| 1 | L1₹48.4 LAccepted-AOC AT ROAD NEAR MES TINALI PO CHABUA DIST DIBRUGARH ASSAM | ₹48.4 L Quoted ₹49.3 L | L1 | Accepted-AOC Being Lowest |
| 2 | L2₹52.0 L+₹2.7 L (5.54%)Rejected-Finance | ₹52.0 L+₹2.7 L (5.54%) | L2 | Rejected-Finance Being other than lowest |
| 3 | L3₹52.0 L+₹2.8 L (5.59%)Rejected-Finance LOONPURIA GAON AT ROAD PANITOLA PO PANITOLA 786183 DIST TINSUKIA ASSAM | TINSUKIA | ASSAM | 786183 | ₹52.0 L+₹2.8 L (5.59%) | L3 | Rejected-Finance Being other than lowest |
| 4 | L4₹53.2 L+₹4.0 L (8.07%)Rejected-Finance A T ROAD CHABUA NEAR ST LUKAS HOSPITAL PO CHABUA DIST DIBRUGARH ASSAM 786 184 | CHABUA | DIBRUGARH | ASSAM | 786184 | ₹53.2 L+₹4.0 L (8.07%) | L4 | Rejected-Finance Being other than lowest |
| 5 | L5₹56.0 L+₹6.7 L (13.7%)Rejected-Finance NOT AVAILABLE | ₹56.0 L+₹6.7 L (13.7%) | L5 | Rejected-Finance Being other than lowest |
Tender Value
₹46.5 L
EMD Value
₹93,000
Closing Date
30 Sept 2024, 6:00 pmClosed
Garrison Engineer AF Mohanbari
Garrison Engineer AF Mohanbari Mohanbari Post Dibrugarh Assam 786012
SPECIAL REPAIR OF LT FEEDER PILLAR OF VARIOUS CAPACITY OF SUB STATION ALONGWITH ALLIED CONNECTED ITEMS AND PROVN OF HIGH MAST LIGHTS AT AF STN DINJAN UNDER GE (AF) MOHANBARI
2024_MES_670156_1
8001/603/E8
Open Tender
Civil Works
Item Rate
180 days
Dinjan
Class D, Category b (i)
7 documents required · 7 mandatory
₹500
Garrison Engineer (AF) Mohanbari
₹93,000
30 Oct 2024
2 Sept 2024
1 Oct 2024
2 Sept 2024
30 Sept 2024
17 Sept 2024
Amount
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sqmm 3.5core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm 3.5core complete all as specified and directed.
Excavation in trenches not exceeding 1.50 mtr wide and not exceeding 1.50 mtr deep for taking out/ laying of under ground cable, pole, pipe, stay and getting out in soft soil strata including making good to the disbturbed surfaces such as hardstanding, footpath/ pavments complete all as specified and directed.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25cm thick spread in any type of soil complete all as specified and directed.
Removing excavated materials to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.50 mtr above the starting point complete all as specified and directed.
M&L for sand cushioning to under ground cable provided with a layer of sand 8 cm depth before laying of cable and 15 cm depth after laying and stretching the cable complete all as specified and directed. Note: Punned thickness of sand shall be measured & paid.
M&L for well burnt sub class 'B' bricks of nominal size 230X115X75 mm abutting each other for mechanical protection of cable with width equal to length of brick including taking out old bricks complete all as specified and directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 50 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Material and Labour for PCC cable route indiacator made out with 300 x 300 x 300 mm thick PCC Block of 1:3:6 type C1 by using 20mm gradded aggragate and embossing HT indicator made out with MS / CI round shaped sheet welded with 200 mm long MS flat iron including 2 coats of synthetic enamel paint over one coat of red oxide primer to iron surfaces fixing at different cable routes complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate 600mm x 600mm x6mm thick elecrode and 32mm x 6mm galvanised iron strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI strip 32mm x 6mm as earth lead by means of bolts, nuts, check nuts and washers (including welding) of galvanised iron or steel and connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed.
Taking down old U/S cable of various size from trenches of any depth and deposite to MES E/M store yard for further disposal as schedule of credit to the contractor complete all as specified and directed. (As per Site requirement)
M&L for High galvanized mast light of 16 mtr height suitable for 9 lantern symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6 mm dia 7/19 guage and double drum winch with luminaire mounting arm, pully assembly, aviation obstruction light, lightning arrester spike including RCC foundation as per height as recommended by OEM complete including LT control panel for the highmast light complete all as specified and directed. (Note: In HM light, cost of luminaires is to be added separately. Rates are inclusive of cost of foundation and cable from panel to each flood light)
Supply and fixing LED flood light 200 watt 230 V AC outdoor type made up of pressure die cast aluminium housing with toughened glass and high power LED and secondary lenses with 30-60D Beam angle with IP66 protection, System Efficacy>110LPW,10KV SPD with impact and corrosion resistant complete with driver and lamp complete all as specified and directed.
Supply, laying,jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core complete all as specified and directed.
Supply and fixing of GI Pipe of 25 mm dia light grade for cable protection pipe complete all as specified and directed.
KP GHOSH AND CO (BID ID -3107311)
M/S A K BROTHERS (BID ID -3105959)
M/s Sashi Enterprise (BID ID -3104490)
M/S CHAKRA GOHAIN (BID ID -3105769)
M/S Abhi Traders (BID ID -3105680)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .