Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.1 LAccepted-AOC | L1 | Accepted-AOC The L1 bidder is techno-commercially eligible and the rate quoted is reasonable and justified, which has been accepted by the Competent Authority, NK Area. | |
| 2 | L2₹2.7 L+₹13,443 (5.19%)Rejected-Finance MAHAVIR NAGAR BUKBUKA KHALARI DISTT RANCHI JHARKHAND 829205 | RANCHI | JHARKHAND | 829205 | L2 | Rejected-Finance L2 | |
| 3 | L3₹2.9 L+₹28,850 (11.1%)Rejected-Finance ANAND NAGAR KAMRE RATU DISTT RANCHI JHARKHAND 835222 | RANCHI | RANCHI | JHARKHAND | 835222 | L3 | Rejected-Finance L3 |
Tender Value
₹2.8 L
EMD Value
₹3,500
Closing Date
8 Sept 2022, 5:00 pmClosed
SO EnM NK
GM Office, NK Area
Repairing and rewiring of damaged AC Circuit/Submain wiring of power point, additional light and plug point, replacement of damaged service wire, control switches and other miscellaneous works in Central Hospital Dakra under GM Unit, NK Area
2022_CCL_254468_1
GM (NK)/EnM/e-NIT/2022-23/ 92
Open Tender
Electrical and Maintenance Works
Item Rate
20 days
GM Unit, NK Area
As per NIT
2 documents required · 2 mandatory
₹3,500
20 Oct 2022
26 Aug 2022
10 Sept 2022
27 Aug 2022
8 Sept 2022
27 Aug 2022
27 Aug 2022 - 3 Sept 2022
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group B
Wiring for light / power plug with 2x4 sq. mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit alongwith 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 x 10 sq. mm + 1 x 10 sq. mm earth wire.
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 3 x 16 sq. mm + 1 x 16 sq. mm earth wire.
Supplying and fixing metal box of 180 mm X 100 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 and 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required
Supplying and fixing metal box of 150 mm X 75 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 amps socket outlet and 5/6 amps piano type switch, connection, painting etc. as required (For light plugs to be used in non residential buildings).
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 x 2.5 sq. mm + 1 x 2.5 sq. mm earth wire.
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc as required.
Earthing with G.I. earth pipe 4.5 Metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc with charcoal / coke and salt as required.
Supplying, installing, testing and commissioning of following capacity TPN tap off box made of 1.6 mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TPN disconnector FSU and HRC fuses, connections, earthing etc as required. 100 amps TPN.
Total impact of GST for the purpose of CTC
M/S NIRAJ ELECTRICALS
M/S SHRI RAM ENTERPRISES
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_263055.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .