Loading…
Loading…
Tender Value
₹2.5 Cr
EMD Value
₹4.9 L
Closing Date
28 Apr 2026, 11:00 amClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (WMS)
ELECTRICAL
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or "V" whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Electrical License: - Tenderer should have valid 'A' Class Electrical Contractor License issued by electrical inspector of any State Government/Union Territory of India. If 'A' Class Electrical Contractor License has expired, tenderer should submit receipt of renewal of 'A' Class Electrical Contractor License issued by electrical inspector of License issuing authority as mentioned above. At the time of contract agreement, contractor must submit valid 'A' Class Electrical Contractor License issued by electrical inspector of License issuing authority as mentioned above else contract will be terminated without any information to successful tenderer. In case of non-submission of valid 'A' Class Electrical Contractor License / receipt of renewal of electrical contractor license along-with offer, their offer will not be considered VALID.
Similar Nature of Work: - (i) Installation, testing & commissioning of LT panels. (ii) Installation, testing & commissioning of HT panels. (iii) Installation, testing & commissioning of Electrical Sub-stations. (iv) Installation, testing & commissioning of transformers. (v) Installation, testing & commissioning of HT switch gears. (vi) Installation, testing & commissioning of LT switch gears.
15 conditions
All the bidders/tenders should ensure that they are GST complaint and their quoted tax structure/rates are as per GST Law. (Please upload certificate of GSTIN registration)
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Rights Of The Railway To Deal With Tender: The authority for the acceptance of the tender will rest with the Railway. It shall not be obligatory on the said authority to accept the lowest tender or any other tender and no tenderer(s) shall demand any explanation for the cause of rejection of his/their tender nor the Railway to assign reasons for declining to consider or reject any particular tender or tenders.
If the tenderer(s) deliberately gives / give wrong information in his / their tender or creates / create circumstances for the acceptance of his / their tender, the Railway reserves the right to reject such tender at any stage.
Provision of Installation of Air Conditioning Unit in Different offices at Mechanical Workshop Gorakhpur.
EL-MWS-GKP-2026-27-01
EL-MWS-GKP-2026-27-01
Open
Works - General
3 Months
Gorakhpur, Uttar Pradesh
₹0
₹4.9 L
28 Apr 2026
4 Apr 2026
14 Apr 2026
37 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 2,46,66,062.22 | ||
| — | 75.00 | — | — | ||
| Supply Installation Testing and commissioning of Variable Refrigerant (VRF)/VRF modular type air Conditioning System of Aggregate Tonnage 75 Ton Comprises of Outdoor Units (Hot & Cold) and Indoor unit of Suitable Size & type with all accessories Piping (Refrigerant & Drain) Wiring (Control Transmission & Controller), Charging of Refrigerant etc as per site requirement and complete in all respect. It should consist of High Efficiency DC Inverter Scroll Compressor with outstandingly precise Control Technology of 0.1 Hz increments inverter frequency. The units shall be Suitable to operate upto 52 Deg C Ambient Temperature. The System should be complete in all respect as per attached technical Specification. (1 unit= 1 Ton) | — | — | — | 57,04,066.5 | |
| — | 1000.00 | — | — | ||
| Supply, Recessing and fixing of PVC Conduit Pipe 25 mm (Medium) | — | — | — | 45,000 | |
| — | 200.00 | — | — | ||
| Supply, Recessing and fixing of Flexible PVC Conduit Pipe 25 mm (Medium) | — | — | — | 7,070 | |
| — | 850.00 | — | — | ||
| Supply of PVC Type C Insulated having FR Properties copper conductor single core cable 4 sq mm. | — | — | — | 31,450 | |
| — | 580.00 | — | — | ||
| Supply of PVC Type C Insulated having FR Properties copper conductor single core cable 10 sq mm. | — | — | — | 58,580 | |
| — | 450.00 | — | — | ||
| Supply of PVC Type C Insulated having FR Properties copper conductor single core cable 16 sq mm. | — | — | — | 53,631 | |
| — | 800.00 | — | — | ||
| Supply of 4Cx25 Sqmm. PVC Insulated PVC Sheathed unarmoured Round Shaped Copper Cable. | — | — | — | 12,00,000 | |
| — | 1000.00 | — | — | ||
| Laying of 4Cx400 Sqmm Aluminum cable in HDPE Pipe. (Cable will be supplied by railway) | — | — | — | 12,21,460 | |
| — | 800.00 | — | — | ||
| Supply & Laying of Polyamide Flexible Conduit Pipe Size 48 mm Inner Dia as per site requirement. | — | — | — | 2,96,000 | |
| — | 3.00 | — | — | ||
| Supply, Fixing, Installation & testing of LT Kiosk Outdoor Type 415 Volt 50 Hz With 400 Amp. TPN 4 Way Copper Bus Bar Size 40x10 mm. | — | — | — | 41,700 | |
| — | 8.00 | — | — | ||
| Supply, Fixing, Installation & Testing of 12 Way Double Door Distribution Board | — | — | — | 16,524.88 | |
| — | 8.00 | — | — | ||
| Supply, Fixing, Installation & Testing of 125 Amp. 4 Pole Isolator. | — | — | — | 14,336 | |
| — | 38.00 | — | — | ||
| Supply, Fixing, Installation & Testing of 25 Amp.1 Pole MCB. | — | — | — | 9,804 | |
| — | 38.00 | — | — | ||
| Supply, Fixing, Installation & Testing of 25 Amp. MCB protected Power Unit Comprising of Suitable rating of Plug Socket 2 Pole MCB, Starter & Polycarbonate Board complete in all respect. | — | — | — | 44,219.84 | |
| — | 1.00 | — | — | ||
| Supply, fixing Installation & Testing of LT Panel With RYB Indicator and digital multifunction meter on Both incoming & outgoing feeder having following features; Incoming 800 Amp 4 Pole 50 kA ACB Rack in Rack Out EDO type Ics=100% Icu=100% Icw having LSIG Protection =2 nos.(Main+spare) Outgoing-- 400 Amp.4 Pole 35 kA MCCB=3 Nos., 250 Amp 4 Pole 35 kA MCCB=2 Nos., 200 Amp. 4 pole 35 kA MCCB =2 Nos., 125 Amp. 4 pole 35 kA MCCB=2 Nos. Copper Bus Bar Size-80x10 mm for 800 Amp. Note- LT Panel should be incorporated with 14 tank processed, IEC 61439-1&2 and type test Assembly. | — | — | — | 21,86,805 | |
| — | 3.00 | — | — | ||
| Supply of Desktop Computer Gen/16 GB DDR RAM 512 GB INTEL I5(1334) | — | — | — | 2,42,490 | |
| — | 1.00 | — | — | ||
| Supply, fixing Installation & Testing of LT Panel with RYB Indicator and digital multifunction meter on Both incoming & outgoing feeder having following features:- Main Incomer 2000 Amp 4 Pole 50 kA ACB=4 nos. Bus Coupler-2000 amp.4 pole 50 kA ACB=02 nos. Outgoing -800 Amp.4 Pole 50 kA ACB =9 Nos. 100 Amp.4 Pole 35 kA MCCB =1 Nos. Spare - 800 Amp. 4 Pole 50 kA ACB =3 Nos. Copper Bus Bar Size-200X10 mm for 2000 Amp. Note- LT Panel should be incorporated with 14 tank processed, IEC 61439-1&2 and type test assembly. | — | — | — | 1,34,60,035 | |
| — | 22.00 | — | — | ||
| Dismantling of Unused Poles & Overhead Conductors in Various Location of Mechanical Workshop Gorakhpur. | — | — | — | 32,890 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocumentACInstallation.pdf Tender Document
ATTACHMENT
I_CT_GCC-
ATTACHMENT
ACS-01to11_merged.pdf
ATTACHMENT
TenderDocumentACInstallation.pdf
ATTACHMENT
GCC_April-2022_2022_CE-I_CT_GCC-2022_POLICY_27_04_22.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .