Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹3.6 LAccepted-AOC | 1 | Accepted-AOC L-1 | |
| 2 | 2₹4.0 L+₹37,088 (10.3%)Rejected-AOC | 2 | Rejected-AOC L-2 | |
| 3 | 3₹4.0 L+₹39,168 (10.9%)Rejected-AOC | 3 | Rejected-AOC L-3 |
Tender Value
₹3.6 L
EMD Value
₹4,000
Closing Date
5 Apr 2021, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE
ETC-II, UPPTCL, PAARESHAN BHAWAN, VIBHUTI KHAND, GOMTI NAGAR, LUCKNOW-226010
WORK
2021_UPTCL_578196_1
ETC-II/L/89/2020-21
Open Tender
Electrical Works
Item Rate
365 days
LUCKNOW
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE, ETC-II, UPPTCL, LUCKNOW
₹4,000
19 Jul 2021
31 Mar 2021
6 Apr 2021
31 Mar 2021
5 Apr 2021
31 Mar 2021
180 days
Amount
Following comprehensive maintenance works are to be conducted during routine Annual/Periodic Maintenance of various bay equipments in 400 and 220 KV bays at 400 KV S/S Sarojininagar, Lucknow by deploying skilled manpower/ electrician, T&P and consumables (if needed) in following bays :- 1.400 KV Bus Coupler Bay. 2.400 KV Lucknow (PG) Bay. 3.400 KV Unnao Bay. 4.500 MVA 400/220/33 KV ICT-I Bay. 5.500 MVA 400/220/33 KV ICT-II Bay. 6.400 KV Bus Transfer Bay. 7.400 KV Singrauli Bay. 8.400 KV Bareilly Bay. 9.80 MVAR Bus Reactor Bay.
Maintenance of Transformers/Bus Reactors
Annual maintenance of ICTs and Bus Reactor including cleaning of bushings, checking and attending minor oil leakages, checking and re-tightening of all nuts and bolts, fastenings, gaskets, valves etc., cleaning of marshalling box and OLTC DM box, re-tightening of all wiring connections, checking proper operation of Buchholz and PRV relays, checking and replenishing of oil levels in WTI/OTI pockets, checking and cleaning of oil level gauge in bushings, cleaning of radiator bank and cooling fans, checking of operation of cooling fans and pumps as per requisite temperature settings, checking proper functionings of all local/remote lamps and annunciations. Sufficient manpower, T&P and safety equipment shall be provided by the contractor so as to complete the jon in minimum time as per the satisfaction of site in-charge. The work also includes opening of HV/LV bushing terminal connections for routine testing of transformers/reactor and re-tightening of connections after completion of testing.
500 MVA, 400/220/33 KV ICT-01 and ICT-02
80 MVAR Bus Reactor
Maintenance of Circuit Breakers
Annual maintenance of all SF-6 Circuit Breakers by cleaning and lubrication of operating mechanism, cleaning of procelain insulators, checking, de-rusting and cleaning of auxiliary switches, checking and attending SF-6 gas leakage, cleaning and lubrication of compressor assembly alongwith checking and attending air leakage and draining of moisture, checking, cleaning, lubrication of closing and tripping coil assemblym cleaning of marshalling boxes, clecking and re-tightening of electrical connections, checking of auto-switching/operation of all pressure switches, DC/AC contactors, limit switches, pole discrepency timers/relays etc. and replacement if needed. Remote/local closing and tripping operations shall be checked alongwith all the possible interlocks and closing/tripping coils shall be replaced if required. Sufficient manpower, T&P and safety equipment shall be provided by the contractor so as to complete the job in minimum time as per satisfaction of site in-charge.
400 KV Circuit Breakers
220 KV Circuit Breakers
Maintenance of Isolatos
Annual cleaning and lubrication of top and bottom operating mechanisms of all 400 KV Pantograph Isolators (with and without earth switch) and 400/220 KV Standard/Tandem Isolators, cleaning of MOM boxes, lubrication of drive motor, cleaning and checking of auxiliary contacts, checking and tightening of all the control cable terminations, verification of all closing/opening interlocks by actual operation and checking of gang/individual and remote/local operation of isolator under the supervision of site in-charge.
400 KV Pantograph Isolators without earth switch
400 KV Pantograph Isolators with 01 earth switch
400 KV Standard Isolators with 01 earth switch
400 KV Standard Isolators with 02 earth switch
220 KV Standard Isolators with 01 earth switch
200 KV Tandem Isolatos without earth switch
Maintenance of Current/Voltage Transformer
Annual maintenance of current transformer by cleaning of insulators, checking of oil level and cleaning of oil level indicator, arresting minor leakage/seepage of oil, if any, checking, cleaning and proper sealing of secondary coil terminal boxes, re-tightening of seondary coil terminations. Sufficient manpower, T&P and safety equipment shall be provided by the contractor so as to complete the job in minimum time as per the satisfaction of site in-charge.
400 KV Current Transformer
220 KV Current Transformer
400 KV CVTs
220 KV CVTs
Maintenance of Lightening Arrestors
Annual maintenance of LAs by cleaning of insulators, tightening of terminal connections, checking of any moisture ingress in surge monitors, checking proper operation of surge counter, replacement of surge monitor if necessary, checking and tightening of earthing strip etc. Sufficient manpower, T&P and safety equipment shall be provided by the contractor so as to complete the job in minimum time as per the satisfaction of site in-charge.
400 KV LAs
220 KV LAs
Maintenance of Bus-Bar
Annual checking and tightening of all clamps, connectors, separators etc. and replacement of the same if necessary along with cleaning of disc insulators and checking for tightness of locking pin of insulator string of 400 KV Quad Moose Bus-Bar. Also, removal of all the bird-nests from gantries and disc insulators.Sufficient manpower, T&P and safety equipment shall be provided by the contractor so as to complete the job in minimum time as per the satisfaction of site in-charge.
Tightening of clamps and connectors in 400/220 KV Bays
Half-Yearly checking and tightening of all clamps and connectors and replacement of the same if necessary, in each of the equipment/jumpers/droppers etc. in the various 400 KV and 220 KV bays.Sufficient manpower, T&P and safety equipment shall be provided by the contractor so as to complete the job in minimum time as per the satisfaction of site in-charge.
400 KV Bays (2X7=14)
220 KV Bays (2X2=4)
Maintenance of Control & Relay Panels, Marshalling Boxes and Junction Boxes
Half-Yearly cleaning of various control and relay panels marshalling boxes and junction boxes by cleaning of all dust and dirt deposits, removal of all debris, bits and pieces of wires and other materials, de-rusting and de-carbonising of all terminals by air blower, soft brush and CRC/cleaning spray; checking and sealing of all open gland-holes, replacement of handles and gaskets of doors if necessary for proper closing of boxes, re-tightening of all terminal connections and minor modifications in wiring if required as per the directions of site in-charge
Control/Relay Panels (2X49=98)
Bay Marshalling Boxes (2X8=16)
Isolator Junction Boxes (2X20=40)
CT Junction Boxes (2X10=20)
CVT Junction Boxes (2X8=16)
LT Power Supply Cubicles (2X9=18)
220 & 48 V Battery Charger Panel (2X5=10)
220 V DCDB (2X2=4)
415 V LT ACDB DCDB (2X2=4)
Gupta Elect and Engg Works
Perfect Power Transformer Associates
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .