AUGMENTATION OF WATER SUPPLY SCHEME FOR OTM AND MD ACCN UNDER GE N AKHNOOR
2026_MES_773669_2
GE(N)/AKH-43/2026-27
Open Tender
Civil Works
Item Rate
180 days
Akhnoor
Class D Cat b i
8 documents required · 8 mandatory
₹500
GE (N) Akhnoor
₹87,000
Yes
18 Aug 2026
18 Aug 2026
3 Sept 2026
18 Aug 2026
1 Sept 2026
25 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing & commissioning of multistage pump set with brass impellers, capable of discharge water approx at 250000 LPH at 125 MTR head, directly coupled with suitable energy efficient KPML motor, 180KW, 4 Phase, 415 V/TEFC/IE2, 50 cycle, coupling+coupling guard, mounted on MS channel common base plate and fixed with suitable bolts, grouted in PCC foundation in PCC (1:2:4), type B1,( using 20mm graded stone aggregates and rate of PCC work will be included in this item) 30 cm above floor level including making connections of inlet and outlet with fittings including nut bolts, packing and PVC insulated, unsheathed, copper conductor cable of suitable size, multistranded, in PVC conduit for connection from starter to motor with proper lugs of suitable size, pressure gauge of 0 to 10 kg/cm2 all as specified and as directed with following specifications.
Flow rated : 250000LPH
Differential head : 125 Mtr
Speed : 1487 rpm at 50 Hz
Impeller dia : 380/304 mm
Efficiency : 68%
Liquid type : Soft Water
Max Working pressure : 13.89 bar.g
Allowed working pressure : 29.17 bar.g
Allowed suction pressure : 4.9 bar.g
Power rating : 180KW/241Hp
Note:- Making of foundation including chasis ,grounding nut bolt and all other fixing arrangement for Pump set as directed by Engr-in-Charge is include in quoted rate. | 1 | Each Job | - | - |
| 2 | Voltage stabilizer for automatic operation,three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ±1% and speed of correction 50 Volts per second and of capacity 500KVA having following protection:- frequency - 50 HZ, Capacity overload - 20% over load for one hour ,Protection - overload and short circuit through microprocessor based MCCB, Indoor type ,Unbalance type ,Suitable for all power factor all as specified and directed. | 1 | Each | - | - |
| 3 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 Sqmm 3.5 core all as specified and directed. | 100 | RM | - | - |
| 4 | Supply, laying, jointing and testing flexible copper cable insulated, earthed, heavy duty electric cable with copper conductor , 1100 Volt grade, cross sectional area 150 sqmm single core (For making connections from starter panel to booster pump) including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed. | 72 | RM | - | - |
| 5 | Supply, laying & testing of MS ERW Steel Pipe including specials, nominal dia 200 mm of thickness 6.0 mm with nut/ bolt, flanges at both endswith welding as required. Makes : Tata Steel, Prakash Surya, Jindal as approved by GE all as specified and directed. | 48 | RM | - | - |
| 6 | Supply, laying & testing of MS ERW Steel Pipe including specials, nominal dia 150 mm thickness 6.0 mm with nut/ bolt, flanges at both endswith welding as required. Makes : Tata Steel, Prakash Surya, Jindal as approved by GE all as specified and directed | 54 | RM | - | - |
| 7 | Voltage stabilizer for automatic operation,three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ±1% and speed of correction 50 Volts per second and of capacity 200 KVA having following protection:- frequency - 50 HZ, Capacity overload - 20% over load for one hour ,Protection - overload and short circuit through microprocessor based MCCB, Indoor type ,Unbalance type ,Suitable for all power factor all as specified and directed. | 1 | Each | - | - |
| 8 | "Supply, installation. testing and commissioning of CPRI approved manned type Solid state , 3-phase ,415 Volts, 50 Hz ac electric automatic motor protection and control panel (Air break star-delta auto starter fabricated out of suitable L&T. Power contactors) of 250HP/400 Amps. Rating for 250 HP (HC/ VT/Sub.) motor pump set
features:-
fabricated out of CRCA metal sheet of appropriate size & dimensions with the following specifications &
POWER HANDLING UNIT (AUTO-STARTER) :
Fabrication of Power Handling Unit (PHU) / Auto Starter with power contactor MNX-400-2Nos.+ MNX- 185-1No. of L&T make along with MCCB of 400 ampere rating also of L&T make.
2) The system should be provided with a solid state fault analyzer cum controller (CC-4P) of schneider/L&T / Guardian make.
3) The complete system should be enclosed in a floor / wall mounted MS sheet enclosure / box of suitable gauge and dimensions with proper entry and exit holes for incoming and outgoing cables. The enclosure should be finished with powder coated painting from inside as well as from outer surface of approved colour. Job also includes mounting of the panel to the wall / floor of the pump room.
"METERING: The enclosure should be front shutter mounted with key locking system having glass window. Digital electronic voltmeter & ampere meter should be provided along with the required current transformer and selector switches. The internal control wiring should be done with flexible PVC LT cable with proper thimbing at each end". | 1 | Each | - | - |
| 9 | Contd...8/-
FEATURES AND SPECIFICATIONS:
5) The system should trip the motor on power failure and on appearance of an electrical fault mentioned below which may otherwise damage the motor field coils and should not restart automatically until unless the system is reset manually, thus providing automation to the system and protection to the motor.
6) The system shall provide protection against: -
a. Low voltage below 350 V
b) High Voltage above 450 V c) Single phasing
d) Reverse phasing
(e) Un Balanced phasing
(f) Overloading."
"NFORMATION SECTION: -
In addition, the system should have the following audio & visual features for a quick and accurat
diagnosis of the appeared fault
/ status for a speedy rectification of the system--
7) Separate LED fault / status indicators.
8) LED phase indicators-3Nos.
9) An isolation by pass system with a blinking indicator.
10) 3 LED, contactor 'COIL OK', indicators, one for each of the contactors / coils. INo.
11) 1No. LED star & delta indicator to check the star to delta timing.
12) A tamper proof starting system to avoid manipulations by the motor operator to keep the syst a permanently ON position." | - | - | - | - |
| 10 | "Supply, installation. testing and commissioning of CPRI approved manned type Solid state , 3-phase ,415 Volts, 50 Hz ac electric automatic motor protection and control panel (Air break star-delta auto starter fabricated out of suitable L&T. Power contactors) of 125HP/185 Amps. Rating for 125 HP (HC/ VT/Sub.) motor pump set
features:-
fabricated out of CRCA metal sheet of appropriate size & dimensions with the following specifications &
POWER HANDLING UNIT (AUTO-STARTER) :
Fabrication of Power Handling Unit (PHU) / Auto Starter with power contactor MNX-185-2Nos.+ MNX- 110-1No. of L&T make along with MCCB of 250 ampere rating also of L&T make.
2) The system should be provided with a solid state fault analyzer cum controller (CC-4P) of schneider/L&T / Guardian make.
3) The complete system should be enclosed in a floor / wall mounted MS sheet enclosure / box of suitable gauge and dimensions with proper entry and exit holes for incoming and outgoing cables. The enclosure should be finished with powder coated painting from inside as well as from outer surface of approved colour. Job also includes mounting of the panel to the wall / floor of the pump room.
"METERING:
The enclosure should be front shutter mounted with key locking system having glass window. Digital electronic voltmeter & ampere meter should be provided along with the required current transformer and selector switches. The internal control wiring should be done with flexible PVC LT cable with proper thimbing at each end". | 1 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.46 MB
Tender432627.pdf
Tender Documents • 1.03 MB
BOQ_879566.xls
BOQ • 1.95 MB
Corrigendum432ndcall.pdf
PDF • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].