Tender Value
Refer Docs
EMD Value
₹39,000
Closing Date
2 Jan 2025, 1:00 pmClosed
District Engiineer, Purba Bardhaman Zilla Parishad
Purba Bardhaman Zilla Parishad
Supply, Installation, testing commissioning of 160 KVA, 415V,50Hz 3Phase Silent Diesel Generator Set at Office Building, Purba Bardhaman Zilla Parishad
2024_ZPHD_786968_1
DE-E-NIT-51 of 24-25
Open Tender
Electrical Work/ Equipment
Item Rate
10 days
Purba Bardhaman Zilla Parishad Office Building
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹39,000
PURBA BARDHAMAN ZILLA PARISHAD
11 Mar 2025
18 Dec 2024
4 Jan 2025
18 Dec 2024
2 Jan 2025
18 Dec 2024
24 Dec 2024
Amount
SITC of 160 KVA ,415V,50Hz 3Phase Silent Diesel Generator Set incl full tank HSD oil,comprising of Engine,Alternator,separate AMF panel, Base frame, Fuel tank,Battery,CPCB-IV+ approved Engine & Acoustic Enclosure having following specifications:-(Make: Cummins/Volvo/ Catterpillar/ Greeves Cotton/ Mahendra/ Kirloskar/Ashok Layland)
Engine:-
Engine Type: 4 Stroke Diesel Engine
Rated Output: 197 BHP or Higher
Duty: PRIME
Cooling: Coolant with radiator
Cylinder: 6, Inline
Aspiration: Turbo Charged Inter cooled
Type of Governor: Electrnoic
Fuel Tank Capacity: Minimum Capacity 250 Ltrs
Fuel Consumption- at 75%rated load with Radiator or Fan: 29.93 Ltr/Hr or Less
Fuel Consumption- at 100% rated load with Radiator or Fan: 35.95 Ltr/Hr or Less
Over Load Capacity: 10% Overload for one hourfor every 12 hourscontinuous running at Full load or better
Engine instrument Panel:Consisting of starting switch with Key,Lube OilIndicator,water temperature Indicator, RPM indicator and Hour meter
Safety Controls:Emergency Stop ,Low Lube Oil Pressure warings/Shutdown ,High Engine Water Temp warning/Shutdown,sensor failure Indicator,Engine over speed indicator,Battery Charging and Low barttery indicator
Exhaust Silencer: Residental Type
Starting System: 12V starting system complete with starter motor, charging alternator with rectifier and Cut-out as per manufacturer standard
Battery: Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak BATTERY WARNING.
Alternator:-
Make:Stamford/Leroy somer/Crompton
Rating: 415V,3PH 50Hz, 160 KVA ,1500rpm
Type:Brushlress,Self Excited and self regulated
Insulation: Calss H
Protection: screen-protected drip proof with Min IP-23 degree of protection
Voltage Regulation(max) : _+ 1% at full load.
Winding Connection: Star with Neutral
Total Harmonic distortion in output waveform:<5%
AMF Panel:-
Cubical type floor mounted AMF Panel made from 14SWG Sheet Steel, duly pretreated,powder coated painted and aesthetically finished, suitable for controlling of 160KVA DG set having following specification/ features. Manufactured by the OEM/CPRI/Approved Panel builder.
250 A, 4 Pole Power Contractor for Mains & DG -2Nos. 250A, 4Pole, 36Ka, MCCB, Microprocessor based with LSIG protections for Mains & DG - 2 Nos.
ii) In Built By-Pass switch for rated capacity
iii)on-delay timer for load change over
iv)On delay timer for engine shut off
v)Engine On-Off switch (Push button type)
vii)Minimum five number indicating lamps to indicate "mains ON" LOAD MAINS Set running "load on set" battery charger on"
viii) Audio visual alarm for Low lubricating oil pressure, "High coolant temperature Start failure ,and DG over load."
x)Microprocessor based relay with composite meter for digital display of following.
a)Generator voltage/AC Mains voltage
b)Generator Current in all phase
c)Frequency
d)Power Factor
e)Indication for Alternator supply
f)Running time indication number of hours of operation and service intervals ,service due indications
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15(fifteen) second from the instant of mains failure.
Acoustic Enclosure:-
The DG set should have integrated acoustic enclosure at the manufacturing state itself High quality acoustic must be certified as per CPCB-IV+ norms.
Base Frame-Rugged in construction fabricated out of ISMC Channel for mounting the engine, Alternator, Acoustic Enclosure etc. mounted on AVM pads and having provision for lifting Hook.
Installation of DG
Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. (PWD schedule G - 03/5.d) (For body earthing)
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: - By ISI-Medium GI pipe. (PWD schedule G - 01/2.a)
Excavation of soil for installation of Earth Electrode and filling & ramming - a) For Soft Soil . (Schedule of PWD page G-1 & Item no. - 1.a)
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works. (Schedule of PWD page E-16 & Item no. - 7.a)
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required:- a) 2 x 80/0.4 (10 sqmm) (For Neutral Earthing) (Schedule of PWD page E-09 & Item no. - 1.m)
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured 4 core 120 sq.mm. cables (Schedule of PWD page F-4 & Item no. - 7.C)
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials.4 core 120 sq.mm. cables (Schedule of PWD page F-5 & Item no. - 8.b- xix)
Supply & laying of 1.1 KV grade 10 core 1.5 sq.mm. PVC copper conductor control cable with socketion partly recessed and partly by shaddle on wall to interconnect DG set with AMF panel.
Terms & Conditions
(i) Rate should be quoted inclusive of all applicable taxes and Duty etc.
(ii) All materials, equipments & accessories must conform to relivent IS specifications. The DG set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
(iii) Nacessary manufacturer's test certificate for Diesel Engine, Alternator etc. will have to submit in triplicate copy during delivery for the equipment.
(iv) Copy of "Type Approval Certificate" for Engine & DG Set must be furnished at the time of delivery issued from component Authority (As per CPCB-IV+)
(v) Circuit Diagram for AMF panel must be submitted from the Manufacturer/OEM.
(vi) The entire set must be warranted at least 60 months from the date of Delivery & 60 months/ 8000 Hrs from the date of Commissioning whichever is latter. However Engine & Alternator should be warranted of 5 years/8000 Hrs, whichever is earlier.
(vii) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
B M ELECTRIC (BID ID -5934759)
SREE GURU ENGINEERING (BID ID -5934749)
GSP Power Projects (Retail Division) (BID ID -5925866)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .