Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.9 CrAccepted-AOC | ₹12.9 Cr | L1 | Accepted-AOC Eligible Lowest Bidder |
| 2 | L2₹14.2 CrRejected-Finance | ₹14.2 Cr | L2 | Rejected-Finance Other than Lowest Bidder |
| 3 | L3₹14.5 CrRejected-Finance | ₹14.5 Cr | L3 | Rejected-Finance Other than Lowest Bidder |
| 4 | L4₹15.4 CrRejected-Finance | ₹15.4 Cr | L4 | Rejected-Finance Other than Lowest Bidder |
Tender Value
₹11.5 Cr
EMD Value
₹9.0 L
Closing Date
14 May 2022, 6:00 pmClosed
Chief Engineer Lucknow Zone,Lucknow
Chief Engineer Lucknow Zone,Lucknow
PROVISION OF KLP (PH-II OF III PHASES) FOR AATS AGRA
2022_MES_513137_1
CELZ/AGR/T-08 OF 2021-22
Open Tender
Civil Works
450 days
Headquarter Chief Engineer Lucknow Zone
As per tender documents
7 documents required · 7 mandatory
₹3,000
GE (East) Agra
₹9.0 L
Yes
9 Jun 2022
11 Mar 2022
16 May 2022
11 Mar 2022
14 May 2022
28 Apr 2022
15 Mar 2022 - 24 Mar 2022
Amount
Sch 'A' Part-I (Buildings & Structures Works) Note : This schedule is pre-priced by MES and the pre-priced rate indicated are under Col. 5.
Total amount of Sch 'A' Part II (Site clearance, excavation and earth work)
Total amount of Sch 'A' Part III (Internal Water Supply )
Total amount of Sch 'A' Part IV (Internal Electrification)
Total amount of Sch 'A' Part V (Sewage Disposal)
Total amount of Sch 'A' Part VI (ROAD,PATH AND CULVERT )
Total amount of Sch 'A' Part VII (Area Drainage)
Total amount of Sch 'A' Part VIII (SOLAR WATER HEATER)
Total amount of Sch 'A' Part IX (External Water Supply )
Total amount of Sch 'A' Part X (External Electrification )
Total amount of Sch 'A' Part XI (DEMOLITION/DISMANTLING)
Sch 'A' Part - XII (Miscellaneous Items) Note - This Schedule is not pre-priced by MES and the pre - priced rate indicated as "Rs 0.00 under col.5 siginifies this fact only.
INTERNAL ELECTRIFICATION Point wiring complete for One light/Fan/Exhaust Fan point controlled by one switch with PVC insualted and unsheathed FRLS cable 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :- In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete for One light point controlled by two way switches with PVC insualted and unsheathed FRLS cable 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :- In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete for one 5 Pin 5 Amp switch Socket outlet point on an independent board, with PVC insualted and unsheathed FRLS CABLE 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :- In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete for one 5 Pin 5 Amp switch Socket outlet point on same board, with PVC insualted and unsheathed FRLS CABLE 1.5 Sqmm (nominal area) ISI marked, multi-stranded copper conductor single core including ISI marked 20 mm dia PVC conduit medium grade concealed in wall and PVC conduit not less than 20 mm in roof / floor slab and ceiling, pressed GI concealed terminal boxes not less than 1.6 mm thick of required size and with top cover 3 mm thick of plastic laminated sheets of requied colour complete, including 1.5 Sqmm PVC, FRLS cable insulated unsheathed copper earth wire to the common earth and connecting to earth dolly, including colour coding of cable shall be Phase-red, Neutral-black and Earth- green with all accessories complete all as specified and directed. Note :-In case of roof/ceiling, heavy duty PVC pipe shall be used without any extra cost.
Point wiring complete with PVC insulated and unsheathed, FRLS cable 2.5 sqmm (nominal area) ,ISI marked, multi-stranded copper conductor single core including ISI marked 20mm dia PVC conduit concealed in wall and MS conduit in roof/floorslab excluding flush metal GI boxes complete,including 1.5 Sqmm,FRLS cable PVC insulated unsheathed copper earth wire to the common earth and connecting to earth dolly,including colour coding of cable shall be Phase-red,Neutral-black and Earth- green with all accessories and all as specified Note :- In case of roof/ceiling, only MS black sheet conduit ISI marked dia of coduit not less than 20 mm shall be used without any extra cost.
Supply and fixing Tele phone socket ,Modular, ISI marked complete all as specified and directed.
Supply and fixing MCB Single pole 1 to 2 amp rating ‘C’ series 10 KA ,240 Volts AC 50 HZ ISI marked complete all as specified and directed.
Supply and fixing TV socket ,Modular, ISI marked complete all as specified and directed.
Switch flush type 5/6 Amps single pole two way complete all as specified and dierected.
Supply and fixing Modular Metal Flush Box for 8 Module complete all as specified and directed.
S&F LED batten Tube light surface / wall mounted with specially designed powder coated aluminum housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired upto terminal block, power consumption <20W (4 FT 20 W), luminaire lumen >2000 lm, system efficiency of >120 lumens /W, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class I, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 45 degree Celsius, driver efficency>85%, power factor>0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) as per L70 criteria, two stages isolated constant current operated driver with range 150-270V AC and seafty extra low voltage safe level <60V DC as per IEC standard with LM70 & LM80 certification complete all as specified and directed
S&F LED batten Tube Light surface / wall mounted with specially designed powder coated aluminum housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired upto terminal block, power consumption <10W (2 feet 10 W) luminaire lumen >1000 lm, system efficiency of >120 lumens /W, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class I, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 45 degree Celsius, driver efficency>85%, power factor>0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) as per L70 criteria, two stages isolated constant current operated driver with range 150-270V AC and seafty extra low voltage safe level <60V DC as per IEC standard with LM70 & LM80 certification.complete all as specified and directed.
S&F LED Building security light fitting with aluminum pressure die cast housing, high purity PC Fresnel diffuser with silicon gasket for IP-65 protection, power consumption <20 W (14W) & luminaire lumen >2500 lm and system efficiency > 120 lm/W, in built electronic driver prewired upto terminal block with driver efficiency >85% power factor >0.95 as light source with toughened glass including two core flexible copper wire of 1.5 sq mm from ceiling rose to the connector of fitting, connection wires not to be more than 2.5 in length and made out of GI tubing 35/40 mm dia /suitable dia light grade bend to shape security light fitting with necessary MS clamp 25 mm wide and 6 mm in thickness in suitable length not more than 30 CM and max length of pipe 1.5 Mtr long with one code of anti corrosive primer and two coats aluminum paint including nuts, bolts and washers complete all as specified and directed.
S&F Mirror light Decorative ultra slim square profile liner LED lighting fixture with extruded polycarbonate body with Minimum 8 Watt & Maximum 11 Watt LED warm white in colour with a luminous efficacy of 120 lum/watt(min) with PF not less than 0.9 with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class I, Ingress protection IP 20, colour rendering index CRI>80, temp range 0 to 45 degree Celsius, driver efficency>85%, power factor>0.9, THD <20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50000 burning hrs (min) as per L70 criteria, two stages isolated constant current operated driver with range 150-270V AC and seafty extra low voltage safe level <60V DC as per IEC standard with LM70 & LM80 certification.complete all as specified and directed.
S&F circular slim surface LED downlighter of 8 Watts with housing made up of die cast aluminum for better thermal management, high transmitivity non yellowing PMMA diffuser for better light output and uniform light distribution without glare, power consumption <10W, luminaire lumen>1000lm, driver and accessories to be prewired, CRI>70, LED efficiency > 120 lm/W photo biological safety report as per IEC624718 & electrical insulation class I, LED life with L70 criteries -37000 hrs colour temp >6000K, Ingress protection IP-20, ambient temperature 0 to 45 degree Celsius, driver efficiency >85%, THD<10% as per IEC 61000-3-2, power factor >0.95, surge protection 2.5 KV, two stages isolatated constant current operated driver with range 150-270V AC and safety extra low voltage safe level <60V DC as per IEC standard with LM79 & LM80 certification complete all as specified and directed.
S&F circular slim surface LED Decorative Wall mounting of 12 Watts with LED Bulb 12 watts complete Polycarbonate housing, globe type Glass protection with high transmitivity non yellowing PMMA diffuser for better light output and uniform light distribution without glare, power consumption <12W, luminaire lumen>1000lm, driver and accessories to be prewired, CRI>70, LED efficiency > 120 lm/W photo biological safety report as per IEC624718 & electrical insulation class I, LED life with L70 criteries -37000 hrs colour temp >6000K, Ingress protection IP-20, ambient temperature 0 to 45 degree Celsius, driver efficiency >85%, THD<10% as per IEC 61000-3-2, power factor >0.95, surge protection 2.5 KV, two stages isolatated constant current operated driver with range 150-270V AC and safety extra low voltage safe level <60V DC as per IEC standard with LM79 & LM80 certification complete all as specified and directed.
Supply and fixing Study Lamp, 14 Watt LED with fixing arrangement on wall with ISI marked complete all as specified and directed.
S&F MCCB 4 pole ,415 V ,AC fixed type 100 amps with breaking capacity 10 KA complete all as specified and directed.
S&F MCCB VTPN DB double door type, 415 Volts AC, with 200 amp rated bus bar of suitable size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricated ,powder coated complete with out MCCB and with enclosure blank plates for unused way suitable for 4 way complete all as specified and directed.
S&F MCB TP 63 Amps 'C" series,,10 KA 415 Volts ,AC complete all as specified and directed.
S&F MCB SPN 40 Amps 'C" series,,10 KA 240 Volts ,AC complete all as specified and directed.
S&F MCB SPN 16 Amps 'C" series,,10 KA 240 Volts ,AC complete all as specified and directed.
S&F MCB single pole 6- 32 Amp rating 'B' Series,10 KA 240 Volts,AC 50 Hz ,ISI marked complete all as specified and directed.
M & L Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground.(earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr. below ground level connecting to galvanised earth lead wire 4.0 mm dia as earth lead upto 7.5 meters long connected by means of bolts, check nuts and washers of GI and earth wire protected by provision of GI pipe medium grade, 15 mm bore including provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4Kg/Sqm) and frame of angle iron 40 x 40 x 3mm fixing with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge plate, common salt and charcoal filling, with fixing arrangement, funnel, wire mesh and earth work in hard / dense soil, returning filling in and removal of surplus soil to a distance not exeeding 50 metre, all as per electrical plate No 3 of SSR 2009 Part-I and connection all as specified and testing on completion. Note: The cost of excavation and earth work, PCC pit and pit covers, funnel and watering pipe, wire mesh, charcoal dust and common salt,20/ 40mm dia, medium grade, GI pipe as protection to GI wire 4.0 mm as main earthing lead from earth electrode to main TPN MCCBs DB/MCB DB/ test point length not less than 7.5mtrs) shall be deemed included in the unit rate for earthing and testing complete all as specified and directed.
EXTERNAL ELECTRIC SUPPLY Supply, Installation, testing and commissioning LT panel board design vertical as per IS/IEC 61439-182 for 415 volts, 50 Hz rated fault level 65 KA with internal arc containment with IP 54 protection rupturing capacity at 415 volts, factry mede in as approved factory having seven tank treatment process for powder coating with thickness not less than 60 microns with paint shape RAL -7035 provided with suitable gasket to make it dust/vermin proof & general contruction comprising of following under item No 37.01 to 37.05 :- ( LT Panel-01 Near 630 KVA Transformer) (a) OUTER SHELL : The outer steel shall be made out of 3.15 mm thick CRCA sheet steel & MS angle section 50x50x6 mm frame with front and back openable, double door system lockable / openable by keys from both sides having flush pattern fency locks with louvers & sir vent gasket for natural flow of air "U" type gasket shall be used to make the outer shell completely vermin proof. The bottam of outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 75 to 100 mm space all around & shall be fabricated in suc a way that the complete inner shell alongwith its control gears & accessories could be taken outsite without disturbing out shell. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the panel, safety shall be made with degree of protection of outer shell be IP -56, computer out self adhesive vinyl danger notic plate having conventional symbol of bone & skulll be provided.
(b) INNER SHELL :- Inner shell made out of 2.0 mm thick CRCA sheet duly compartmentalised for each control gear, front & back openable single door system lockable / openable keys from both sides having chromium plated 19 mm dia fancy locks (02 Nos in each compartment having loouvers & air vent gasket for natural flow of air, "U" type gasket shall be used to made the inner shell completely vermin proof & to accommodate incommer/out going MCCBs and electrical grade aluminium for rated continuos current of 400 Amps for main bus bar with 65 KA short time current (rms) for 1 Sec & 105 KA (Peak) rated dynamic short circuit with stand with heat shrinkable sleeves alongwith shoulder for joints & earth bus bar of aluminium 50x10 sqmm size (Minimum ) with short circuit rating of 30 KA per sec duly colour coded shall be mounted on suitable size "F" class insulator made of nonhygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material at an interval not less than 500 mm through out the length of the TPN busbar. The cubical incomer MCCB as well as out going shall ha ve aluminium TPN extension links of current carrying capacity not less that 1.5 times the rated capacity of indidual feeder. The extension links shall not be less than 300 mm long supported on suitable size "F" class insulator made of non hygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material at interval not less than 500 mm through out the length of the TPN bus bar. The cubical incommer MCCB as well out going shall have aluminium TPN extension links of current carrying capacity not less then 1.5 time the rated capacity of individual feeder, the extension links
37.01 Contd... shall not be less than 300 mm long supported on suitable size F Class insulator made of non hygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material having provision for termination of incomer & Outging cables. All inter connections between the bus bar as well as outgoing feeder shall be carried out with TPN copper busbar of rating not less than 1.5 times rated capacity of individual outgoing feeder & should be insulated with heat shrinkable PVC sleeves.
All control wires shall be with 2.5 Sqmm multistranded copper conductor and shall be properly bunched, tied, ferruled for proper identifacation and crimped with adequate size of copper lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating having thickness not less 100 microns. A detachable predrilled gland plate of thickness 3.15 mm powder coated should be used at the bottom. The inner shell should be powder coated siemens grey structural RAL7032 shade. An inspection lamp LED 5 watt with movable non ferrous chromium plated arm fitted on top side of inner shell should be provided. The degree of protection for inner shell shall be IP -42 & carry the following controls :-
INCOMING : (a) Supply and fixing of MCCB, 4 pole, 200 Amps, 415 Volt, with microprocessor release Icu = 36 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard Qty - 01 Nos. (b) Digital panel meter for Amp,volt,KWH,PF and other parameters flush mounting of size 96x96 mm.-01 No.
OUTGOING : (c) Supply and fixing of MCCB, 4 pole,100 Amps, 415 Volt, with thermal magnetic release Icu = 16 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard Qty - 01 Nos. (d) Supply and fixing of MCCB, 4 pole,40 Amps, 415 Volt, with thermal magnetic release Icu = 16 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard Qty - 02 Nos. (e) MCB 4 Pole, TPN, 40 Amps "c series 10 KA - 02 Nos
Supply and fixing of MCCB, 4 pole, 200 Amps, 415 Volt, with microprocessor release Icu = 36 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard Qty - 01 Nos. (Fixing into the existing panel board at the take over point near 630 KVA transformer)
Supply, Installation, testing and commissioning LT panel board design vertical as per IS/IEC 61439-182 for 415 volts, 50 Hz rated fault level 65 KA with internal aarc containment with IP 54 protection rupturing capacity at 415 volts, factry mede in as approved factory having seven tank treatment process for powder coating with thickness not less than 60 microns with paint shape RAL -7035 provided with suitable gasket to make it dust/vermin proof & general contruction comprising of following :- ( Near 500 KVA tfr LT Panel-02 for feeding to Offrs accn & 90 ORs SM Bk)
(a) OUTER SHELL : The outer steel shall be made out of 3.15 mm thick CRCA sheet steel & MS angle section 50x50x6 mm frame with front and back openable, double door system lockable / openable by keys from both sides having flush pattern fency locks with louvers & sir vent gasket for natural flow of air "U" type gasket shall be used to make the outer shell completely vermin proof. The bottam of outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 75 to 100 mm space all around & shall be fabricated in suc a way that the complete inner shell alongwith its control gears & accessories could be taken outsite without disturbing out shell. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the panel, safety shall be made with degree of protection of outer shell be IP -56, computer out self adhesive vinyl danger notic plate having conventional symbol of bone & skulll be provided.
(b) INNER SHELL :- Inner shell made out of 2.0 mm thick CRCA sheet duly compartmentalised for each control gear, front & back openable single door system lockable / openable keys from both sides having chromium plated 19 mm dia fancy locks (02 Nos in each compartment having loouvers & air vent gasket for natural flow of air, "U" type gasket shall be used to made the inner shell completely vermin proof & to accommodate incommer/out going MCCBs and electrical grade aluminium for rated continuos current of 400 Amps for main bus bar with 65 KA short time current (rms) for 1 Sec & 105 KA (Peak) rated dynamic short circuit with stand with heat shrinkable sleeves alongwith shoulder for joints & earth bus bar of aluminium 50x10 sqmm ssize (Minimum ) with short circuit rating of 30 KA per sec duly colour coded shall be mounted on suitable size "F" class insulator made of nonhygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material at an interval not less than 500 mm through out the length of the TPN busbar. The cubical incomer MCCB as well as out going shall ha ve aluminium TPN extension links of current carrying capacity not less that 1.5 times the rated capacity of indidual feeder. The extension links shall not be less than 300 mm long supported on suitable size "F" class insulator made of non hygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material at interval not less than 500 mm through out the length of the TPN bus bar. The cubical incommer MCCB as well out going shall have aluminium TPN extension links of current carrying capacity not less then 1.5 time the rated capacity of individual feeder, the extension links
39.02 Contd...shall not be less than 300 mm long supported on suitable size F Class insulator made of non hygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material having provision for termination of incomer & Outging cables. All inter connections between the bus bar as well as outgoing feeder shall be carried out with TPN copper busbar of rating not less than 1.5 times rated capacity of individual outgoing feeder & should be insulated with heat shrinkable PVC sleeves.
All control wires shall be with 2.5 Sqmm multistranded copper conductor and shall be properly bunched, tied, ferruled for proper identifacation and crimped with adequate size of copper lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating having thickness not less 100 microns. A detachable predrilled gland plate of thickness 3.15 mm powder coated should be used at the bottom. The inner shell should be powder coated siemens grey structural RAL7032 shade. An inspection lamp LED 5 watt with movable non ferrpus chromium plated arm fitted on top side of inner shell should be provided. The degree of protection for inner shell shall be IP -42 & carry the following controls :-
INCOMING : (a) Supply and fixing of MCCB, 4 pole, 200 Amps, 415 Volt, with microprocessor release Icu = 36 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard Qty - 01 Nos. (b) Digital panel meter for Amp,volt,KWH,PF and other parameters flush mounting of size 96x96 mm.-01 No.
OUTGOING : (c) Supply and fixing of MCCB, 4 pole,160 Amps, 415 Volt, with Microprocessor release Icu = 25 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard Qty - 01 Nos. (Outgoing for officers trainees area Panel ) (d) Supply and fixing of MCCB, 4 pole,40 Amps, 415 Volt, with thermal magnetic release Icu = 16 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard Qty - 05 Nos.(Outgoing for 90 SM BK & DH/CH ). (e) MCB 4 Pole, TPN, 40 Amps "c series 10 KA - 02 Nos
Supply, Installation, testing and commissioning LT panel board design vertical as per IS/IEC 61439-182 for 415 volts, 50 Hz rated fault level 65 KA with internal aarc containment with IP 54 protection rupturing capacity at 415 volts, factry mede in as approved factory having seven tank treatment process for powder coating with thickness not less than 60 microns with paint shape RAL -7035 provided with suitable gasket to make it dust/vermin proof & general contruction comprising of following :- (Officers Living accn LT Panel No 3)
(a) OUTER SHELL : The outer steel shall be made out of 3.15 mm thick CRCA sheet steel & MS angle section 50x50x6 mm frame with front and back openable, double door system lockable / openable by keys from both sides having flush pattern fency locks with louvers & sir vent gasket for natural flow of air "U" type gasket shall be used to make the outer shell completely vermin proof. The bottam of outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 75 to 100 mm space all around & shall be fabricated in suc a way that the complete inner shell alongwith its control gears & accessories could be taken outsite without disturbing out shell. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the panel, safety shall be made with degree of protection of outer shell be IP -56, computer out self adhesive vinyl danger notic plate having conventional symbol of bone & skull be provided.
(b) INNER SHELL :- Inner shell made out of 2.0 mm thick CRCA sheet duly compartmentalised for each control gear, front & back openable single door system lockable / openable keys from both sides having chromium plated 19 mm dia fancy locks (02 Nos in each compartment having loouvers & air vent gasket for natural flow of air, "U" type gasket shall be used to made the inner shell completely vermin proof & to accommodate incommer/out going MCCBs and electrical grade aluminium for rated continuos current of 400 Amps for main bus bar with 65 KA short time current (rms) for 1 Sec & 105 KA (Peak) rated dynamic short circuit with stand with heat shrinkable sleeves alongwith shoulder for joints & earth bus bar of aluminium 50x10 sqmm ssize (Minimum ) with short circuit rating of 30 KA per sec duly colour coded shall be mounted on suitable size "F" class insulator made of nonhygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material at an interval not less than 500 mm through out the length of the TPN busbar. The cubical incomer MCCB as well as out going shall ha ve aluminium TPN extension links of current carrying capacity not less that 1.5 times the rated capacity of indidual feeder. The extension links shall not be less than 300 mm long supported on suitable size "F" class insulator made of non hygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material at interval not less than 500 mm through out the length of the TPN bus bar. The cubical incommer MCCB as well out going shall have aluminium TPN extension links of current carrying capacity not less then 1.5 time the rated capacity of individual feeder, the extension links
40.02 Contd...shall not be less than 300 mm long supported on suitable size F Class insulator made of non hygroscopic, noncumbustile, track resistant high strength FRP/SMC/DMC material having provision for termination of incomer & Outging cables. All inter connections between the bus bar as well as outgoing feeder shall be carried out with TPN copper busbar of rating not less than 1.5 times rated capacity of individual outgoing feeder & should be insulated with heat shrinkable PVC sleeves.
All control wires shall be with 2.5 Sqmm multistranded copper conductor and shall be properly bunched, tied, ferruled for proper identifacation and crimped with adequate size of copper lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating having thickness not less 100 microns. A detachable predrilled gland plate of thickness 3.15 mm powder coated should be used at the bottom. The inner shell should be powder coated siemens grey structural RAL7032 shade. An inspection lamp LED 5 watt with movable non ferrpus chromium plated arm fitted on top side of inner shell should be provided. The degree of protection for inner shell shall be IP -42 & carry the following controls :-
INCOMING : (a)Supply and fixing of MCCB, 4 pole,160 Amps, 415 Volt, with Microprocessor release Icu = 36 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard - 01 Nos. (b) Digital panel meter for Amp,volt,KWH,PF and other parameters flush mounting of size 96x96 mm.-01 No.
OUTGOING : (c) Supply and fixing of MCCB, 4 pole,40 Amps, 415 Volt, with thermal magnetic release Icu = 16 KA & Ics =100% Icu with adjustable over load setting (minimum 70% to 100%) as per IEC - 60947-I and 60947-2 standard - 04 Nos. (Outgoing for officers trainees area Panel ) (d) MCB 4 Pole, TPN, 40 Amps "c series - 02 Nos
M & L Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground.(earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr. below ground level connecting to galvanised iron earth strip 25 x 4 mm as earth lead upto 7.5 meters long connected by means of bolts, check nuts and washers of GI and earth wire protected by provision of GI pipe medium grade, 15 mm bore including provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4Kg/Sqm) and frame of angle iron 40 x 40 x 3mm fixing with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge plate, common salt and charcoal filling, with fixing arrangement, funnel, wire mesh and earth work in hard / dense soil, returning filling in and removal of surplus soil to a distance not exeeding 50 mtr, all as per electrical plate No 3 of SSR 2009 Part-I and connection all as specified and testing on completion. Note: The cost of excavation and earth work, PCC pit and pit covers, funnel and watering pipe, wire mesh, charcoal dust and common salt,20/ 40mm dia, medium grade, GI pipe as protection to GI wire 4.0 mm as main earthing lead from earth electrode to main TPN MCCBs DB/MCB DB/ test point length not less than 7.5 metres) shall be deemed included in the unit rate for earthing and testing complete all as specified and directed.
Earthing complete with galvansided steel earth plate electrode 600 x 600 x 6.0mm thick directly burried in the ground (Earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.50M below the normal ground level, GI wire 4.0 mm dia from earth plate/ electrode to test point (upto max distance of 7.50M is included in unit rate) and connected to earth plate & earth test point by means of bolts, nuts, check nuts and washers of galvanised iron or steel, 15mm bore GI pipe light grade including necessary fittings for protection of earthing wire, watering pipe 20 mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade stone aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be renderd 12 mm thick plaster in cement mortor (1:4), funnel with wire mesh of 22 gauge (0.63 mm) 8 mesh per linear including 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS deformed bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) including all necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and connection from DB to earth electrode with same GI wire alongwith protection pipe and testing on completion complete all as specified and directed.
Supply, erecting and installation of steel tubular, swaged, pole of overall length 9 meter having maximum tensile strength 42 Kgf/mm2 of type 410 SP-31 conforming to IS-2713-1980, single swan neck made out of 50 mm dia MS pipe 1.5 mtr long to be jointed on top of LT pole incl fabrication work for fixing street light. A through hole of 14 mm dia shall be provided at height of 2.5 mtr from base plate for inserting 2 core cable from junction box to top of the pole and top portion shall be fabricated for fixing street light fittings including earth work complete with cast iron base plate, having suitable dia of hole through the pole with nuts & bolts for earthing arrangement, bottom portion of tubular steel pole having 165.10 mm outer dia in 5 meter length, 4.5 mm wall thickness, middle portion having 139.70 mm outer dia in 2 metre length 4.5 mm wall thickness and top portion having 114.30 mm outer dia in 2 meter length, 3.65 mm wall thickness of pole wall, respectively, bottom MS square plate duly painted with two coat of black bituminous paint throughout, internally and externally up to planting depth and painting remaining portion of pole with two coats of aluminium paint to the entire exposed surfaces over one coat of red oxide primer making / pasting three nos circular strips each of 100 mm wide with one yellow and 02 Nos black colour strip synthetic enamel paint and marking / stencil writing of pole numbers with black paint including necessary excavation & earth work, removing excavated soil from site complete all as specified & directed. Note :- Necessary Excavation and earth work, PCC Work for foundation / erection of pole assembly will be deemed to be included in the unit rate.
S&F LED Security light fitting 35 watt, 230 V, IP-65/66 protection with aluminium pressure die cast housing, high power PC fresnel diffuser with silicon gasket for IP 65 protection, power consumption < 25 W & luminaires illuminations > 2500 lm and luminous efficacy > 120 LM/Watt in built electronic driver prewired upto terminal block with driver efficiency > 85%, power factor > 0.95, with toughened glass incl bracket made out of GI tubing 25 mm dia light grade pipe 1.2 mtr long bent to shape & fixing to LT pole with 2 Nos MS clamps of size 32x3 mm incl suitable nut, bolt etc complete all as specified and directed.
Supply and fixing bus bar chamber TPN 415 volts, 32 amps with copper bus bar on porcelain insulators fixed on pole with 02 Nos FI clamps 25x3 mm inccluding 3 core 1.5 Sqmm flexible wire from bus bar to street light complete all as specified and directed.
Supply and fix post top lantern LED type 20 watt, luminous output > 2000 lux with luminous efficacy > 100 LM/watt 230 volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impect and corrosion resistant in built electric driver complete with driver and lamp complete all as specified ant directed.
M&L for Cable jointing kit suitable for 1100 volts grade LT Cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm complete all as specified and directed.
M&L for Cable jointing kit suitable for 1100 volts grade LT Cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed.
M&L for Cable jointing kit suitable for 1100 volts grade LT Cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 50 Sqmm complete all as specified and directed.
M&L for Cable jointing kit suitable for 1100 volts grade LT Cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 25 Sqmm complete all as specified and directed.
M&L for Cable jointing kit suitable for 1100 volts grade LT Cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 2 core XLPE armoured aluminium conductor cable of size 25 Sqmm complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 240 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 120 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 95 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 50 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 25 Sqmm 3.5 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 25 Sqmm 2 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ,ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 10 Sqmm 4 core complete all as specified and directed.
Supply, laying, jointing and commissioning of LT UG cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor ,ISI marked confirming to IS 7098 through pipe/road crossing in ducts, on poles, trenches etc of size 10 Sqmm 2 core complete all as specified and directed.
EXTERNAL WATER SUPPLY M&L for construction of valve chamber 650 x 650 x 650 mm (internal dimensions), including excavation & earth work 100 mm thick PCC 1:4:8 Type D-2 using stone aggregate as in foundation, 230 mm thick fly ash brick work in cement mortar 1:4 , 15 mm thick rendering in cement mortor 1:4 on internal surface of valve pit and mild steel sheet cover 6 mm thick angle iron size 40 x 40 x 6 mm frame around of valve pit, sheet welded on four corners, locking arrangement with pad lock of size 50 mm brass, 6 leavers and duplicate key (Make Godrej) or equivalant specified make as approved including two coat synthetic enamel paint over one coat of red oxide primer on prepared steel surface complete all as specified shown on drawing and as directed.
SUMMER APPLIANCES Supply and Fixing Refrigerator electric driven (single phase), 230V, 50 Hz, capacity 300/310 Litres, BEE 5 star rated complete all as specified and directed.
Supply, Installation, commissioning of Metal Top Deep Freezer single phase 240 volt, 50 HZ, 300/320 litre capacity complete all as specified and directed.
Supply, Installation, commissioning of Water Cooler fully stainless steel, electric driven single phase 240 volt, 50 HZ, having approx storage and nominal cooling capacity 60/120 Litres complete all as specified and directed.
Supply, Fixing, testing and commisioning of desert cooler electric driven single phase, 50 Hz, 230 V, and having nominal air flow capacity of 6000 CUM per hour or nearest size complete all as specified and directed.
Supply and fix voltage stabilizer for automatic operation , single phase naturallly air cooled indoor type & designed for input variation between 170 v to 270 v with output voltage stabilised at 230 V with accuracy + 2.5% and capacity 3 KVA complete all as specified and directed.
Supply and fix voltage stabilizer for automatic operation , single phase naturallly air cooled indoor type & designed for input variation between 170 v to 250 v with output voltage stabilised at 230 V with accuracy + 2.5% and capacity 1 KVA complete all as specified and directed.
GEYSER Supply and fix Electric Water heater, storage type, steel body with Glass lined coated (inner body copper outer body –ABS), inner tank and heating element upto 2 KW capacity 25 litres, BEE 5 star rated complete with all accessories such as safety valve, thermotate, NRV, connection piece etc as required complete all as specified and directed.
Supply and fix Electric Water heater, storage type, steel body with Glass lined coated (inner body copper outer body –ABS), inner tank and heating element upto 2 KW capacity 50 litres, BEE 5 star rated complete with all accessories such as safety valve, thermotate, NRV, connection piece etc as required complete all as specified and directed.
TELE COMMUNICATION Rigid non-metallic PVC conduit 25 mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed.
Rigid non-metallic PVC conduit 20 mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed.
M & L for PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 100 mm x 100 mm and 50 mm deep complete all as specified and directed.
Submain wiring with two single core 2.5 sqmm copper conductor, PVC insulated, multistranded, unsheathed cable ISI marked drawn in 20 mm dia PVC conduits and conduit fittings complete (concealed type) in wall surface / ceiling for sub main connection including 2.5 sqmm PVC insulated multistranded unsheathed copper conductor used as earth wire to common earth and connection to earth dolly complete all as specified and directed. Note: - Two single core 2.5 sqmm copper conductor, one run PVC conduit and one run of 2.5 sqmm earth wire shall be considered & measured as one unit.
Submain wiring with two single core 4 sqmm copper conductor, PVC insulated, multistranded, unsheathed cable ISI marked drawn in 20 mm dia PVC conduits and conduit fittings complete (concealed type) in wall surface / ceiling for sub main connection including 4 sqmm PVC insulated multistranded unsheathed copper conductor used as earth wire to common earth and connection to earth dolly complete all as specified.(For connection to flood light) Note:- Two single core 4 sqmm copper conductor, one run PVC conduit and one run of 2.5 sqmm earth wire shall be considered & measured as one unit.
Submain wiring with two single core 6 sqmm copper conductor, PVC insulated, multistranded, unsheathed cable ISI marked drawn in 20 mm dia PVC conduits and conduit fittings complete (concealed type) in wall surface / ceiling for sub main connection including 6 sqmm PVC insulated multistranded unsheathed cop-per conductor used as earth wire to common earth and connection to earth dolly complete all as specified and directed. (Note:- Two single core 6 sqmm copper conductor, one run PVC conduit and one run of 6 sqmm earth wire shall be considered & measured as one unit .
Submain wiring with two single core 10 sqmm copper conductor, PVC insulated, multistranded, unsheathed cable ISI marked drawn in 25 mm dia PVC conduits and conduit fittings complete (concealed type) in wall surface / ceiling for sub main connection including 10 sqmm PVC insulated multistranded unsheathed cop-per conductor used as earth wire to common earth and connection to earth dolly complete all as specified and directed. (Note:- Two single core 10 sqmm copper conductor, one run PVC conduit and one run of 10 sqmm earth wire shall be considered & measured as one unit.
S & F of Gun Metal gate valve of 80 mm bore cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions complete all as specified and directed.
VEE SONS BUILDERS PVT LTD
Akrati Technimont Limited
M/s Madan Lal Bansal and Co. Contractors Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid