Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.4 LAccepted-AOC SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹24.8 L+₹2.9 L (13.5%)Rejected-Finance 110059 NEW DELHI NATIONAL CAPITAL TERRITORY OF DELHI 110059 | WEST DELHI | DELHI | 110059 | L2 | Rejected-Finance High Rate quoted | |
| 3 | L3₹24.9 L+₹3.0 L (13.7%)Rejected-Finance | L3 | Rejected-Finance High Rate quoted | |
| 4 | L4₹28.5 L+₹6.7 L (30.5%)Rejected-Finance WZ 109 PLOT NO 327 CHAND NAGAR NEW DELHI | L4 | Rejected-Finance High Rate quoted | |
| 5 | Rejected-Technical WARD NO 40 REGRON KA MOHALLA NEAR RAVI DASS JI MANDIR SHIV BARI BIKANER RAJSTHAN 334001 | BIKANER | RAJASTHAN | 334001 | - | Rejected-Technical Not recommended for not enlisted in c (iii) category. |
Tender Value
₹29.8 L
EMD Value
₹59,660
Closing Date
15 Nov 2023, 6:00 pmClosed
Col Shery Goel, CWE Bikaner
HQ CWE Bikaner, Bikaner Mil Stn
Repair and maintenance of EOT Cranes and misc installation at Military Station Kanasar under AGE (I) Kanasar
2023_MES_623118_1
CA No CWE BKN-Token No. 33/2023-2024
Open Tender
Civil Works
Item Rate
330 days
AGE (I) Kanasar
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
AGE (I) Kanasar
₹59,660
Yes
20 Dec 2023
13 Oct 2023
22 Nov 2023
13 Oct 2023
15 Nov 2023
1 Nov 2023
13 Oct 2023 - 21 Oct 2023
Amount
Note applicable to all items of Schedule ‘A’ :- The items considered in this Schedule ‘A’ are for repair and maintenance of 52 Nos EOT Cranes at various locations in Kanasar Military Station. The defect/fault in EOT Crane shall be intimated to the contractor through complaint slip and/or telephonically by the representative of GE and same must be rectified by the contractor through OEM (i.e. Rockwell, Universal, Dinesh, Hercules, Pedvak, etc) within five days of intimation. If contractor fails to rectify the defect/fault within 05 days of intimation, a penalty at the rate of Rs. 1000/- per day per EOT Crane shall be imposed on the contractor after 05 days till the defect/fault is rectified. A complaint Log Book in this regard shall be maintained by the contractor duly signed by the Engineer-in-Charge. The rates quoted by the contractor shall deemed to be included this aspect.
M&L for dismantling of various components of Flame proof Electrically Operated EOT Crane of following capacity ranging from 2 Ton to 10 Ton of any span (45 Metre maximum) of cross/long travel and height of hoist (10 metre maximum) for carrying out overhauling and repairing various items (Electric motors, Main gear box, cross travel gear box, limit switch, pandent switch, electric control panel, thrusters, break drums, etc) and re-fixing the components in its position, tighting all nut & bolts / screws after carrying out overhauling / repair work including cleaning and removing old grease/ oil from tracks, steel wire rope, main hoist motor drum with approved cleanser and steel wire brush, regreasing with new grease for smooth running of wheels, pulleys, steel wire rope, etc and replacing minor extras / hardware as required, complete rewiring of electric control panel (consisting of VFD, transformer, contactors, choke / line reactor, electronic circuit) by new wire as per existing installed wire, including reprogramming of Variable Frquency Drives (VFD) with the help of laptop for new parameter entry, cleaning control panel with air blower, repairing all contacts of Pendant command control switch including replacing unserviceable parts such as push button, contacts, replacing broken cable plastic trollys, replacing all broken / leakage shaft seals/ oil seals / 'O' seals / 'V' seals of any size of thruster / gear box complete all as specified and as directed.
Notes : (i) Repair/overhauling of EOT Crane shall be carried out through authorized service agency of Original Equipment Manufacturer (OEM). The contractor shall submit documentary proof/evidence in this regard before taking EOT Cranes under repair, overhauling, etc. (ii) Make and model of part to be replaced shall be same as used/recommended by OEM. (iii) Repairing/replacement of unserviceable Major main components catered for separately under respective items of this Schedule shall be measured & paid for separately. (iv) Grease/ Push buttons/ contacts /plastic cable trolly/ shaft seal/ oil seal / 'O' seal / 'V' seal included in quoted rates of this item and no extra payment shall be made.
EOT Crane of Capacity 2 Ton
EOT Crane of Capacity 3 Ton
EOT Crane of Capacity 5 Ton
EOT Crane of Capacity 10 Ton
M&L for repair/overhauling/servicing of Main Hoist Gear Box/ Cross travel gear box/ Long travel gear box of flame proof EOT Crane of following capacity including cleaning, recutting, polishing the gear teeth after remetalling and making good, remetalling of driving shaft, machining, finishing, polishing and making good for smooth running of crane, replacing worn out bushes, bearings on drive and non drive ends, reassembling all the components after necessary repair works, replacing the gear oil of the gear box upto required level, making adjustment to ensure trouble free smooth running of gear system complete all as specified and as directed. Notes : (i) Repair/overhauling/servicing of Gear Box shall be carried out through authorized service agency of Original Equipment Manufacturer (OEM). The contractor shall submit documentary proof/evidence in this regard before taking Gear Box under repair, overhauling, servicing, etc. (ii) Make and model of part to be replaced shall be same as used/recommended by OEM. (iii) Gear oil, ball bearing & spare parts as required shall be measured and paid for separately under respective items of this Schedule.
EOT Crane of Capacity 2 Ton
EOT Crane of Capacity 3 Ton
EOT Crane of Capacity 5 Ton
EOT Crane of Capacity 10 Ton
M&L for repair/overhauling the Flame proof electro hydrauilc Thruster & brake of following capacity of EOT Crane with gear holding brakes of Hoist / Creep / Cross travel and Long travel, rewinding the burnt out winding of electrohydrauiic thruster motor with super enamel copper wire of existing gauge and varnishing, heating and testing etc complete repairing of oil pump by replacing worn out parts, oil seal, ‘O’ ring and bush and bearing - 02 Nos (6201), check nuts, lock pin all as required including draining out old unserviceable oil complete all as specified & as directed :- Notes : (i) Repair/overhauling of Thruster shall be carried out through authorized service agency of Original Equipment Manufacturer (OEM). The contractor shall submit documentary proof/evidence in this regard before taking Thruster under repair, overhauling, etc. (ii) Make and model of part to be replaced shall be same as used/recommended by OEM.
Main hoist Thruster of 10 Ton EOT Crane.
Main hoist Thruster of 5 Ton EOT Crane.
Main hoist Thruster of 2 Ton / 3 Ton EOT Crane.
Cross Travel Thruster of 10 Ton EOT Crane.
Cross Travel Thruster of 5 Ton EOT Crane.
Cross Travel Thruster of 2 Ton / 3 Ton EOT Crane.
Long Travel Thruster of 10 Ton EOT Crane.
Long Travel Thruster of 5 Ton EOT Crane.
Long Travel Thruster of 2 Ton / 3 Ton EOT Crane.
Supply and fixing in replacement Hydrauilc oil (ISI marked) of approved grade for filling in the electrohydrauilc thruster upto specified level under the relevant item of this Schedule all as directed.
Supply and fixing in replacement Gear oil (ISI marked) of 80W-90 grade for filling in the gear boxes upto specified level under the relevant item of this Schedule all as directed.
S&F Contactor 3 pole, model 3TF47 (make – Siemens or equivalent model in makes mentioned in Appendix 'B' here-in-after), Coil voltage 230V, 63 Amp, for 50 HP capacity motor with 2 NO & 2 NC auxilairy contact, including disconnecting & taking down old unserviceable contactor complete all as specified & as directed.
S&F Contactor 3 pole, model 3TF49 (make – Siemens or equivalent model in makes mentioned in Appendix 'B' here-in-after), Coil voltage 230V, 80 Amp, for 50 HP capacity motor with 2 NO & 2 NC auxilairy contact, including disconnecting & taking down old unserviceable contactor complete all as specified & as directed.
S&F Contactor 3 pole, model A110-30 of 110 Amps, (make – ABB or equivalent model in makes mentioned in Appendix 'B' here-in-after) including disconnecting & taking down old unserviceable contactor complete all as specified & as directed.
S&F Contactor 3 pole, model KMIA of 63 Amps, HP @ 230 volt 25 HP and HP @ 460 volt 50 HP having coil voltage 240 volt (make – ABB or equivalent model in makes mentioned in Appendix 'B' here-in-after) including disconnecting & taking down old unserviceable contactor complete all as specified & as directed.
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal of shaft on main hoist wire rope drum on both side for 10 Ton capacity gear box for main hoist for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal of shaft on main hoist wire rope drum on both side for 5 Ton capacity gear box for main hoist for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal of shaft on main hoist wire rope drum on both side for 2 Ton / 3 Ton capacity gear box for main hoist for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal on both side for Cross Travel of 10 Ton capacity EOT Crane for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal on both side for Cross Travel of 5 Ton capacity EOT Crane for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal on both side for Cross Travel of 2 Ton / 3 Ton capacity EOT Crane for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal for Long Travel of 10 Ton capacity EOT Crane for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal for Long Travel of 5 Ton capacity EOT Crane for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing in replacement Ball bearing along with shaft seal/ oil seal / 'O' seal / 'V' seal for Long Travel of 2 Ton / 3 Ton capacity EOT Crane for replacement under the relevant item of this Schedule all as directed. Make : TATA / SKF / NBC
Supply and fixing galvanized Steel wire rope conforming to IS-2266-2002 of nominal diameter of 16mm having 6x19M(12/6-1) multi stranded construction steel core CRW grade 1570, having mass 97.4 Kg/100 RM with minimum breaking force of 102 KN suitable for lifting load of 10 Ton including greasing complete all as specified and as directed including taking down old unserviceable steel rope. Make : Usha / Bombay Foot / National or as used/recommended by OEM. Notes : (i) The steel rope shall be best performed plough straight non rotating type conforming to IS-2266. (ii) The breaking strength of the rope shall not be less than 6 time the safe working load thereon. (iii) Test Certificate of manufacturer shall be submitted by the contractor.
Supply and fixing galvanized Steel wire rope conforming to IS-2266-2002 of nominal diameter of 11mm having 6x19M(12/6-1) multi stranded construction steel core CRW grade 1570, having mass 46.1 Kg/100 RM with minimum breaking force of 63 KN suitable for lifting load of 5 Ton including greasing complete all as specified and as directed including taking down old unserviceable steel rope. Make : Usha / Bombay Foot / National or as used/recommended by OEM. Notes : (i) The steel rope shall be best performed plough straight non rotating type conforming to IS-2266. (ii) The breaking strength of the rope shall not be less than 6 time the safe working load thereon. (iii) Test Certificate of manufacturer shall be submitted by the contractor.
Supply and fixing galvanized Steel wire rope conforming to IS-2266-2002 of nominal diameter of 9mm having 6x19M(12/6-1) multi stranded construction steel core CRW grade 1570, having mass 30.8 Kg/100 RM with minimum breaking force of 42 KN suitable for lifting load of 3 Ton including greasing complete all as specified and as directed including taking down old unserviceable steel rope. Make : Usha / Bombay Foot / National or as used/recommended by OEM. Notes : (i) The steel rope shall be best performed plough straight non rotating type conforming to IS-2266. (ii) The breaking strength of the rope shall not be less than 6 time the safe working load thereon. (iii) Test Certificate of manufacturer shall be submitted by the contractor.
Supply and fixing in replacement Power contactor of capacity 70 Amps, AC-03, 415 Volts, 50 Hz, 3 Ph, 3 pole along with auxiliary contacts 2NO + 2NC, Coil voltage - 110 V, complete all as specified & as directed.
Supply and fixing in replacement Power contactor of capacity 12 Amps, AC-03, 415 Volts, 50 Hz, 3 Ph, 3 pole along with auxiliary contacts 2NO + 2NC, Coil voltage - 110 V, complete all as specified & as directed.
Supply and fixing in replacement Power contactor of capacity 18 Amps, AC-03, 415 Volts, 50 Hz, 3 Ph, 3 pole along with auxiliary contacts 2NO + 2NC, Coil voltage - 110 V, complete all as specified & as directed.
Supply and fixing in replacement Power contactor of capacity 32 Amps, AC-03, 415 Volts, 50 Hz, 3 Ph, 3 pole along with auxiliary contacts 2NO + 2NC, Coil voltage - 110 V, complete all as specified & as directed.
Supply and fixing in replacement Power contactor of capacity 50 Amps, AC-03, 415 Volts, 50 Hz, 3 Ph, 3 pole along with auxiliary contacts 2NO + 2NC, Coil voltage - 110 V, complete all as specified & as directed.
Supply and fixing in replacement Flame proof three phase Rotary type limit switch with 35:1 to 50:1 ratio as per site, suitable for following capacity EOT crane for Main hoist / long travel / Cross Travel of make (Sudhir, Shyam, Suni Crane Control, Baliga, Spee-o-control Pvt Ltd) as used / recommended by OEM, complete all as specified & as directed.
EOT Crane of Capacity 2 Ton
EOT Crane of Capacity 3 Ton
EOT Crane of Capacity 5 Ton
EOT Crane of Capacity 10 Ton
Supply and fixing in replacement Flame proof three phase lever type limit switch as per site, suitable for following capacity EOT crane for Main hoist / long travel / Cross Travel of make (Sudhir, Shyam, Suni Crane Control, Baliga, Spee-o-control Pvt Ltd) as used / recommended by OEM, complete all as specified & as directed.
EOT Crane of Capacity 2 Ton
EOT Crane of Capacity 3 Ton
EOT Crane of Capacity 5 Ton
EOT Crane of Capacity 10 Ton
S&F in replacement Trailing flexible copper conductor cable (ISI marked) of size 1.5 Sqmm 16 Core, 1100 Volt, with & including movable clamps and single flanged rollers, complete all as specified & as directed.
S&F in replacement PVC insulated & FR PVC round sheathed, multi stranded copper conductor cable (ISI marked) steel wire armoured of size 2.5 Sqmm 4 Core, 1100 Volt, complete all as specified & as directed.
S&F in replacement PVC insulated & FR PVC round sheathed, multi stranded copper conductor cable (ISI marked) steel wire armoured of size 4 Sqmm 4 Core, 1100 Volt, complete all as specified & as directed.
S&F in replacement PVC insulated & FR PVC round sheathed, multi stranded copper conductor cable (ISI marked) steel wire armoured of size 6 Sqmm 4 Core, 1100 Volt, complete all as specified & as directed.
S&F in repair Flame proof Thruster brake shoes for following capacity of EOT crane of size 100 mm x 125 mm x 12 mm thick as per existing installed on site with necessary copper rivets etc complete of make 'Ferrodo liner' or 'Usha' or as used / recommended by OEM, complete all as specified & as directed.
EOT Crane of Capacity 2 Ton
EOT Crane of Capacity 3 Ton
EOT Crane of Capacity 5 Ton
EOT Crane of Capacity 10 Ton
M&L for disconnecting the burnt flame proof electric motor of capacity upto 1 HP, 3 Phase, 415 Volt from the EOT cranes transporting to workshop, taking out old winding and rewinding the motor with same gauge of copper wire, varnishing, overhauling complete including replacing the ball bearing on both ends, re-fitting to crane, re-connecting and testing complete all as specified & as directed.
M&L for disconnecting the burnt flame proof electric motor of capacity upto 3 HP, 3 Phase, 415 Volt from the EOT cranes transporting to workshop, taking out old winding and rewinding the motor with same gauge of copper wire, varnishing, overhauling complete including replacing the ball bearing on both ends, re-fitting to crane, re-connecting and testing complete all as specified & as directed.
M&L for disconnecting the burnt flame proof electric motor of capacity 5 HP, 3 Phase, 415 Volt from the EOT cranes transporting to workshop, taking out old winding and rewinding the motor with same gauge of copper wire, varnishing, overhauling complete including replacing the ball bearing on both ends, re-fitting to crane, re-connecting and testing complete all as specified & as directed.
M&L for disconnecting the burnt flame proof electric motor of capacity 10 HP, 3 Phase, 415 Volt from the EOT cranes transporting to workshop, taking out old winding and rewinding the motor with same gauge of copper wire, varnishing, overhauling complete including replacing the ball bearing on both ends, re-fitting to crane, re-connecting and testing complete all as specified & as directed.
Supply and fixing in replacement Variable Fequency Drive (VFD) / Vector Inverter / AC drive suitable for 3 phase electric motor used for EOT crane gear working on 3 phase 380- 480V power supply, protective structure enclosed type, cooling system force, permisible frequency fluctuation ±5%, 0.2 Hz- 400Hz having suitable input/output for 3.0 HP electric motor complete all as specified and as directed. Make :- Mitsubishi/ Yaskawa Electric Corporation / CG/ ABB / L&T or as per installed on site as recommended by OEM.
Supply and fixing in replacement Variable Fequency Drive (VFD) / Vector Inverter / AC drive suitable for 3 phase electric motor used for EOT crane gear working on 3 phase 380- 480V power supply, protective structure enclosed type, cooling system force, permisible frequency fluctuation ±5%, 0.2 Hz- 400Hz having suitable input/output for 7.5 HP electric motor complete all as specified and as directed. Make :- Mitsubishi/ Yaskawa Electric Corporation / CG/ ABB / L&T or as per installed on site as recommended by OEM.
Supply and fixing in replacement Variable Fequency Drive (VFD) / Vector Inverter / AC drive suitable for 3 phase electric motor used for EOT crane gear working on 3 phase 380- 480V power supply, protective structure enclosed type, cooling system force, permisible frequency fluctuation ±5%, 0.2 Hz- 400Hz having suitable input/output for 10 HP electric motor complete all as specified and as directed. Make :- Mitsubishi/ Yaskawa Electric Corporation / CG/ ABB / L&T or as per installed on site as recommended by OEM.
Supply and fixing in replacement 3 phase line reactor / choke suitable for Variable Fequency Drive (VFD) / Vector Inverter / AC drive used for upto 15 HP electric motor or 10 Amps capacity (maximum) as per site requirement conforming to IS 2025, 1271, 12021 having inductance 2.5854, terminals for three phase input/ output connection complete all as specified and as directed. Make : Standard Magnetic India / The Transformenr company / OM Industries or as per installed on site as recommended by OEM.
Supply and fixing in replacement Control Transformer three phase having HT/LT ratio of 440/110 V AC, 50 / 60 Hz, Capacity 200 VA copper wound complete all as specified and as directed.
Supply and fixing in replacement Dynamic Braking Register (DBR), construction type Aluminium house bar having tolerance less than 1 ohm, two terminal end of capacity 250 ohm 400 Watt complete all as specified and as directed.
Supply and fix in replacement Dynamic Braking Register (DBR), construction type Aluminium house bar having tolerance less than 1 ohm, two terminal end of capacity 350 ohm 400 Watt complete all as specified and as directed.
Supply and fix in replacement Dynamic Braking Register (DBR), construction type Aluminium house bar having tolerance less than 1 ohm, two terminal end of capacity 700 ohm 400 Watt complete all as specified and as directed.
Supply and fix in replacement following Spares/Components in EOT Crane of 2 Ton capacity after approval and as directed by Engineer-in-Charge :-
Carbon Brush for sleepring motor motion.
Over Load Relay.
Brake Lining.
Magnetic Coil.
Clutch Plate and Pin for cross travel motion.
Thrust Bearing.
Gear Wheel.
Pendant Push Button with auxiliary contacts.
Supply and fix in replacement following Spares/Components in EOT Crane of 3 Ton capacity after approval and as directed by Engineer-in-Charge :-
Carbon Brush for sleepring motor motion.
Over Load Relay.
Brake Lining.
Magnetic Coil.
Clutch Plate and Pin for cross travel motion.
Thrust Bearing.
Gear Wheel.
Pendant Push Button with auxiliary contacts.
Supply and fix in replacement following Spares/Components in EOT Crane of 5 Ton capacity after approval and as directed by Engineer-in-Charge :-
Carbon Brush for sleepring motor motion.
Over Load Relay.
Brake Lining.
Magnetic Coil.
Clutch Plate and Pin for cross travel motion.
Thrust Bearing.
Gear Wheel.
Pendant Push Button with auxiliary contacts.
Supply and fix in replacement following Spares/Components in EOT Crane of 10 Ton capacity after approval and as directed by Engineer-in-Charge :-
Carbon Brush for sleepring motor motion.
Over Load Relay 5 to 10 Amps.
Brake Lining.
Magnetic Coil.
Clutch Plate and Pin for cross travel motion.
Thrust Bearing.
Gear Wheel.
Pendant Push Button with auxiliary contacts.
Supply and fix in replacement Variable Fequency Drive (VFD) / Vector Inverter / AC drive suitable for 3 phase electric motor used for EOT crane gear working on 3 phase 380- 480V power supply, protective structure enclosed type, cooling system force, permisible frequency fluctuation ±5%, 0.2 Hz- 400Hz having suitable input/output for 5 HP electric motor complete all as specified and as directed. Make :- Mitsubishi/ Yaskawa Electric Corporation / CG/ ABB / L&T or as per installed on site as recommended by OEM.
M&L for load testing of over head travelling crane of following capacity EOT crane as per manufacture norm for safe working rating load including arrangement of dead load measurement unit with link steel wire rope and required suitable load for testing with duly varying the load upto 110% of the rated capacity of crane including transporting to testing load at difference location and also providing load test certificate in triplicate set from authorised OEM duly singed complete all as specified and directed.
EOT Crane of capacity 2 Ton
EOT Crane of capacity 3 Ton
EOT Crane of capacity 5 Ton
EOT Crane of capacity 10 Ton
M&L for painting of following capacity EOT double girder traveling over head travaling EOT cranes system alongwith trolly, foot parth, railing system and including both sides girder and its connected item fixing accessories / equpts such as panel, motor (Main hoist motor, Long travel motors, cross travel motors including gear box and thruster brake) complete for crane system by applying two coats of flame proof paint of colour golden yellow/ Tractor orange/ gray colour or existing sample with existing making painting as per existing type colour code including writing SM/MES No complete all as specified and directed.
EOT Crane of capacity 2 Ton
EOT Crane of capacity 3 Ton
EOT Crane of capacity 5 Ton
EOT Crane of capacity 10 Ton
Disconnecting electrical connection opening of the LT panel board of EOT Crane, disconnecting and removing the burnt out cable end termination, cutting and reterminating the cable end portions with lugs of proper size and removing the burnt out control and power wiring from the panel board, providing new wiring with suitable size copper cable and replacement of damaged burnt out connectors, fuse holders and cable lugs including cleaning of control panel, checking of all auxiliary & main power contactors, over load relays complete all as specified and directed.
Supply and fixing in replacement Electro magnetic brake/Thruster brake with brake drum of any size complete all as specified and directed.
Supply and fixing in replacement 160 Amp HRC fuse DIN type carrier male female type with HRC fuses complete all as specified and as directed.
Supply and fixing in replacement 100 Amp HRC fuse DIN type carrier male female type with HRC fuses complete all as specified and as directed.
Supply and fixing in replacement 63 Amp HRC fuse DIN type carrier male female type with HRC fuses complete all as specified and as directed.
Supply and fixing in replacement 32 Amp HRC fuse DIN type carrier male female type with HRC fuses complete all as specified and as directed.
Supply and fixing in replacement of flame proof suspension type pendent/hanging controling unit controlling unit with flame proof start/stop push buttons with indicator lamp and emergency control switch, lifting hook for UP and down, long travel motion, cross travel and conneting to controling micro speed panel suitable for safe and smooth operating system of EOT Crane of following capacity including making cable connection and testing complete all as specified and directed. Make : BCH/ Shyam/Sudhir or equivalent model and make.
EOT Crane of capacity 2.0 Ton
EOT Crane of capacity 3.0 Ton
EOT Crane of capacity 5.0 Ton
EOT Crane of capacity 10.0 Ton
Supply and fixing in replacement packing kit for gear box complete all as specified and directed. Make : Cranex, API, KM Engg.
Supply only current collector assembly as per existing suitable for 02 Ton capacity EOT cranes at different locations complete all as specified and directed.
Supply only current collector assembly as per existing suitable for 03 Ton capacity EOT cranes at different locations complete all as specified and directed.
Supply only current collector assembly as per existing suitable for 05 Ton capacity EOT cranes at different locations complete all as specified and directed.
Supply only current collector assembly as per existing suitable for 10 Ton capacity EOT cranes at different locations complete all as specified and directed.
Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing excavated soil/material to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50 metre above the starting point complete all as specified and as directed.
M&L for dry sand (Local Tibba sand) and punning for cushioning and cover for protection of under ground electric cable complete all as specified and as directed. Notes : (i) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured.
M&L for sub class ‘B’ (old size) burnt clay bricks laid flat and dry abutting each other with gap between adjacent bricks not exc. 10mm for protection of underground electric cable in such a way that the length of brick is at right angle to the central axis of cable complete all as specified and as directed.
M&L for Galvanized iron tubing, 50mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (25mmx3mm) clamps, bolts, nuts and washers for protection of LT electric cable complete including taking down old unserviceable pipe with clamps complete all as specified and directed. Note :- Excavation & earthwork shall be measured & paid for separately.
M&L for Boring of holes of 80mm bore under road, pavement, hard standing, (minimum 1.0m below) etc by trench less technology using necessary machine / manually without disturbing the top surface suitable for passing the GI protection pipe / cables, complete all as specified and as directed.
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 70 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including dismantling & taking out old unserviceable cable complete all as specified and directed. Notes :-(i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
Supply, laying, jointing and testing LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 35 sqmm 3.5 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including dismantling & taking out old unserviceable cable complete all as specified and directed. Notes :- (i) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately. (ii) Road cutting/floor cutting /cutting holes etc in walls required for laying/fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
Taking down / taking out old unserviceable burnt / punctured / faulty aluminium / LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 35 sqmm, 3.5 core laid in trenches/ducts, through pipe, under floors or roads crossing/ Path/ drains/ along poles etc and relaying / refixing the same after rectification of defect including cutting making jointing complete all as specified & as directed. Notes :- (i) Excavation & earth work and cable jointing kit shall be measured & paid for separately. (ii) Old serviceable brick / precast PCC cable cover shall be reused and rate quoted shall dement to included for the same.
Taking down / taking out old unserviceable burnt / punctured / faulty aluminium / LT XLPE insulated screened, bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 70 sqmm, 3.5 core laid in trenches/ducts, through pipe, under floors or roads crossing/ Path/ drains/ along poles etc and relaying / refixing the same after rectification of defect including cutting making jointing complete all as specified & as directed. Notes :- (i) Excavation & earth work and cable jointing kit shall be measured & paid for separately. (ii) Old serviceable brick / precast PCC cable cover shall be reused and rate quoted shall dement to included for the same.
S&F MCB, 6 to 32 Amps, Single Pole, 240 Volts, 10 kA, ‘C’ Curve, with over load and short circuit protection, fixed in repairs, complete all as specified and as directed.
S&F MCB, 32 Amps, Double Pole, 415 Volts, 10 kA, ‘C’ Curve, with over load and short circuit protection, fixed in repairs complete all as specified and as directed.
S&F MCB, 63 Amps, TP, 415 Volts, 10 kA, ‘C’ Curve, with over load and short circuit protection, fixed in repairs complete all as specified and as directed.
S&F MCB, 40 Amps, TPN, 415 Volts, 10 kA, ‘C’ Curve, with over load and short circuit protection, fixed in repairs, complete all as specified and as directed.
M&L for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/ welded to earth plate at one end and other end of strip connected to transformer / GOD / Panel / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m including dismantling & taking out old existing unserviceable earthing complete all as specified and as directed. Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
Supply and fixing in replacement Bus Bar chamber cubical type with busbar chamber having 4 wire, 415 Volts factory made dust proof vermin proof for outdoor using made out of CRCA sheet 3.00mm thick powder coated with MCCB 100 Amp 4 pole breaking capacity 16 KA, machine pressed, both side opening in two halves with provision of rubber beading and locking arrangement, including aluminium bus bar of 200 Amps capacity 4 strip mounted on DMC/Epoxi insulator, bus bar chamber shall be provided with inspection cover, panel shall be mounted on angle iron frame and legs made from angle of size 40 x 40x 6mm, frame and legs dully spray painted internally and externally with two coat of synthetic enameled paint over a coat of red oxide, leg grouted in PCC (1:3:6) type C1 (using 20mm graded crushed stone aggregate) complete all as specified & as directed.
Supply, installation, testing and commissioning factory LT feeder pillar box (KIOSK), indoor type (cubical type), floor mounted, suitable for 415 volts 3 phase & neutral, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bars suitable capacity in colour code RYB with 3 phase & neutral installed on porcelain insulators with bus bar chamber shall be provided with inspection covers, each MCCB/cubical switch independent opening. The panel shall be dust & vermin proof, protection class IP-65 and made out of CRCA sheet of 3mm thick, powder coated finish on outside & inside surfaces (approved shade), double door (front & rear), in two shalves with provision of rubber beading and front opening type with aprons for cable entry, with double door shutter & locking arrangement {including provn of 65mm Godrej (Freedom) lock with 2 keys},, dange notice board in front and rear sidesand MS angle iron frame work (made out of 40mmx40mmx5mm thick), frame legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregate) including internal wiring with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 6 sqmm with proper ferrule & cable gland inlcuding taking down old unserviceable LT panel complete and also comprising of the following:- INCOMING : (a) MCCB 250 Amps, 4 Pole, 415 Volts, adjustable thermal and magnetc setting type rupturing capacity 25 kA, - 01 Nos (b) Bus bar electrolytic grade aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 500 Amp, 4 pole, not less than 30cm long mounted on insulators for incomming supply. (c) Neon indicating lamp RYB - 01 Set (d) Digital voltmeter 0-500 volts - 01 No (e) Digital Ammeter 0-200 Amps with suitable ratio of CTs - 01 No
Description of serial item No. 82.00 contd… OUTGOING : (f) MCCB 200 Amps 4 Pole, 415 Volts, adjustable thermal and magnetc setting type rupturing capacity 25 kA, 415 Volts - 01 No (g) MCCB 160 Amps 4 Pole, 415 Volts, adjustable thermal and magnetc setting type rupturing capacity 16 kA, 415 Volts - 01 No (h) MCCB 100 Amps 4 Pole, 415 Volts, adjustable thermal and magnetc setting type rupturing capacity 16 kA, 415 Volts - 02 No (j) MCB 63 Amps, TPN, 415 Volts, rupturing capacity 10 kA, 'C' series - 04 No (k) MCB 32 Amps, DP, 415 Volts, rupturing capacity 10 kA, 'C' series - 04 No (l) Digital Load manager multy functional energy meter having facility to measure true RMS value, KWH, neutral current, for quadrant energy, max demand (KW, KVA, Kvar & Amp), CT operated 415 volts, 50 Hz AC supply including CTs. -01 set. Make : L&T Cat Part No WDM303FDN B1 (m) Neon Indicator lamps (RYB) - 01 Set Note : Foundation/platform shall be in PCC 1:2:4 type B1 using 20mm graded crushed stone aggregate (Foundation not less than 600mm above the ground level and not less than 300mm below the ground level) including necessary form work & 10mm thick cement plaster on exposed surfaces in CM 1:4 duly applied with three coats of white wash and quoted rate shall deemed inclusive of same.
V r traders
Gupta Suppliers
Suman Uni Controllers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .