludge) in the ratio of 5:1 (05 part of stacked volume of manure). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth & 8% stacked volume of manure. Each pit to be mixed with antitermite chemical / granules thimet 10G @50-100gms / pit
i) Pit size 0.60mts x 0.60mts (Dia x Depth)
ii) Pit size 0.45 dia x 0.60mts Depth
b)Supply & plantation of shrub and / or rose sapling to pit, appropriate stacking & initial maintenance for 30 days. Replacement of sapling casualties immediately.
c) Afterward 01 year maintenance as per standard specification
SHRUBBERY PLANTATION - (SHRUBS IN GROUPS)
a) Digging beds in all type of soils and refilling the same with the good earth (excavated / imported) mixed with antitermite chemical / granules @100gm/sqmts) & manure (organic manure / cow dung / sludge) in the ratio of 5:1 by volume (05 part of staked volume of good earth & 1 part of stacked volume of manure). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth &8% stacked volume of manure
i) L X W X 0.60 mts depth
b)For roses, rose mixture @500gms / sq mts to be used additionally, before plantation
c)Termite treatment - Thimet 10G granules @100 gms / Sqmts
d) Supply & plantation of shrub sapling to pit, appropriate stacking & initial maintenance
e)Afterward 01 year maintenance as per standard specification
HEDGE PLANTATION
a)Digging trenches of approved / desired size of L X W (45-50cms) X D (30-60cm) in all type of soil. Refilling the trenches with good earth (excavated / imported) mixed with manure (cowdung / sludge / dump) in the ration of 5:1 (05 part of good earth and 01 part of manure by stacked volume). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth &8% stacked volume of manure. Fore Termite treatment add Thimet 10G granules @ 100gms / running mts. Flooding the trench with water and than rough & fine dressing of trenched area including removal of undesirable weeds & vegetation
b)Supply & plantation of approved varieties of hedge plant saplings. It should be well grown, fully established & disease free. Sapling height & density as follows
Hedge with sapling height -0.45 mts to 0.60mts (After Plantation)
Density - @07 Nos plants / running meters (staggered condition)
c)Maintenance the hedge by regular watering, trimming & pruning etc for 30 days initially. Replacement of sapling casualties immediately
d)Afterward maintenance of hedge length for 01 (one) year as per standard maintenance specification
GROUND COVER
a) Digging of ground cover marked area upto a depth of 30 cms in all type of soils. Refilling the same with (excavated / supplied) good earth mixed with manure (organic / cow dung / sludge) in the ration of 8:1 (08 part of good earth *01 part of manure by stacked volume). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth & 8% stacked volume of manure. For Termite treatment add Thimet 10G granules @100 gms/Sq mts. Flooding with water the entire area. Rough & fine dressing of the ground cover bed area and removal of weeds & unwanted vegetation & its disposal
b)Supply and plantation of approved / desired ground cover plant varieties, well established, fully grown, disease free and good foliage. Plantation density should be @36 ground cover plants / square metre, or less as desired or decided by site incharge. Maintenance of all the ground cover area for 30 days till the plants establish well.
c)Regular maintenance afterward for 01 year as per standard specification
FLOWER BED PREPARATION
Digging of FLOWER BED marked area upto a depth of 30 cms (Canna Beds - 60cms depth) in all type of soils. Refilling the same with (excavated / supplied) good earth mixed with manure (organic / cowdung/ sludge) in the ration of 5:1 (05 part of good earth & 01 part of manure) . Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% by stacked volume of stacked volume of good earth & 8% stacked volume of manure. For Termite treatment add Thimet 10G granules @100gms / sq mts. Flooding the entire with water. Rough & fine dressing the flower bed area and removal of weeds & unwanted vegetation & its disposal with all lead and lifts
a) SEASONAL FLOWERING BED SIZE FORMAL STYLE - Lx1.0mts width, INFORMAL STYLE - Any style as desired
b)Supply & plantation of seasonal flowers sapling @36 seedlings / sq mts (minimum three times in a year)
BUL BOUS / CUTTINGS - FLOWERING - Dahalia Plants @16 plants / Sqm) Winter
c)Maintenance of flower beds regularly upto 1 year as per standard specifications. Replacement of casualty immediately
MOUND
Preparation of mounds of various size and shape by available excavated / supplied earth in a layers not exceeding 20cm in depth, breaking clods, watering of each layer, dressing etc with all lead & lifts complete as per direction of Officer in charge. Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth and 8% stacked volume of manure
BRICK EDGING
Edging with bricks (Class I) laid in PCC (1:2:4) length wise, including required excavation, refilling, consolidating withhand packing and spreading surplus earth neatly within all lead and lifts
Brick Paving : Supply and Paving of wire cut bricks on sand bed
Terracotta Pot : Terracotta Pots of height 4' & width 1m made with 8mm rod chicken mesh with cement mortar complete
PVC Pipe Line : Supply & laying of 63mm dia PVC pipeline of ISI including excavation of outlet back filling of trenches of 0.60m depth fixing with all accessories and providing outlet wherever required backfilling of trenches etc complete
Supply & erection of 2 Hp pump with all accessories including panelboard etc
Supply, erection, testing and commissioning of 1.5sqmm 3 core copper cable
GOOD EARTH / AGRICULTURE SOIL
Supply and stacking of good earth / agriculture soil from approved source / field ; of approved quality / pH & suitable for plantation work with all leads, lifts, carriage and royalty / taxes etc. Cost of good earth to be paid separately, after reduction of 20% of stacked volume of good earth
b)cattle manure : Supply of cattle manure
Supply of grass and planting by dibbling the area including watering & maintenance of lawn for 30 days or more till grass forms a thick lawn cushion free from weeds
SUBHEAD-XXX : FURNITURE
Supply of Sr. Executive Table of curve shape of size 2350 x 1050 x 750mm made out of 19mm thick commercial board with 4mm thick Teak veneer in Double (Decorative) pattern & top to have 30mm thick, front. having 4 Nos drawers (Right/Left) ride on Quadro Sliding channels, with locking arrangment with teak wood foot rest of size 100 x 30, all exposed edges to have teak wooden Beading and top to have finish with PU polish and inner sides with 0.8 lamination etc. all complete. Side Unit of size 1350 x 525 x 750 mm made out of 19 mm thick commercial block board covered with 4 mm teak veneer on sides, front & upper top to have designer pattern with 4 mm thick teak veneer in decorative & dsigner pattern having 4 Nos of drawers on right / left hand side and key board tray ride on telescopic channels all edges cover with teak wood lipping & back with 6 mm thick commercial ply, Top finished with PU Polished and internal surface finished with 0.8 mm thick lamination etc all complete.
Supply of officer Table of size 1500 x 750 x 750 mm made out of 18mm thick commercial plywood with 1mm thick lamination of approved brand and shade for frame / box work and top, exposed internal surfaces finished with 0.60mm thick lamination of approved brand and shade, drawer unit with three drawers on sliding channels, key board slide out tray of approved brand, superior qualit brushed steel hardware fittings, locking arrangements, teak wood beading / lamination to all exposed edges finish with melamine polish including surface preparation etc, complete all as directed.
Manufacture and supply of table of size 1200 x 600 x 750 mm made out of 18mm thick MR grade plywood for frame work, top and sides, drawers with telescopic sliding channels, all exposed plywood surfaces cladded with 1mm thick laminate, all exposed edges to have teakwood beading with one drawer and one shutter with locking arrangements etc., complete with melamine polish and all as per drawing.
Supply of 600mm deep and 750 mm height Conference Table for 10 persons made out of 19 mm thick commercial board with 4 mm teak veneer & top to have 40mm thick with 4mm thick teak and italian veneer on top in designer pattern and 19 mm thick commercial board tapered foot rest, vertical member with 19mm thick commercial board. Back with 19mm thick commercial board including 4 mm thick teak veneer all exposed edges to have teak wood beading including PU polishing etc. all complete.
Supply and placement of Executive high back chair,The seat shall be made up of 1.2 +/- 0.1 cm thick hot pressed moulded reconstituted wood & upholstered with leather and moulded polyurethane foam. The back shall be designed with contoured lumber support for extra comfort. Size of back shall be (W)-46.0cm, (H)-57.0cm & size of seat shall be (W)-49.0cm x (D)-49.5cm. High Resilience (HR) foam should be used in making seat & back which shall be moulded with density 45 +/- 2 kg/m ³ and hardness load 16+/- 2 kgf as per IS: 7888 for 25% compression. The back rest should be connected to the mechanism with a drop-lift mechanism which can be adjusted in the range of 7.0+/-0.5cm for the comfortable back support to suitable individual need.
Supply of Mid back chairs made up of 1.2cm thick hot-pressed plywood for seat and back, upholstered with fabric upholstery covers and moulded polyurethane foam. BACK SIZE : 47.5 cm. (W) with SEAT SIZE : 47.0 cm. (W) x 48.0 cm. (D) The polyurethane foam is moulded with density = 45 ±2 kg/m and hardness = 20 ±2, on hampden machine at 25% compression. The one-piece armrests are injection moulded from black Co-polymer polypropylene.The chair shall have center tilt mechanism. The bellow is 3 piece telescopic type and injection moulded in black polypropylene. The pedestal is injection moulded in balck 30% glass-filled Nylon and fitted with 5 Nos. of Twin wheel castors. The twin wheel castors are injection moulded in 30% glass filled black Nylon etc., complete all as per Model no: BRAVO-
Supply of Visitor chair with arms, without castors, cushion at seat and back duly upholsted. The polyurethane foam is moulded density 45±2 kg/m³ and hardsness 20±2 at 25% compression with PU arm rest injection moulded from black co polymer polypropylene. The powder coated tublar frame is cantiliver type and made out of 25.4mm x 2mm thick MS ERW tube etc., complete all as per Model no: BRAVO -FU9U12R of Godrej Make or eqivalents of Wipro/Featherlite/Durian/Ikea.
Supply of Executive Designer sofa made out of 50 x 25mm second class hard wood frame having with teak wood in designer & decorative pattern and 125mm thick high density foam in seat & back with 50mm thick rubber foam quitting with 20mm thick u foam of high density including upholstry with fabric of approved shade & quality all exposed teak wood frame finish with melamine polish .
a) Three seater of size 1950 x 835 x 700 etc all complete.
b) Single seater of size 750 x 835 x 550 etc all complete.
a) Supply of centre table of size 1050x525x450mm made out of teak wood frame, 45x45mm teak wood leg and 70x20mm side & top support, top to have 8mm thick glass with edge polish, all wooden surface finish with melamine polish including of all necessary hardware and fitting etc., all complete.
b) Supply of corner table of size 525x525x450mm made out of teak wood frame, 45x45mm teak wood leg and 70x20mm side & top support, top to have 8mm thick glass with edge polish, all wooden surface finish with melamine polish including of all necessary hardware and fitting etc., all complete.
Supply of Storewell of size 1981H x 916 x 486D made of multi bend constuction, inter locking design and full length over lapping, doors and side should be provided with three way bolting mechanism, all the steel surfaces shall be anti corrision treated and oven baked powder coating, e top, bottom, sides material thickness should be 0.9mm and back material thickness should be 0.8mm, removable main door with stiffeners of material thickness 0.9mm should be provided. Almirah plain should be provided with 4 plain adjustable shelves of 0.8mm thickness making 5 compartments etc., complete all as per manufacturer's specifications of store well model of Godrej make or equivalents of Wipro/Featherlite/Durian/Ikea.
Manufacture and supply of ESD Work table(surface resistance :106 to 110 Ohms) with following specifications.Size of 1500x750x1500 mm ht, with 6 power points,Channel with 40 MM. Ms sqr pipe, provision for keeping CPU, 1 No detatchable drawer etc., complete as directed by the Engineer- in-charge. Drg.no.CRF - 03 with all required fittings.
Supply and fixing of modular computer workstation of size (1200 x 600 x1200 ) Partition with framework of 60mm thick partition in powder coated mild steel, top rail and vertical rails made using powder coated aluminum profiles, paneling with tile based insert system in a combination of 12mm the prelam boards / fabric covered particle board with options of writing board laminated and soft board. Table top to have 25mm thick PVC edge banded finished prelaminated particle board with cable outlet, cable raceways provided with 2 level raceways with slots for networking and electrical terminals. and including pedestals of size 460(W)x450(D)x690(H). Body with prelaminated particleboard with edge banding (18mm for sides, top and bottom paneling, 8mm for back paneling), drawer front: 18mm thick prelaminated particle board, drawers: 22swg powder coated mild steel or full/half panel metabox of Hettich / equivalent make Movement of Drawers: Smooth sliding powder coated bottom mounted / incase of powder coated MS draws . Locking: front locking
Supply of Computer chair with arms, without castors, cushion at seat and back duly upholsted. The polyurethane foam is moulded density 45±2 kg/m³ and hardsness 20±2 at 25% compression with PU arm rest injection moulded from black co polymer polypropylene. The powder coated tublar frame is cantiliver type and made out of 25.4mm x 2mm thick MS ERW tube etc., complete all as per Model no: BRAVO -FU9U12R of Godrej Make or eqivalents of Wipro/Featherlite/Durian/Ikea.
Vertical blinds with 100mm wide fabric with chain connected bottom weights etc.,
Providing acoustic wall panelling as per standard specifications including veneer / fabric panelling in approved design etc.,
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid