Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.7 CrAccepted-AOC | ₹6.7 Cr Quoted ₹6.9 Cr | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹9.4 Cr+₹2.5 Cr (35.8%)Rejected-AOC | ₹9.4 Cr+₹2.5 Cr (35.8%) | L2 | Rejected-AOC Other than lowest |
| 3 | L3₹10.0 Cr+₹3.1 Cr (44.3%)Rejected-AOC | ₹10.0 Cr+₹3.1 Cr (44.3%) | L3 | Rejected-AOC Other than lowest |
| 4 | L4₹10.0 Cr+₹3.1 Cr (44.5%)Rejected-AOC PROP ZISHAN ALI ADARSH NAGAR NEW BUS STAND RAMGARH CANTT RAMGARH | ₹10.0 Cr+₹3.1 Cr (44.5%) | L4 | Rejected-AOC Other than lowest |
| 5 | Rejected-Technical | - | - | Rejected-Technical Banned by CENC |
Tender Value
₹6.5 Cr
EMD Value
₹6.5 L
Closing Date
7 Sept 2020, 6:00 pmClosed
CE 31 Zone
HQ CE 31 Zone C/o 56 APO
CONSTN OF LEFT OVER WORK KLP ACCN FOR ZONAL WKSP AT SMS
2019_MES_266971_5
CONSTRUCTION OF LEFT OVER WORK OF KLP ACCN FOR ZON
Open Tender
Civil Works
Lump-sum
730 days
Srinagar
Class A Cat a i
6 documents required · 6 mandatory
₹3,000
GE 970 EWS
₹6.5 L
Yes
7 Oct 2020
5 Aug 2020
9 Sept 2020
5 Aug 2020
7 Sept 2020
21 Aug 2020
5 Aug 2020 - 13 Aug 2020
Amount
Sch 'A' Part-I (Building Works) Note : This schedule is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
LUMPSUM/ OTHER PRE-PRICED PROVISIONAL SCHEDULES OF WORKS
Completion of incomplete items of Construction of block of education building RCC framed construction with brick masonry single storey including platform, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Completion of incomplete items of Construction of block of building for officer’s Mess RCC framed construction with brick masonry single storey including porch, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Completion of incomplete items of Construction of block of building for Single Officer’s accommodation RCC framed construction with brick masonry single storey complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Completion of incomplete items of Construction of block of building for Single JCOs accommodation including scooter shed, RCC framed construction with brick masonry double storey including ramp, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Construction of block of building for single JCOs accommodation including scooter shed, RCC framed construction with brick masonry single storey including ramp, complete all as specified and as shown on drawings
Construction of block of building for JCOs Mess, RCC framed construction with brick masonry panel single storey including platform, complete all as specified and as shown on drawings
Construction of block of building for Religious Institute RCC framed construction with brick masonry single storey including platform, complete all as specified and as shown on drawings
Completion of incomplete items of Construction of block of building for ORs institute RCC framed construction with brick masonry single storey, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Construction of block of building for security control room RCC framed construction with brick masonry single storey, including Verandah and platform, complete all as specified and as shown on drawings
Completion of incomplete items of Construction of block of building for Tradesman Shop RCC framed construction with brick masonry single storey, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Completion of incomplete items of Construction of block of building for Turbo charger room RCC framed construction with brick masonry single storey, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Construction of block of building for Drying and Ironing room RCC framed construction with brick masonry single storey, complete all as specified and as shown on drawings
Completion of incomplete items of Construction of bicycle cum scooter stand RCC framed construction with brick masonry single storey, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Completion of incomplete items of Construction of open garage RCC framed construction including approns, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Completion of incomplete items of Construction of block of building for Cook House and dining hall RCC framed construction with brick masonry single storey, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Completion of incomplete items of Construction of block of building consisting of Garage and servant quarters for single officers accommodation RCC framed construction with brick masonry single storey, including ramps, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Construction of block of building for Guard room RCC framed construction with brick masonry single storey, complete all as specified and as shown on drawings
Construction of block of building for opto electronic laboratory RCC framed construction with brick masonry single storey, complete all as specified and as shown on drawings
Completion of incomplete items of Construction of block of building for servant quarters RCC framed construction with brick masonry single storey, including platform, complete all as specified, shown on drawings and the details given in Annexure to the Sch A Part-I forming part of contract agreement .
Construction of Dhobi Ghat 4 stones, complete all as specified and as shown on drawings.
Construction of incinerator, complete all as specified and as shown on drawings.
Construction of block of sentry post RCC framed construction with brick masonry single storey, complete all as specified and as shown on drawings
Construction of transformer shed (15 Sqm), complete all as specified and as shown on drawings
Schedule 'A' Part-II (INTERNAL WATER SUPPLY WORKS) carried forward from pre-priced Schedule.
Sch 'A' Part-III, SEC-I (INTERNAL ELECTRIFICATION WORKS) carried forward from pre-priced Schedule.
Schedule 'A' Part-III, SEC-II (INTERNAL ELECTRIFICATION WORKS) Note : This schedule is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply and fixing fluorescent tube light fittings T-5, 1x28 watt, 230 V, surface / wall mounted type, white powder coated CRCA sheet housing complete with tube -01 No, bipin holders with replaceable electronic ballast having PF not less than 0.9, connector block etc, Complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size, complete all as specified and directed. Make: Surya Cat Part No. SDB128T5EBI/P401, Havells Cat Part No LHIT01128050 and Philips Cat Part No TMS 112M1xTL5-28 WEBT
Supply and fixing fluorescent tube light fittings T-5, 2x28 watt, 230 V, surface / wall mounted type, white powder coated CRCA sheet housing complete with tube 02 Nos, bipin holders with replacement electronic ballast having PF not less than 0.9, connector block etc, complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size ,complete all as specified and directed. Make: Surya Cat Part No. SUB228T5EBI/P3, Havells Cat Part No LHIT01228050 and Philips Cat Part No TMS 122M2xTL5-28 WEBT
Supply and fixing 1x18 watt CFL retro fit type having PF not less than 0.9 complete all as specified and directed.
Supply and fixing CFL light fittings 1x11 W, 230V, 50Hz attractive wall mounted mirror fitting with metallic channel and white reflector suitable for 1x11 W CFL having PF not less than 0.9, lamp holder, connectors block etc complete with all accessories prewired and including connecting up with suitable twisted flexible copper conductor cable, complete all as specified and directed.
Supply and fixing CFL light fittings 1x15 W, 230V, 50Hz wall mounted Decorative Polycarbonate fitting model City 1 including retrofit 1x18 W CFL having PF not less than 0.9, lamp holder, connections block etc complete with all accessories prewired and including connecting up with suitable twisted flexible copper conductor cable, complete all as specified and directed.
Supply and fixing CFL light fittings 2x18 W, 230V, 50Hz surface mounted mirror optics luminaries housing in CRCA sheet steel and expoy powder coated white with designed metallised louvers (Parallite P-5) including 2x18 W CFL having PF not less than 0.9, lamp holder, connectors block etc complete with all accessories prewired and including connecting up with suitable twisted flexible copper conductor cable, complete all as specified and directed
Supply and fixing 1x85 W street light fitting epoxy black powder coated sheet steel housing, clear acrylic cover with anodized aluminum reflector including 1x85 W retrofit CFL PF not less than 0.9 mounted on wall with GI pipe light grade 40mm dia of 1.2 mtr lenght bend to shape with 2 Nos of FI clamp 50x6mm with the suitable size nuts, bolts and making the connections from ceiling rose to fitting complete with all accessories, complete all specified and directed. Make: Surya Cat Part No SUL85CFRFALDDE4002, Havells Cat Part No lHRC 24185099 or Bajaj Cat part No BJSLF85RFCFLE27
Supply and fixing MCCB four pole 415V, 50 Hz, 25KVA ‘C curve of rating (125A), complete all as specified and directed.
Supply and fixing MCB four pole 415V, 50 Hz, 10 KA ‘C’ curve of rating (100A), complete all as specified and directed.
Supply and fixing MCB TPN 415V, 50Hz, 10 KA ‘C’ curve of rating (40A), complete all as specified and directed.
Supply and fixing MCB SPN 240V, 50Hz, 10 KA ‘C’ curve of rating (40A), complete all as specified and directed.
Supply and fixing MCB SPN 240V, 50Hz, 10 KA ‘C’ curve of rating (50A), complete all as specified and directed.
Supply and fixing MCB SPN 240V, 50Hz, 10 KA ‘C’ curve of rating (63A), complete all as specified and directed.
Supply and fixing MCB SPN 240V, 50Hz, 10 KA ‘C’ curve of rating (6 -32A), complete all as specified and directed.
Supply and fixing MCB SPN 240V, 50Hz, 10 KA ‘C’ curve of rating (0.5-5A), complete all as specified and directed.
Supply and fixing MCB SP 240V, 50Hz, 10 KA ‘C’ curve of rating (40A), complete all as specified and directed.
Supply and fixing MCB SP 240V, 50Hz, 10 KA ‘C’ curve of rating (50A), complete all as specified and directed
Supply and fixing MCB SP 240V, 50Hz, 10 KA ‘C’ curve of rating (6 -32A), complete all as specified and directed
Supply and fixing MCB SP 240V, 50Hz, 10 KA ‘C’ curve of rating (0.5-5A), complete all as specified and directed
Supply and fixing plug and socket DBs TPN powder coated sheet metal deep drawn DBs with plug and socket or capacity 30 Amp with TP MCB of 30 Amp, 10 KA capacity including insulated neutral link adjustable din rail and connecting links complete all as specified and directed.
Supply and fixing TV Socket outlet single, complete all as specified and directed
Supplying and fixing telephone socket with top connector, complete all as specified and directed.
M &L Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level, connecting to the Galvanised iron earth lead 4mm dia, by means of bolts, nuts, protected by provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 40x40x6mm with lugs 02 Nos. and with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering performated at bottom 1.75 metre long placed on top edge of earth plate, common salt and charcoal filling, test point made out of Bronze/ Gun metal with fixing arrangement, funnel, wire mesh and excavation/earth work in hard dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No 3 SSR 2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. Note:- The quoted rate of earthing shall be deemed to included cost of 7.5m long galvanised wire 4mm dia and protection pipe of 15mm bore medium grade, 20mm watering pipe Any variation in length shall be adjusted through deviation order based on SSR rates adjusted with quoted rates.
M &L Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx 3.15mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level, connecting to the copper earth lead strip 20 x 3mm by means of bolts, nuts, check nuts and washer of GI and earth strip protected by provision of GI pipe medium grade 40mm bore including provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 40x40x6mm with lugs 02 Nos. and with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt and charcoal filling, test point made out of Bronze/ Gun metal with fixing arrangement, funnel, wire mesh and excavation/earth work in hard dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No 3 SSR 2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. Note:- The quoted rate of earthing shall be deemed to included cost of 7.5m long copper strip 20x3mm and protection pipe of 40mm bore medium grade, Any variation in length shall be adjusted through deviation order based on SSR rates adjusted with quoted rates.
Supply and fixing factory made epoxy powder coated distribution board TPN 08 ways (VTPN DB) with metal door (IP43) protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for /universal mounting with and including 200 Amps bus bar, neutral bar standard DIN rail, each bar and cable ties for cable management. Top and bottom, removable gland plates and suitable for one four pole MCCB 125 Amps, 25 KA incomer 24 SP MCBs (or any combination of SP/TP MCBs) as outgoing, complete all as specified and directed. Note:- Outgoings to be measured paid separately.
Sch 'A' Part-IV ( Sewage disposal ) carried forward from pre-priced Schedule.
Sch 'A' Part-V, ( Protective work) carried forward from pre-priced Schedule.
Sch 'A' Part-VI, (Road, path culverts, hardstanding, prade ground and car parking) carried forward from pre-priced Schedule.
Sch 'A' Part-VII, (Area Drainage works) carried forward from pre-priced Schedule.
Schedule 'A' Part-VIII (Bore Well Works) Note : This schedule is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply, jointing, assembling and lowering and fixed in position 250mm nominal bore MS ERW ISI marked casing pipe having wall thickness 8mm as per IS-4270-1992 and jointing with electric arc welding, screwed and socket of size 250 x 8mm, with random length of pipe of 3 to 6 metre flat iron for over lapping duly welded for perfect jointing including cutting, threading, coupling and painting with two coats of bituminous paint on external surfaces of pipe upto entire depth below ground level complete all as specified and directed.
Supply, jointing, assembling and lowering and fixed in position 200mm nominal bore MS ERW (ISI marked) casing pipe having wall thickness 8mm as per IS-4270-1992 and jointing with electric arc welding, screwed and socket of size 200 x 8mm, with random length of pipe of 3 to 6 metre flat iron for over lapping duly welded for perfect jointing including cutting, threading, coupling and painting with two coats of bituminous paint on external surfaces of pipe upto entire depth below ground level complete all as specified and directed.
Development of bore well using 250 PSI compressed air and suitable capacity submersible pump set by pumping muddy water untill sand free clear water is obtained from the well or any CGWB approved method complete all as specified and directed.
Borewell cap size not less than 30cm long 15cm wide and 10 mm thick and of required dia MS pipe duly threaded internally fabricated out of suitable MS pipe and welded with MS strip both sides, complete all as specified and directed.
S&F MS bail plug of size 200mm bore 1m long 8mm thick complete all as specified and directed.
S&F MS reducer of size 250mmx200mmx8mm thick complete all as specified and directed.
Supply and packing Pea gravels of size 5mm to 8mm of approval quality all round and casing/slotted pipe up to the entire depth of bore hole upto ground level complete all as specified and directed.
S&F MS clamp in two flaps fabricated out of MS sheet 20mm thick 150mm wide and 1.75m length bend to shape to hold 200mm dia casing pipe with nuts, bolts and washers, etc suitable for 250mm dia casing pipe duly 2Nos hole drilled 25mm dia on each side, complete all as specified and directed.
Material and labour for Plain cement concrete 1:3:6 type C-1 (using 20mm graded stone aggregate) as in mass concrete finished even and fair without using extra cement including necessary form work complete all as specified and directed.
Supply and fixing Strata box made out of 20mm thick veneered particle board and 12 mm thick plywood with 25mm x 25mm aluminium anlgle 2mm thick base over all length 1200mmx750mmx100mm with front glass sheet sliding type cover with aluminium frame all around with 2 Nos key holes plates of size 40mmx25mmx3mm thick complete showing name of tube well location and strata sample with depth including a coat of synthetic enamel paint over a coat of wood primer complete all as specified and directed by Engr-in-Charge.
Supply, fixing and testing of Submersible pump set with submersible electric motor suitable for 4145 Volts, 3 phase, 50 Hz Ac supply suitable for lowering in 250mm dia bore well supplied and installed and capacity 6.5 LPS discharge at 140 meter head complete all as specified and directed.
Supply, connecting, lowering with column pipe including tieing with PVC lockable tie strip and testing of submersible cable with copper conductor stranded of size 6 Sqmm 3 Core complete all as specified and directed.
Supply and lowering column pipe galvanized ‘Heavy class’ complete and installed duly flanged both side with groove for placing of cables, welded with nut, bots and washers complete of size 50mm dia, complete ass as specified and directed.
Supply, installed, testing and commissioning centrifugal electric driven, pumping set complete suitable for 415 Volts, 3 phase 50 Hz, 7.5 HP with min 30 mtr head, complete all as specified and directed. Note:- (i) Pump shall be mounted on PCC platform of suitable size within overall cost quoted. (ii) Automatic star delta starter panel duly mounted on suitable angle iron frame of size 40x40x6mm including grouting and cable connection shall be carried out with in overall coast quoted. (iii) Temporary shed consisting of angle iron frame of size 40x40x6mm and AC sheet roofing to have minimum clearance all around complete all as shown in TD drawing shall be included in over all cost quoted.
Sch 'A' Part-IX, SEC-I (EXTERNAL WATER SUPPLY WORKS) carried forward from pre-priced Schedule.
Schedule 'A' Part-IX, SEC-II (EXTERNAL WATER SUPPLY WORKS) Note : This schedule is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply and fixing gun metal gate valves of size 50mm bore with operating iron wheel, flanged ends of class II, (ISI marked) including all jointing material such as rubber gaskets nuts, bolts and washers etc, complete all as specified and directed.
Supply and fixing cast iron non return valve with by pass arrangement of size 50mm bore with flanged ends of class PN 1.0 confirm to IS 5312/2004, (ISI marked) including all jointing material such as rubber gaskets nuts, bolts and washers etc, complete all as specified and directed.
Material and labour for 2 cut in position and threading both side for taking branch connection 20mm dia including earth work, tee, nipple, union and necessary GI fittings and taping existing pipe of required size for connection 20mm dia pipe complete all as specified and directed.t.
Material and labour for 2 cut in positon and threading both side for taking branch connection 25mm dia including earth work, tee, nipple, union and necessary GI fittings and taping existing pipe of required size for connection 25mm dia pipe complete all as specified and directed.
Material and labour for 2 cut in positon and threading both side for taking branch connection 50mm dia including earth work, tee, nipple, union and necessary GI fittings and taping existing pipe of required size for connection 50mm dia pipe complete all as specified and directed.
Dismantling of pipe off sizes and refixing the same after clearing complete all as specified and directed.
Supply and fixing 5000Ltrs capacity PVC rotational moulded polyethylene water storage tank (cylindrical vertical with closed top) ISI marked, hoisted on platform and fixed with inlet and outlet of 50mm bore GI medium grade tubing, complete all as specified and directed.
Sch 'A' Part-X, SEC-I (OIL FIRED HEATERS/RO PLANT/AC/STABILIZER) carried forward from pre-priced Schedule.
Schedule 'A' Part-X, SEC-II (OIL FIRED HEATERS/RO PLANT/AC/STABILIZER) Note : This schedule is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply, installation, testing and commission of oil fired heaters using HSD oil complete with SS combustion chamber and equipment automatic monoblock burner assembly with sequence controller, photo cell for flame failure HT transfer electrode, blower assembly, suitable digital temperature controller chimney, beyond roof level SS reflector ceramic coated heat exchanger built in oil storage tank with filter and analog level indicator etc and of capacity 25000 K cal/HR complete all as specified and directed. Note (a) A mild steel fuel tank of capacity 100 ltr as per design of manufacturer duly mounted on a raised platform made out of brick work and tank duly covered with CGI sheet roof including provision of fuel pipe from fuel tank to burner is also be provided within overall cost quoted. (b) Higher capacity model can be offered at no extra cost.
Supply, installation, testing and commissioning of commercial Reverse Osmosis System (RO, 100-120 Ltrs/hrs capacity or nearest higher size with suitable raw water and treated water storage tank of capacity 5000 ltr including all necessary arrangements for fixing/installations and electric connections from electric point and water connection for outlet raw water tank to RO and RO to inlet of treated water and storage tank. The plant shall be installed indoor and shall be able to operate in temperature range upto (-) 15 degree Celsius . Arrangement and piping of waste water disposal upto outside the building is including in the cost. The optput water has to be got tested from authorized rep and should meet the IS requirements of drinking water. Cost of testing is deemed to be included in the quoted rates. Any other item required to make the plant functional will also be provided by the contractor included in the rate functional will also be provided by the contractor included in the rate quoted. Make: RWT-ROS-007 Kent/Eureka Forbes/Usha Brita/Renuka.
Supply and installation of Electric Chimney 1200 Cum/hr product name canua suction 1160 Cum/hr, complete all as specified and directed. Make: Faber
Supply and installation of voltage stabilizer coper wound for automatic operation, single phase naturally air cooled and designed for input variation between 180 Volt to 275 Volt with output voltage stabilized at 230 Volt with accuracy + 2.5% and speed of correction 8 Volts per second and of capacity 5 KVA.
Supply, installation and testing air shower of over all size 200mm (wide)x1830mm(depth)x2050mm(height) suitable for capacity 2-3 person entry at a time with inside size 915mm(wide)x1730mm(depth)x2050mm(height) with door size 901mm(wide)x2040mm(Height) and cabinet made out of 20mm thick high quality commercial board line with white laminated sheet on all exposed. Surface painted from inside and door made out of aluminum anodized frame with transparent glass in including door closer on each side model AS-106 complete with 3 phase AC motor of 2 HP with blower assembly direct drive MS backward curved blade impeller statically and dynamically balanced complete all as specified and directed.
Supply and installation of air curtain of size 3’ wide made out of CRCA duly powder coated complete with balanced mortar blower (Plastic Blower) assembly suitable for velocity approximately 2000 FPM at outlet of nozzle. Air curtain are suitable for door height of 7’ complete all as specified and directed. Note of Srl item No. 101 & 102:- (a) Thermadyne or its equipments and other materials required for installation shall be included in quoted rates. (b) Cost of all electrical connection testing equipment’s and any other materials required for installations shall be included in the over all cost quoted.
Supply and fixing material pass box of size 915 x 915 x 915mm, complete all as specified and directed.
Sch 'A' Part-XI, SEC-I (External Electrification) carried forward from pre-priced Schedule.
Schedule 'A' Part-XI, SEC-II ((External Electrification) Note : This schedule is not estimated by MES and the estimated rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Supply, installation, testing and commissioning of Diesel Engine/driven generating set of capacity 20 KVA (16KW), 415 Volt, 0.8 PF, mounted on base platform with flexible coupling, 1500 RPM, alongwith sound prood enclosure (Acoustic Enclosure) designed for reducing the sound level to 75 dBA (average) IS 10001/10002 Part-10 as per approved CPCB norms and as per GSR 371(E) and 17.05.2002 with silent pipe a silence muffer covered with asbestos rope 25mm thick independently supported from Engine to outside of power house upto 1.00 mtr. Arm pad, foundation as per manufacturer’s design, cold starting kit, Battery start with suitable size of standard cables for connecting from DG Set to panel board (DG set shall be capable of operating in temperature range of (-20 degree C to 35 degree C) complete with and including the following:- (A) Prime Mover :- Diesel Engine of suitable capacity not less than 26.9 HP water cooled (radiator type), closed circuit as per IS-100001/10002 or ISO-3046 direct inject type with turbo charger. Make: Cummins India Ltd/Kirloskar. The DG set shall be capable of running 24 hrs. Engine shall be equipped with all standard fitting as per manufacturers recommendation and mounted on common base platform through flexible coupling with following accessories:- (a) RPM cum hours meter. (b) Battery charging ammeter. (c) Ignition key and starting with push button switch. (d) Lubricating oil pressure. (e) Mechanical Governer controlling.
(f) Toggle switch for idle running. (g) Oil temperature gauge. (h) Water temperature gauge. (j) Safety control (Trip) of the following:- (i) High water temperature. (ii) Low lubricant oil pressure. (iii) Over speed. (k) Lubricating oil heater to avoid freezing. (I) 12 Volts starting equipment comprising of the following:- (i) 1 Nos 12 Volts, 90 AH Batteries (Make-Exide type 25xnN 21 or Base/Amaron) (ii) Battery charging alternator with inbuilt regulator. (iii) Self Starter motor of suitable capacity. (iv) Battery leads (copper stranded cable) of suitable size with brass thimbles and terminals. (B) ALTERNATOR :- Alternator of capacity 20 KVA (16KW), 50 C/S, 415 Volts, 1500 RPM, 0.8 PF self excited self regulated, screen protected with self excited filled brush rotating fixed designed to be copied with above engine through flexible coupling,. The alternator shall be conforming to IS-13364
Note: The contactor shall produce a copy of approved certificate to authenticated the above from the OEM/OEAD. (E) Tool Kit:- Tool kit as supplied by the manufacturers alongwith the each DG set -01 set complete. (F) Maintenance Spares :- (i) Fuel filter element -02 Nos. (ii) Oil filter element -03 Nos. (iii) Element air cleaner outer -06 Nos. (iv) Element air cleaner inner -06 Nos. (v) V belt -02 Nos. (vi) Filter lubricant oil by pass -02 Nos. Note:- Quoted rates are deemed to be including the following:- (i) DG set shall be mounted on platform design given by manufacturer cost of which is included in overall cost. (ii) Manufacturers test certificate spare parts, catalog, manufacturers instructions and maintenance manual in original shall be supplied by the contractor with each DG set. (iii) The complete DG set shall be tested by rep of AO within overall cost quoted. All arrangements including POL shall be made by contractor. (G) DG sets shall be supplied alongwith acoustic original enclosure of the manufacture’s suitable for 20 KVA DG set as per CPCB norms.
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth plate not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised iron earth lead 4mm dia GI wire by means of bolts, nuts, check nuts and washers of galvanized iron and earth wire protected by provision of GI medium grade pipe 15mm bore including M&L of concrete base in PCC (1:2:4) type B-1 using 20mm graded stone aggregates and making PCC pit 30cmx30cmx30cm (inner dimensions) fixed with angle iron frame made out of 40x40x6mm angle iron duly covered with 40mm thick cover RCC (1:2:4) reinforced with XPM (weight not less than 4 kg/Sqm) and handle of 6mm dia MS bar made to shape light grade 20mm bore pipe for watering, placed on top edge of earth plate, earth electrode should be covered with layers of common salt and charcoal 15cm all around test point with providing & fixing arrangement, funnel, wire mesh complete all as shown on plate No-3, SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. Note:- Item of earthing includes cost of 7.5m long galvanized iron earth lead (wire/strip) and protection pipe of 15mm GI medium grade and 20mm bore light grade pipe for watring. Any variation in length shall be adjusted through deviation order to be priced on SSR 2010 subject to enhancement by valuation of deviation percentage vide scheduled.
Supply, installation, testing and commissioning of Diesel Engine/driven generating set of capacity 62.5 KVA (50KW), 415 Volt, 0.8 PF, mounted on base platform with flexible coupling, 1500 RPM, alongwith sound proof enclosure (Acoustic Enclosure) designed for reducing the sound level to 75 dBA (average) IS 10001/10002 Part-10 as per approved CPCB norms and as per GSR 371(E) and 17.05.2002 with silent pipe a silence muffer covered with asbestos rope 25mm thick independently supported from Engine to outside of power house upto 1.00 mtr. Arm pad, foundation as per manufacturer’s design, cold starting kit, Battery start with suitable size of standard cables for connecting from DG Set to panel board (DG set shall be capable of operating in temperature range of (-20 degree C to 35 degree C) complete with and including the following:- (A) Prime Mover :- Diesel Engine of suitable capacity not less than 83 HP water cooled (radiator type), closed circuit as per IS-100001/10002 or ISO-3046 direct inject type with turbo charger. Model S 3.8-G-7. The Diesel engine shall be capable of running 24 hrs continuously with 10% overloading for one hour in every 12 hrs. Engine shall be equipped with all standard fitting as per manufacturers recommendation and mounted on common base platform through flexible coupling with following accessories:-
(a) RPM cum hours meter. (b) Battery charging ammeter. (c) Ignition key and starting with push button switch. (d) Lubricating oil pressure. (e) Mechanical Governer controlling. (f) Toggle switch for idle running. (g) Oil temperature gauge. (h) Water temperature gauge. (j) Safety control (Trip) of the following:- (i) High water temperature. (ii) Low lubricant oil pressure. (iii) Over speed. (k) Lubricating oil heater to avoid freezing. (I) 12 Volts starting equipment comprising of the following:- (i) 1 Nos 12 Volts, 120 AH Batteries maintenance free type (Make-Exide type 25xnN 21 or equivalent as recommended by manufacturers) (ii) Battery charging alternator with inbuilt regulator. (iii) Self Starter motor of suitable capacity. (iv) Battery leads (copper stranded cable) of suitable size with brass thimbles and terminals.
Note: (a) The contactor shall produce a copy of approved certificate to authenticated the above from the OEM/OEAD. (b) DG set shall be mounted on platform design given by manufacturer cost of which is included in overall cost quoted. (c) Manufacturers test certificate spare parts, catalogue, manufacturers instructions and maintenance manual in original shall be supplied by the contractor with each DG set. (d) The complete DG set shall be tested by rep of AO within overall cost quoted. All arrangements including POL shall be made by contractor. (E) Maintenance Spares :- (i) Fuel filter element -02 Nos. (ii) Oil filter element -03 Nos. (iii) Element air cleaner outer -06 Nos. (iv) Element air cleaner inner -06 Nos. (v) V belt -02 Nos. (vi) Filter lubricant oil by pass -02 Nos. (F) DG sets shall be supplied alongwith acoustic original enclosure of the manufacture’s suitable for 62.5 KVA DG set as per CPCB norms.
Supply and fixing street light fitting 150 Watts HPSV with pressure dia cast aluminum housing, POT optics reflector and poly carbonate cover having IP 66 protection complete with ballast, igniter, holder and HPSV lamp 150 watt including fixing arrangement of street light bracket of 1.5M long 40mm dia light grade GI pipe and 02 set of clamps made out of 40x6mm MS flat, nut and bolts as required, complete all as specified and directed. Make:- Surya Cat Part No. SUL15SV/MHPOT CAWCG/IP66, havells Cat Part No. LHRS26115C99+LHBW20115036 and Philips Cat Part No. SPP3351xSONT150WGB
Supply and fixing bus bar chamber fabricated out of 2mm thick MS sheet with openable front fitted with aluminum bus bar TPN 63 Amps capacity and SP MCB 2.5 Amps and cable glands suitable for 16 Sqmm 4 core armored cable and including fixing arrangement with pole including PVC cable 2.5 Sqmm two core from junction box to security light fittings complete.
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanized iron earth lead strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanized iron and earth wire protected by provision of GI earth wire protected by provision of GI pipe medium grade pipe 40mm bore including M&L of concrete base in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover RCC (1:2:4) reinforced with XPM (weight not less than 4 kg/Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorous bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 mtr, all as per electrical plate No. 3 of SSR 2009 Part-I and connection to earth test point all as specified of indicated including testing on completion. Note:- Item of earthing includes cost of 7.5m long galvanized strip 32x6mm dia and protection pipe of 40mm bore GI medium grade. Any variation in length shall be adjusted through deviation order based on SSR rates adjusted with quoted percentage of Sch ‘A’ Part-X (Sec-I)
Dismantling of cable off sizes and refixing the same complete all as specified and directed.
Common burnt clay old size sub class ‘B’ bricks laid at right angle along the cable complete all as specified and directed.
Laying only XLPE insulated screened PVC bedded galvanised steel strip armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor, of cross sectional area 185 Sqmm 3.5 Core complete allas specified and directed. NOTE: Cable shall be issued under Sch 'B' free for laying.
Laying only XLPE insulated screened PVC bedded galvanised steel strip armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor, of cross sectional area 70 Sqmm 3.5 Core complete allas specified and directed. NOTE: Cable shall be issued under Sch 'B' free for laying.
Laying only XLPE insulated screened PVC bedded galvanised steel strip armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor, of cross sectional area 50 Sqmm 3.5 Core complete allas specified and directed. NOTE: Cable shall be issued under Sch 'B' free for laying.
Laying only XLPE insulated screened PVC bedded galvanised steel strip armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor, of cross sectional area 35 Sqmm 3.5 Core complete allas specified and directed. NOTE: Cable shall be issued under Sch 'B' free for laying.
Laying only XLPE insulated screened PVC bedded galvanised steel strip armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor, of cross sectional area 25 Sqmm 4 Core complete allas specified and directed. NOTE: Cable shall be issued under Sch 'B' free for laying.
Laying only XLPE insulated screened PVC bedded galvanised steel strip armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor, of cross sectional area 10 Sqmm 4 Core complete allas specified and directed. NOTE: Cable shall be issued under Sch 'B' free for laying.
Laying only XLPE insulated screened PVC bedded galvanised steel strip armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor, of cross sectional area 10 Sqmm 2 Core complete allas specified and directed. NOTE: Cable shall be issued under Sch 'B' free for laying.
Sch 'A' Part-XII ( Site Clearance) carried forward from pre-priced Schedule.
Sch 'A' Part-XIII ( Dismantling and demolition) carried forward from pre-priced Schedule.
Sch 'A' Part-XV ( DEFECTS IN COMPLETE WORK) carried forward from pre-priced Schedule.
mirco builders
M/s Hafizullah Beigh
SHAH AND SONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .