COMMANDER WORKS ENGINEER PUNE - 411001
HEADQUARTERS COMMANDER WORKS ENGINEERS GEN CARIAPPA MARG, PUNE-411 001
85989 SPECIAL REPAIR / REPLACEMENT OF BER TRANSFORMER AND ALLIED WORKS AT ALC, AICTS AND NURSING CADET MESS UNDER AGE E/M-I OF GE (SOUTH) PUNE
2026_MES_789160_1
85989 CWE PUNE
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
GE (SOUTH) PUNE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
GE (SOUTH)
₹2.1 L
Yes
12 Sept 2026
12 Sept 2026
17 Oct 2026
12 Sept 2026
10 Oct 2026
3 Oct 2026
13 Sept 2026 - 18 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking down existing transformer 500/315/300/250/ 200 / 160 / 100 kVA by disconnecting its HT/LT connection, including lifting, shifting, loading, unloading, transportation and depositing the transformer in MES store yard from the work site, complete all as specified and as directed.
Note: All necessary tools & plants (T&P) required for dismantling shall be included in the quoted rate. | 7 | EACH JOB | - | - |
| - | Supply, Installation, Testing and Commissioning of copper wound transformer step down, outdoor type complete with standard fittings, HT 22 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180, level 2 and above of capacity 315kVA complete all as specified and directed. | 1 | EACH JOB | - | - |
| - | Supply, Installation, Testing and Commissioning of copper wound transformer step down, outdoor type complete with standard fittings, HT 22 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180, level 2 and above of capacity 200kVA complete all as specified and directed. | 1 | EACH JOB | - | - |
| - | Supply, Installation, Testing and Commissioning of copper wound transformer step down, outdoor type complete with standard fittings, HT 22 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180, level 2 and above of capacity 250 kVA complete all as specified and directed. | 1 | EACH JOB | - | - |
| - | Supply, Installation, Testing and Commissioning of copper wound transformer step down, outdoor type complete with standard fittings, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180, level 2 and above of capacity 250 kVA complete all as specified and directed. | 1 | EACH JOB | - | - |
| - | Supply, Installation, Testing and Commissioning of copper wound transformer step down, outdoor type complete with standard fittings, HT 22 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180, level 2 and above of capacity 500 kVA complete all as specified and directed. | 1 | EACH JOB | - | - |
| - | Supply, Installation, Testing and Commissioning of copper wound transformer step down, outdoor type complete with standard fittings, HT 22 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180, level 2 and above of capacity 100 kVA complete all as specified and directed. | 1 | EACH JOB | - | - |
| - | Supply, Installation, Testing and Commissioning of copper wound transformer step down, outdoor type complete with standard fittings, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180, level 2 and above of capacity 315 kVA complete all as specified and directed. | 1 | EACH JOB | - | - |
| - | SPECIFICATIONS FOR SER. ITEM No 02.00 to 08.00 :-
Tapping on HV [%] : 2.5% to ˗5% upto 200 kVA, +5% to -10% for 250 kVA to 500 kVA in step of 2.5% as per Latest BIS norms
Phase & Frequency : 3 Phase & 50 Hz
Connection : Delta Star
Vector Group : DYN 11
Cooling : ONAN
Type : Outdoor
Insulation : Class A | - | - | - | - |
| - | Ser. Item No. 8.00 Contd....
Note : The Transformers shall also be provided with following Terminal Arrangement & Fittings and rate quoted against respective item is deemed to be included for the same:
Terminal Arrangement:
[a] LV Side: Cable Box & HV side : Open bare bush with LA and arcing horns protection
[b] Quad furcating cable box with five compression glands for PVC Cable and One additional neutral terminal shall be brought out separately for earthing purpose on LV Side.
[c] First filling of new and unused Transformer Oil [IS – 335 Marked], filtered and tested up to 60KV dielectric strength at 2.5mm air gap between testing electrodes. Certification of dielectric strength shall be submitted by the Contractor after filling the oil.
[d] Routine tests mentioned in these tender documents and relevant IS are to be followed.
[e] OEM should be BIS certified & BEE star labled for all the rating of transformers that are to be installed. | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 4.58 MB
BOQ_884628.xls
BOQ • 0.30 MB
85989TenderDocs.pdf
Tender Documents • 4.82 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .