Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | l1₹3.8 LAccepted-AOC | l1 | Accepted-AOC l1 | |
| 2 | l2₹5.6 L+₹71,465 (14.8%)Rejected-Finance | l2 | Rejected-Finance L2 | |
| 3 | l3₹9.4 L+₹4.5 L (93.9%)Rejected-Finance NOT AVAILABLE | l3 | Rejected-Finance Highest |
Tender Value
₹4.8 L
EMD Value
₹4,800
Closing Date
8 Feb 2024, 4:30 pmClosed
Sr. Executive Engineer
Sr. Executive Engineer ESD HPSEBL Kotla
Tender for complete Overhauling of remaining 2x5.33MVA Power Transformers at 66/22KV Sub-Station Samoli including replacements of all gaskets of Radiators, Top Plate, Inspection Plate, Buchholz Relay, OSR Relay and all Valves to eliminate any oil lea
2024_HPSEB_84865_1
ESDK-25/2023-2024
Limited
Electrical Works
Percentage
60 days
Samoli (Rohru)
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
Yes
₹4,800
13 Feb 2024
1 Feb 2024
9 Feb 2024
1 Feb 2024
8 Feb 2024
1 Feb 2024
1 Feb 2024 - 6 Feb 2024
Amount
RADIATOR GASKET REPLACEMENT: Providing Nu-Cock Sheet, cutting in shape of gaskit (“ NU-CORK '' make Grade RC-70 C, Joint less) afterwards removing of all old gaskits and fixing along with silicon sealant and quick dry adhesive, carbon cleaning of each radiator hole as per site requirments of 2x5.3MVA Power Transformers at Samoli.
TOP PLATE GASKET REPLACEMENT:Deep cleaning of core by lifting of core with specilised jack mechanism via scrubbing & dehydrated hot oil to remove any sludge particles or metal remanents via drain outlet to improve IR, PPM and BDV values of oil and transformer as per site requirments of 2x5.3MVA Power Transformers at Samoli.
INSPECTION PLATE, BUCHHLOZ & OSR RELAY, VALVE GASKET:eplacement of all gaskits of inspection plates, buchhloz & OSR relays and all oil valves alongwith adhesive treatment.
CORE AND TANK CLEANING:Deep cleaning of core by lifting of core with specilised jack mechanism via scrubbing & dehydrated hot oil to remove any sludge particles or metal remanents via drain outlet to improve IR, PPM and BDV values of oil and transformer as per site requirments of 2x5.3MVA Power Transformers at Samoli.
DEHYDRATION AND FILTRATION:dehydration and filteration of oil (10600Ltrs. of transformer & 400Ltrs. additional used for cleaning) via specilised machinary which includes micron, magnetic and bag filtration, removing of moisture via raising the temprature to 65 degrees and minimum 7 degrees for improving BDV (till >75kV) and PPM oil ratings as per site requirments of 2x5.3MVA Power Transformers at Samoli.
DEEP FLUSHING:lifting of core via dual jack set up of 8 Jack system and manual cleaning of core and tank via scrubbing and and carbon cleaning adhesive to restore the tank and core to brand new condition as per site requirments of 2x5.3MVA Power Transformers at Samoli.
PAINTING:paint work on transformer, with chemical washing, cleaning all parts & Paint with sprey paint & used heat proof paint include labour Charges etc. to restore the transformer to brand new condition as per site requirments of 2x5.3MVA Power Transformers at Samoli.
RAJAT SINGH
ANKUSH KUMAR
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .