SUPERINTENDING ENGINEER
33/11 KV SUBSTATION KOYAL ENCLAVE GDA BHOPURA GZB
RENOVATION AND PROTECTION WORK OF 33/11 KV SUBSTATION
2024_PVVNL_981735_1
T-34/W/EDC/2024-25
Open Tender
Electrical Works
Item Wise
365 days
EDD-I, II, III LONI
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SUPERINTENDING ENGINEER EDC LONI
₹24,000
Yes
27 Mar 2025
9 Dec 2024
27 Dec 2024
9 Dec 2024
27 Dec 2024
9 Dec 2024
Amount
Cartage of PCC Pole & ST Pole 8.5/9/11/13 Mtr. Long From Central store GZB/Shahibabad JE Store (Dist.) to site of work including loading unloading of both ends. ( Distance up to 0-60 km.)
cartage of Other Line Material (Other then Pole) ACSR Dog Conductor, ACSR Rabbit Conductor, ACSR Weasel Conductor, 33 KV Cross Arm, 33 KV Polymeric Pin insulator, 33 Polymeric Disc insulator, 33 KV Cable Box O/D 3x300 SQMM, 33 KV stay set 20x1800MM, Stay wire 7/8 SWG, MS Earthing Rod 2540x20 MM, 11 KV Cross Arm, LT Insulator, 11 KV Polymeric Pin Insulator, 11 KV Polymeric Disc insulator, Stay Set, MS Channel 100x50x6 MM, MS Angel 65x65x6 MM, 11 KV HT Cable 3x185 SQMM XLPE, 11 KV HT CableBox 3x185 SQMM O/D, Stay wire 7/10 SWG, 11 KV VCB O/G CTR 200/100/5A. 350 MVA(1250 Amp), 33 KV BUS Isolator 800A, 33 KV LINE Isolator 800A, Battery charger 24 volt, Battery Set 24 volt from Central Store Gzb./Shahibabad JE Store (Dist.) to site of work including loading unloading of both sides(. ( Distance up to 0-60 km.)
Excavation of Foundation pit in Normal Soil/Soft and Hardsoil Rock and its back filing and leveling Erection of Single pole with PCC Pole/ ST Pole encluding Fixing of all accessories like all types of MS Angel/MS Channel and brackets, cross arm, All types Disc. and Pin Insulator & LT Insulator etc. (fully dressed) including MS galvanised fabricated items, after digging of a suitable size pit for each pole. Work shall be done as per RESPO specification. Single PCC Pole 8.5 Mtr. Long/ST Pole /9/11/13 Mtr. Long.
Concreting /Grouting of PCC Pole /ST Pole 8.5/9/11/13 Mtr. Long of support up to RESPO norms level including back filling and ramming work & muffing(on STP Poles) etc. shall be done as per RESPO specification.
Erection, Fixing of stay rod 16x1800 mm after digging of a suitable size pit shall be done as per RESPO specification including fixing of stay wire clamp and nuzzling etc with all accessories related to concern work.
Grouting of stay set with GI wire including execavation of stay pit, concreating, installation of all accessories including stay clamp, stay insulator, anchor plate, nut & bolts complete as per technical specification and RESPO drawing.
Earthing with M.S. Earth Rod 2540x40 mm long including driving of M.S. Rod 1 Mtr. Apart from support 0.5 Mtr. Below ground level and connecting with support with the help G.I wire No. 6 SWG.
Laying, Sagging, Binding, and jumpring etc. Of ACSR Weasel Conductor on the pole as per RESPO specification and as per direction of engineer in charge it includes cost of labor, T&P Carrier etc. Prepared for proper completion of work.
Laying, Sagging, Binding, and jumpring etc. Of ACSR Dog Conductor on the pole as per RESPO specification and as per direction of engineer in charge it includes cost of labor, T&P Carrier etc. Prepared for proper completion of work.
Carriage of 11 KV VCB O/G CTR 200/100/5A. 350 MVA(1250 Amp) & 11 KV VCB I/C CTR 600/300/5A. 350 MVA, 24 VOLT(1250 Amp) from Central store GZB / Shahibabad /JE Store (Dist.) to site of work including loading unloading of both ends. (Distance up to 0-60 Km.)
Mounting, Fixing & commisioning of 11 KV VCB O/G CTR 200/100/5A. 350 MVA(1250 Amp) & 11 KV VCB I/C CTR 600/300/5A. 350 MVA, 24 VOLT(1250 Amp) with all accessories.
Carrige of Pole Scrape, Damage Conductor, Old VCB, Battery Set, Battery Charger, Bus Isolator Scrape & Line Isolator Scrape from site of work to JE store (Dist.)/Store Centre including loading unloading of both ends with the help of Crane if required. (Distance up to 0-60)
Laying of 11KV Overhead XLPE Cable 3x185sqmm & support of stay wire 7/8 SWG & 7/10 SWG for hanging purpose of cable as per related Estimate & direction of Engineer incharge.
Fixing & commisioning of 11 KV Cable Box 3x185 XLPE SQMM O/D Properly as per RESPO Norms
Replacement & Fixing of 33 KV CABLE BOX Jointing Kit (O/D) 3X300 SQMM Properly.
Laying of 11KV Underground XLPE Cable 3x185sqmm Cable (HDD Method) with Laying of HDPE Pipe including Cost of HDPE Pipeas per related Estimate & direction of Engineer incharge.
Laying and Fixing of Guarding with G.I. Wire 6/8 SWG including all accessories
Installation & Fixing of 33 KV Bus Isolator 800 A with all accessories. Work shall be done as per RESPO specification.
Installation & Fixing of 33 KV Line Isolator 800 A with all accessories. Work shall be done as per RESPO specification.
Providing and fixing of Wooden Block with clamp & required nut and bolts
Installation & Fixing of Battery Set 24 Volt & Battery Charger 24 Volt with proper connectioning.
Providing & Fixing Clamps for ST Pole/Pcc Pole.
Providing & Fixing of Alluminum lugs 8MM with nuts and bolts for earthing
Providing & Fixing Danger Board with Clamp.
Providing & Fixing of Barbed wire
Providing & Fixing of Different sizes of nuts and bolts for different type of clamps with washers of best quality as per requirement
Providing Sp. Pipe earthing of 5 MVA & 10 MVA Power T/F pf capacity at UECD-II by using B-class. GI Pipe of 1.5" dia and making hand pipe type earth boring 60' deep. Neutral & Body separately with the help of GI Strip 50x5 mm duly galvaized shall be used. One earthing for T/F body and Second for Neutral both these points shall be connected to earth through GI strip (50x5mm) separately. All required materials shall be supplied by the contractor.
SANJAY POWER PROJECTS PVT LTD (BID ID -4803194)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .