Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.5 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹12.2 L+₹73,565.20 (6.39%)Rejected-Finance H NO 01 MADINA BAGH MEHJOOR NAGAR NEAR HOTEL RAFADA SRINAGAR 190015 J K | BUDGAM | JAMMU AND KASHMIR | 190015 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹13.1 L+₹1.6 L (14.0%)Rejected-Finance | L3 | Rejected-Finance Other than lowest |
Tender Value
Refer Docs
Closing Date
7 Jul 2021, 6:00 pmClosed
GARRISON ENGINEER (AF) THOISE
GARRISON ENGINEER (AF) THOISE 19 FBSU, c/o 56 APO, PIN 937219
REPAIR/ REPLACEMENT OF INTERNAL WIRING, DBs, MCB, SUB MAIN WIRING, LED LIGHT FITTING, UG CABLE, LT CONTROL SWITCH GEAR/PANEL AND OTHER CONNECTED ITEMS AT BASE CAMP AREA UNDER GE (AF) THOISE
2021_MES_451764_1
GEAF/T-22/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
BASE CAMP UNDER GARRISON ENGINEER (AF) THOISE
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER (AF) THOISE
Exempted
13 Sept 2021
16 Jun 2021
9 Jul 2021
16 Jun 2021
7 Jul 2021
23 Jun 2021
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc and complete all as specified and directed at site by Engr-in-charge.
M&L for point wiring with 1.5 sqmm copper conductor FRLS (multistranded) PVC insulated and unsheathed electric cable 1100 volt (ISI Marked) with proper color coding in and incl PVC casing and caping and accessories (ISI Marked) with all fittings/accessories and incl PVC insulated and unsheathed electric cable 1100 volt 1.5 Sqmm FRLS (multistranded) copper conductor cable(green color) as continuous earth wire connected to common earth dolly incl hard PVC boards of required size and shape and fiitings etc covered with 3mm thick plastic laminated sheet (Make: Hylum) for one light point controlled by one,one way switch, and complete all as specified and directed at site by Engr-in-charge. Make of wire: Anchor/Polycab/Finolex/ Havells
All as srl item no 2.00 here in before, but for One 3 pin socket outlet, 5 Amps on the same board with other switches, and complete all as specified and directed at site by Engr-in-charge. Make of wire: Anchor/Polycab/Finolex/ Havells
All as srl item no 2.00 here in before, but for One 3 pin socket outlet, 5 Amps on independent board complete all as specified and directed at site by Engr-in-charge. Make of wire: Anchor/Polycab/Finolex./ Havells
All as srl item no 2.00 here in before, but 4.0 Sqmm copper conductor FRLS (Multistranded) PVC insulated and unsheathed electric cable 1100 volt (ISI marked) and 4.0 Sqmm copper conductor as continuous earth wire for 3 pin socket multipurpose 15 Amps on independent board, and complete all as specified and directed at site by Engr-in-charge. Make of wire: Anchor/Polycab/Finolex./ Havels
M&L for Switch socket combination 2 in 1, 5 A flush type , ( Box Type) and complete all as specified and directed at site by Engr-in-charge. Make: Cona/SSK/Leader/ Anchor
M&L for Switch socket combination, 3 pin 16 Amps, 240 volts flush type and complete all as specified and directed at site by Engr-in-charge. Make: Cona/SSK/Leader/ Anchor
S&F of Switch piano, flush type single pole, one way 5 Amp, and complete all as specified and directed at site by Engr-in-charge. all as spfd and directed. Make: Cona/SSK/Leader/Anchor
M&L for Ceiling rose, 3 phase/PVC/ polycarbonate, isolated body, 65x50 mm, 3 terminal to be fixed on PVC block, and complete all as specified and directed at site by Engr-in-charge. Make: Cona/SSK/Leader/Anchor
M&L for Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings, and complete all as specified and directed at site by Engr-in-charge. Make :Cona/SSK/Leader/ Anchor
S&F in replacement decrorative ultra slim aluminium square profile LED light fixture with high lumen output with extruded polycorbonate environment friendly energy efficent LED light fitting complete with 1x 22 Watt including connecting electrically to ceiling rose using cord flexible 3 core PVC insulated over all sheathed with flexible copper conductor of size 1.5 sqmm, and complete all as specified and directed at site by Engr-in-charge. Make:- PHILIPS/Bajaj/ Wipro/Syska/ Havells
Replacement of sheet metal enclosures (factory made) for distribution board, single door when MCBs are to be used , single pole and neutral , 240 volts, 4 way with 200 Amps, rated bus bar, and complete all as specified and directed at site by Engr-in-charge. Make : Legrand/Havells/ Bajaj/C&S
Replacement of sheet metal enclosures (factory made) for distribution board, double door when MCBs are to be used , single pole and neutral , 240 volts, 8 way with 200 Amps, rated bus bar, and complete all as specified and directed at site by Engr-in-charge. Make : Legrand/Havells/ Bajaj/C&S
Replacement of sheet metal enclosures (factory made) for distribution board single door when MCBs are to be used, Triple pole and neutral, 415volts, 4 way with 20 Amps, reted bus bar, and complete all as specified and directed at site by Engr-in-charge. Make : Legrand/Havells/ Bajaj/C&S
Replacement of MCB SP 6 to 32 Amps, 240 volts, 16 KA C curve complete all as specified & directed by Engr-in-Charge. Make : Legrand/Havells/ABB/ C&S
Replacement of MCB TPN 63 Amps, 240 volts 16 KA C curve complete all as specified & directed by Engr-in-Charge. Make : Legrand/Havells/ABB/ C&S
Replacement of MCB SPN 32 Amps, 240 volts 16 KA C curve Complete all as specified & directed by Engr-in-Charge. Make : Legrand/Havells/ABB/C&S
Replacement of protected extention box with with 2 No Luminous 6 Amp Switch with 2 No 6 Amp Multi sockets complete all as specfied and directed by Engr-in-Charge. Make : C&S/ Bajaj/Havells
Replacement of protected extention box with with 2 No Luminous 6 Amp Switch with 3 No 6 Amp Multi sockets complete all as specfied and directed by Engr-in-Charge. Make : C&S/ Bajaj/Havells
Supply & Fixing in repair of sub main wiring with two runs of single core 4.0 Sq mm PVC insulated sheathed stranded copper conductor 650 / 1100 V grade with colour code and one run of 4.0 Sq mm ( 22 / 0.3 mm ) single core PVC insulated copper conductor green colour cable as earth continuity conductor drawn in and including PVC casing and caping of suitable size with all necessary fixture/accessories, and complete all as specified and directed at site by Engr-in-charge. Note :Two runs of 4.0 Sqmm copper cable,one run of earth wire of 4.0 Sqmm copper cable shall be measured & paid as one length.
Replacement of service wire of Aluminium conductor of size 6 Sqmm 2 core complete all as specfied and directed by Engr-in-Charge. Make : Havells/Polycab/Finolex
Replacement of service wire of Aluminium conductor of size 10 Sqmm 2 core complete all as specfied and directed by Engr-in-Charge. Make : Havells/Polycab/Finolex
Replacement of 1.5 Sqmm Copper cable single core complete all as specified and directed by Engr-in-Charge. Make : Polycab,finolex,Anchor
Supply and fix Led new adore 07 W B22 CDL ball Lamp complete all as specified and directed by Engr-in-Charge. Make : Havells cat Part No LHLDERUEML8X007 or equivalent in Wipro/ Syska
Replacement of 2.5 Sqmm Copper cable single core complete all as specified and directed by Engr-in-Charge. Make : Polycab,finolex,Anchor
Replacement of 35 Sqmm Copper cable single core complete all as specified and directed by Engr-in-Charge. Make : Polycab,finolex,Anchor
Replacement of 4.0 Sqmm Copper cable single core complete all as specified and directed by Engr-in-Charge. Make : Polycab,finolex,Anchor
Replacement of 6.0 Sqmm Copper cable single core complete all as specified and directed by Engr-in-Charge. Make : Polycab,finolex,Anchor
Replacement of XLPE insulated ( Heavy Duty) electric cable with copper conductor working voltage of 1100 Volt grade of size 6 Sqmm , 3 core unarmoured complete all as specfied and directed by Engr-in-Charge.
Replacement of XLPE insulated ( Heavy Duty) electric cable with copper conductor working voltage of 1100 Volt grade of size 4 Sqmm , 3 core unarmoured complete all as specfied and directed by Engr-in-Charge.
Supply only Insulation tape Roll of Size 20 MMx25 Mtr complete all as specfied and directed by Engr-in-Charge.
S& F in replacement Call Bell Ding Dong type complete all as specfied and directed by Engr-in-Charge.
Replacement of on load change over switch 400 Amp complete all as specfied and directed by Engr-in-Charge.
Replacement of on load change over switch 100 Amp complete all as specfied and directed by Engr-in-Charge.
M&L for MCCB 250 AMP 4 Pole adjustable type complete all as specified and directed by Engr-in-Charge. Make : L&T/Havells/Legrand/Schneider
M&L for MCCB 200 AMP 4 Pole adjustable type complete all as specified and directed by Engr-in-Charge. Make : L&T/Havells/Legrand/Schneider
Supply and Laying XLPE insulated Armoured LT heavy duty electrical cable 1100 Volts grade with Aluminium conductor of size 16 Sqmm 4 core complete all as specfied and directed by Engr-in-Charge.
Supply and Laying XLPE insulated Armoured LT heavy duty electrical cable 1100 Volts grade with Aluminium conductor of size 25 Sqmm 3.5 core complete all as specfied and directed by Engr-in-Charge.
Supply and Laying XLPE insulated Armoured LT heavy duty electrical cable 1100 Volts grade with Aluminium conductor of size 35 Sqmm 3.5 core complete all as specfied and directed by Engr-in-Charge.
Excavation, in trenches not exceeding 1.5 mtr wide and not exc 1.5 mtr in depth for laying under ground cable n.exc 10 Sqm on plan and n.exc 1.5m in depth in in hard / dense soil and getting out complete all as specified and directed by Engr-in-Charge.
Returning, filling in, including spreading leveling watering and well ramming in layers not exc 25 cm thick all as specified and directed by Engr-in-Charge.
Removal of surplus excavated material to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
Sand cushioning to under ground cable with dry sand locally available 8cm thick before laying the cable and 15 cm above the cable, stretching and testing of cable complete all as specified and directed by Engr-in-Charge. Note:- (i) Excavation and earth work to be measured and paid for separately (ii) Thickness of 18 cms after punning down shall be considered for payment
M&L for PCC cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm laid Flat in trenches over the cable with length 250mm perpendicular to the direction of cable, adjacent/ abutting each other, complete all as specified and directed by Engr-in-Charge. Note:-Excavation and earth work to be measured and paid for separately
S&F fabrication of panel board double door outdoor type of size 1.0mtr x 0.50mtr x 0.90mtr and 3.15mm MS sheet duly powder coated complete with angle iron 50mmx50 mm frame CPRI approved including 200 Amp copper basbar, 160 Amp 4 Pole MCCB, connecting with bus bar, complete all as specified and directed by Engr-in-Charge.
Earthing complete with copper plate electrode 600x600x3.15mm thick electrode burried directly in ground not less than 3.0 mtr deep below normal ground level with top edge of earth plate not less than 2.5 mtr below normal ground level connected to and including and 20x3 mm copper strip as earth lead by means of bolt ,nuts, check nuts, and washers of stainless steel and duly welded incl PCC pit in PCC 1:2:4 type B-I angle iron 40x40x3mm frame, pit in PCC 1:2:4 type B-I cover 40mm reinforced with XPM weight not less than 4 Kg/Sqm and 6mm dia bar handle, excavation and earth work in any type of soil, charcoal dust and salt light grade GI watering pipe 20mm bore with funnel and wire mashand medium grade GI protection pipe 40mm bore and earth wire up all as shown in electrical plate No 3 of MES SSR- Part-I all as directed and specified by Engineer-in-charge. Note:- (i) Water pipe shall be provided in slanting position. (ii) On testing after completion of the job if the desired earth resistance is not obtained then the contractor shall redo the earthing without incurring any extra cost to the government. No claim whatsover shall be admissible to the contractor on this account again.
M/S BALI CONSTRUCTIONS
M/S ADHISH ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .