Executive Engineer (EnM) WnS (WEST)
C-2A Block Janakpuri BPS New Delhi-110058.
Replacement of LT Panel with All Allied Electrical Equipment at DG-III in Vikaspuri Constituency.
2020_DJB_194800_15
e-NIT No.12 / EnM (WEST)/ 2020-21
Open Tender
Miscellaneous Works
Works
30 days
C-2A Block Janakpuri BPS New Delhi
Please refer Tender Documents.
3 documents required · 3 mandatory
₹500
Yes
DJB Account No. 50448339804
₹6,600
Yes
9 Oct 2020
21 Sept 2020
29 Sept 2020
21 Sept 2020
29 Sept 2020
21 Sept 2020
Dismantling of old/existing panel from site after disconnecting the incoming and outgoing electric supply and shifting the material to store.
Fabrication of starter panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP-54 protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipments of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1200MM x1000x350mm. Having following components of approved make.
MCCB 415V, TP 3phase 50KA 50Hz,250Amp with spreader - Make L&T
MCB Single pole 6Amp. Make L&T/Havells
Power capacitors 415V unit of 15Kvar Make: Epcos
Over load relay 45-75Make: L&T/siemens
Digital Amp. Meter Make AE/L&T
Digital Volt Meter0-500V -Make AE/L&T
Motor protection Relay Make: L&T/Siemens/Protech
Power contactor 220V 3phase110Amp. Make L&T/siemens
Power contactor 220V 3phase95Amp. Make L&T/siemens
Add on block 2NO +NC Make: L&T/Siemens
Star delta timer on delay Make: L&T/Siemens
Indicating lights LED type RYB & On/OFF Make : L&T /Havells
Push Button ON/OFF Make: SG/L&T
Current Transformer200/5 Make:AE /Advance/Saviour
Current Transformer100/5 Make:AE /Advance/Saviour
On load change over switch 200 Amp. Open execution type Make:L&T
Fitting of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hard wares complete in all respect.
Loading ,unloading by crane or heavy labor and cartage up to site cleaning & dressing the surface for Installation of the panel at site on base frame ,laying of cable, termination of cable both incoming & out going side
Testing & commissioning of panel, as per required parameters with relevant IS .testing of the panel prior to switching on as follow i) Continuity and earth testing ii) Meggaring of all equipment’s for phase to phase, neutral to body, neutral to earth and phase to earth. iii) checking for all tightness of nut and bolts iv) Alignments of doors etc. v) Interlocking tests. All function tests
DAYAL TRADERS
APU Engineering Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .