Loading…
Loading…
Tender Value
₹3.3 Cr
EMD Value
₹3.3 L
Closing Date
28 Aug 2026, 11:00 am5d left
Special repair work at JNV Dhenkanal (Odisha)
NBCC/SBG/ODISHA/NIT/26-27/44
NBCC/SBG/ODISHA/NIT/26-27/44
Open Tender-Domestic
Civil Works - Buildings
Dhenkanal, Odisha
₹11,800
₹3.3 L
21 Aug 2026
21 Aug 2026
28 Aug 2026
28 Aug 2026
Name of Work:-Special repair work at JNV Dhenkanal (Odisha)
Sl. No Description Amount (in Rs.)
Schedule Non-Schedule Total
1 External Electrical Works 57,12,370.00 1,36,09,800.00 1,93,22,170.00
Internal electrical Works of School Building & miscellaneous
3 Minor Repair Work in School Building,Girls & Boys Dormitory 61,56,606.69 - 61,56,606.69
Grand-Total 3,30,99,536.00
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
" External Electrical Works at JNV Dhenkanal”.
Bill of Quantities
Sl No. Description Unit Quantity Rate (Rs.) Amount (Rs.)
Schedule Non-Schedule Schedule Non-Schedule
Fabrication, Supply, Installation , testing and Commissioning of 400 Amps , 415V, 125 amp TPN Switch
1 NDSR Disconnector (SFU), 415V, 3 phase with neutral feeder panel etc. as required with HRC Fuse/Kit Kat Nos. 1 1,52,000.00 - 1,52,000.00
arrangement for double feeder outgoing.
Fabrication, Supply, Installation , testing and Commissioning of 100 amp, 415V, 3 phase with neutral Bus-
Bar panel etc. as required including timer for street lights & for four outgoing feeders.
Fabrication, Supply, Installation , testing and Commissioning of 63 amp, 415V, 3 phase with neutral Bus-Bar
panel etc. as required for domestic feeders along with required size of MCCBs.
Supply & Fixing of 250 mm × 200 mm size Fibre Reinforced Plastic (FRP) Junction Box including 4-way
connector with 01 no. (6 amp) MCB etc. as required.
Supplying , Testing and Commissioning of 1.1 KV grade Aluminium XLPE power cable of following size suitable
for 415 Volt, 3Ph, 50 c/s supply.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size
6 10.1 direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as - -
7 13.42 Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. Each 60 3,378.00 2,02,680.00 -
Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms,
insulators etc. as required.
Earthing with G.I. earth pipe 3 Meter long, 150 mm dia including accessories, and providing masonry
9 NDSR enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt) Nos. 50 8,500.00 - 4,25,000.00
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend,
10 15.15 couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing - -
trench, complete as required.
Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded
11 10.9 stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top Nos. 75 683.00 51,225.00 -
with a thickness of 10cm including inscription duly engraved as required.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and
shuttering - All work up to plinth level :
1:2:4 (1 cement : 2 coarse sand (zone-lll) derived from natural sources : 4 graded stone aggregate 20 mm
nominal size derived from natural sources)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of
PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
Excavation of existing bituminous/concrete road by using excavator/JCB/groove cutting machine to facilitate
15 NDSR laying of UG cable including disposal of material within 50 m lead and providing and laying in position 1:2:4 meter 500 1,500.00 - 7,50,000.00
all works up to plinth level to fill up the excavated trenches after laying of cable.
Supply and erection of 6 mtr octagonal pole (Top: 70 mm, Bottom: 130 mm, Thickness: 3 mm) with base
16 NDSR plate 425 × 425 × 12 mm, P.C.D.: 425 mm with 4 nos. holes of M26, hot dip galvanized including foundation Each 40 15,000.00 - 6,00,000.00
and foundation bolts.
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
" External Electrical Works at JNV Dhenkanal”.
Bill of Quantities
Sl No. Description Unit Quantity Rate (Rs.) Amount (Rs.)
LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135
lm/Watt).Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure
die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%,
Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge
protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P.
F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection,EMI-EMC as per CISPR-15, lenses
for beam angleas per IESNA type I/II/III as per the width of the roadand the project requirement., suitable
to fit in up to65mm dia pipe, life time (LED,Driver & electricalcircuitary) of minimum 50000 Burning Hourswith
17 8.14 70% of initial Lumen maintained till lifeends as per LM80 extrapolation IES TM-21-11report, CCT 3000° K / - -
4000°K / 5700°K /6500°K (Asper ANSI Bin), SDCM(Standard Deviation ColorMatching) <5, Maximum power
consumption shouldnot more than the specified rating and Fixture shallbe of relevant BIS standard complete
in all51DELHI SCHEDULE OF RATES (E&M)-2025respect i/c external connections with 1.5 sq mm FRLS/HFFR,
PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM
warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for
LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge
as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction
temperature shall not rise above 90°C).
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for
18 2.10 inductive load of following poles in the existing MCB DB complete with connections, testing and - -
commissioning etc. as required.
Supply of Erection of 20 Mtrs. High Mast Tower polygonal shape shaft suitable for 6 luminaires (symmetric),
suitable for wind speed up to 180 km/hr.
Material conforms to BS EN 10025.
High mast accessories & mechanical components including head frame & pulley assembly, winch bracket,
lantern carriage ring, guide ring, compensating disc, lightning arrestor, etc.
Including wire rope, safety wire rope, D-shackle clamps, nuts and bolts, foundation accessories, winch
assembly, cable & power tools (motor).
Top Dia: 150 mm, Bottom Dia: 450 mm, Thickness: 4.3 mm.
LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >135 lm/Watt)
Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium
body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input
voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge
protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P.
F. ≥ 0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection,54DELHI SCHEDULE OF RATES
(E&M)-2025EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the
project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000
20 8.17 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 - -
report, CCT 3000 ° K / 4000 ° K / 5700 ° K /6500 ° K (As per ANSI Bin) , SDCM(Standard Deviation Colour
Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of
relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC
insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM
warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for
LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge
as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction
temperature shall not rise above 90°C).
Providing RCC foundation for 20 m high mast including excavation, PCC, reinforcement, anchor bolt fixing,
concreting, curing and backfilling complete as per approved drawing.
Total (Schedule + Non Schedule) 1,93,22,170.00
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
" Internal Electrical Works For School Admin Building and miscellaneous work at JNV Dhenkanal”.
Bill of Quantities
Sl No. Description Unit Quantity Rate (Rs.) Amount (Rs.)
Schedule Non-Schedule Schedule Non-Schedule
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm
FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed
1 1.1 steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box - -
and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor
single core cable etc. as required.
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm
FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm
FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing
surface/ recessed steel/PVC conduit including dismantling as required.
Wiring for circuit/submain wiring along with earth wire with the following sizes of
3 1.14 FRLS PVC insulated copper conductor, single core cable in surface/recessed medium - -
class PVC conduit as required:
Supplying and fixing of following sizes of medium class PVC conduit along with
4 1.21 accessories in surface/recess including cutting the wall and making good the same in - -
case of recessed conduit as required.
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor,
single core cable in the existing surface/ recessed steel/ PVC conduit as required.
Dismantling of existing damaged/unwanted wirings, switch boards, DBs & other
accessories including angle iron frame etc. as required after disconnecting the power,
including making temporary arrangement for power and making good the damages
etc., complete as required.
Supplying and fixing following size/ modules, GI box along with modular base &
cover plate for modular switches in recess etc. as required.
Supplying and fixing following modular switch/ socket on the existing modular plate
& switch box including connections but excluding modular plate etc. as required.
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
" Internal Electrical Works For School Admin Building and miscellaneous work at JNV Dhenkanal”.
Bill of Quantities
8.5 1.24.7 TV antenna socket outlet Each 60 168.00 10,080.00 -
Supplying and fixing two module stepped type electronic fan regulator on the
9 1.25 existing modular plate switch box including connections but excluding modular plate Each 60 402.00 24,120.00 -
etc. as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden
block including connections etc. as required.
12 1.34 Supplying and fixing brass batten/ angle holder including connection etc. as required. Each 120 154.00 18,480.00 -
Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar,
neutral bus bar, earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)
13.2 NDSR 2 Way , Single Door Each 60 1,000.00 - 60,000.00
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature
14 2.10 circuit breaker suitable for inductive load of following poles in the existing MCB DB - -
complete with connections, testing and commissioning etc. as required.
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
" Internal Electrical Works For School Admin Building and miscellaneous work at JNV Dhenkanal”.
Bill of Quantities
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc.
LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation,
Testing & Commissioning of LED surface mounted Batten light of following body
material and construction as per IS : 10322 with driver (Replaceable) as per the
requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt,
frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection
of 2.5 KVwith Short & Open circuit protection ,THD < 10% , P.F. ≥ 0.95, IP20, CRI
>80, Flicker free (flicker shouldbe below 5 %), life time (LED, Driver & electrical
circuitry), of minimum 50000 Burning Hours 47DELHI SCHEDULE OF RATES (E&M)-
2025with 70% of initial Lumen maintained till life ends, CCT 3000 ° K / 4000 ° K /
5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3,
Maximum power consumption should not more than the specified rating and Fixture
shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/
Embossing/ Screen printing on housing complete in all respect i/c external
connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core
cable and earthing etc. as required with Minimum 5 year OEM warranty. System
lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing
required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be
as approved by Engineer-in-Charge as per requirement. (Thermal management:
heat sink of aluminium housing such that LED junction temperature shall not rise
Powder coated die cast /Extruded aluminium
Body (Thickness > 1.20 mm)
Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct
Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades,
30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding,
steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as
below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion)
17 9.1 less than 10%, remote (preferably mobile app based) for speed control and all - -
remaining accessories including safety pin, nut bolts, washers, temperature rise=75
0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz,
single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external
connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core
cable and earthing etc. as required.
17.1 9.1.3 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) Each 90 2,882.00 2,59,380.00 -
Supplying of 250mm dia Exhaust Fan suitable for rating of 230-250 V, 50Hz co with
all accessories such as Mounting frame, louvers etc. complete in all respect
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
" Internal Electrical Works For School Admin Building and miscellaneous work at JNV Dhenkanal”.
Bill of Quantities
Installation, Testing and Commissioning of exhaust fan in the existing opening,
19 1.50 including making good the damage, connection, testing, commissioning etc. as - -
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all
Making hole for installation of exhaust fan of size upto 450mm sweep by demolishing
brick workmanually/by mechanical means including disposal ofmalba within 50
meters lead and making good the wallby plastering etc. as required. (DSR Civil 2023
item no. 15.7.4 and 13.1.2)
12 mm cement plaster of mix:
1:6 (1 cement : 6 fine sand)
Demolishing brick work manually / by mechanical means including stacking of
21.2 15.7.4 serviceable material and disposal of unserviceable material within 50 metres lead as cum 2.00 2,060.00 4,120.00 -
per direction of Engineer-in-Charge.
Supplying and fixing metal box of following sizes (nominal size) on surface or in
22 1.22 recess with suitable size of phenolic laminated sheet cover in front including painting - -
etc. as required.
Supplying and fixing following modular switch/ socket on the existing modular plate
& switch box including connections but excluding modular plate etc. as required.
Supplying and fixing 40 A rating, 240 V, 10 kA, "C" curve, Double Pole miniature
24 NDSR circuit breaker suitable for inductive load in the existing surface, complete with Each 30 1,400.00 - 42,000.00
connections, testing and commissioning etc. as required.
Fabrication, Supply, Installation , testing and Commissioning of 200 Amps or as
25 NDSR required , 415V Main LT Panel Distribution Box complete as per per direction of Each 1 30,000.00 - 30,000.00
Engineer-In Charge.
Total (Schedule + Non-Schedule) 76,20,759.40
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
Minor Repair Work in School Building,Girls & Boys Dormitory at JNV, Dhenknal , ODISHA
Sl No Item Description Units Total Qty Rate (in Rs.) Amount (in Rs.)
Schedule Non-Schedule Schedule Non-Schedule
E. Repairs to Door/Windows
Dismantling doors, windows and clerestory windows (steel or wood) shutter
85 15.12 including chowkhats, architrave, holdfasts etc. complete and stacking within
50 metres lead :
15.12.1 Of area 3 sq. metres and below Nos 80.00 367.20 29,376.00
86 14.9 Renewal of old putty of glass panes (length) Mtr 600.00 56.15 33,690.00
Providing and fixing bright finished brass single acting spring hinges with
necessary brass screws etc. complete :
Providing and fixing factory made single extruded WPC (Wood Polymer
Composite) solid plain flush door shutter of required size comprising of virgin
polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural
fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum
toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and
screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum
88 26.87 compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and
resistance to spread of flame of Class A category with property of being
termite/borer proof, water/moisture proof and fire retardant and fixing with
stainless steel butt hinges of required size with necessary full body threaded
star headed counter sunk S.S screws, all as per direction of Engineer-In
Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be
paid separately)
Providing and fixing wire gauge shutters using galvanized M.S. wire gauge
of average width of aperture 1.4 mm in both directions with wire of dia 0.63
mm, for doors, windows and clerestory windows with hinges and necessary
9.27.2 30 mm thick shutters
9.27.2.2 With ISI marked stainless steel butt hinges of required size 20.00
9.27.2.2.2 Kiln seasoned and chemically treated hollock wood Sqm 20.00 3,447.80 68,956.00
Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and
screws etc. complete : (Copper oxidized as per IS 1378).
Providing and fixing ISI marked flush door shutter conforming to IS :2202 (Part I) non
decorative type, core of block board construction with frame of 1st class hard wood and
91 9.21.3 well matched commercial 3 ply veneerong with vertical grains or cross bands and face Sqm 20.00 2,093.70 41,874.00
veneers on both faces of shutters:25 mm thick (for cupboard) including ISI marked niclel
plated bright finished M.S. piano Hinges with necessary screws
Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel
type) with necessary screws etc. complete : (Copper oxidized as per IS : 1378).
Providing and fixing aluminium handles, ISI marked, anodised (anodic coating
93 9.100 not less than grade AC 10 as per IS : 1868) transparent or dyed to required
colour or shade, with necessary screws etc. complete :
Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised
94 9.101 (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed
to required colour and shade, with necessary screws etc. complete.
9.101.2 Twin rubber stopper Nos 20.00 72.35 1,447.00
Providing and fixing 2nd class teak wood lipping/ moulded beading or taj beading of size
95 9.112 18X5 mm fixed with wooden adhesive of approved quality and screws/nails on the edges of Mtr 250.00 102.15 25,537.50
the Pre-laminated particle board as per direction of Engineer-in-charge.
Providing and fixing wooden moulded corner beading of triangular shape to
96 9.111 the junction of panelling etc. with iron screws, plugs and priming coat on
unexposed surface etc. complete 2nd class teak wood.
Providing and fixing magnetic catcher of approved quality in cupboard / ward
robe shutters, including fixing with necessary screws etc. complete.
9.114.1 Triple strip vertical type Mtr 25.00 52.50 1,312.50
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
Minor Repair Work in School Building,Girls & Boys Dormitory at JNV, Dhenknal , ODISHA
Sl No Item Description Units Total Qty Rate (in Rs.) Amount (in Rs.)
Providing and fixing wooden moulded beading to door and window frames with
iron screws, plugs and priming coat on unexposed surface etc. complete :
9.40.2 Kiln seasoned and chemically treated hollock wood
Providing and fixing ISI marked oxidised M.S. single acting spring hinges with
necessary screws etc. complete. (Copper oxidized as per IS 1378).
Providing and fixing nickel plated M.S. pipe curtain rods with nickel plated
Providing and fixing pressed steel door frames conforming to IS: 4351,
manufactured from commercial mild steel sheet of 1.60 mm thickness, including
hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle
of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or
rigidly fixed together by mechanical means, including M.S. pressed butt hinges
2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as
specified and applying a coat of approved steel primer after pre-treatment of
the surface as directed by Engineer-in-charge:
Providing and fixing factory made ISI marked steel glazed doors, windows and
ventilators, side /top /centre hung, with beading and all members such as
F7D,F4B, K11 B and K12 B etc. complete of standard rolled steel sections, joints
102 10.11 mitred and flash butt welded and sash bars tenoned and riveted, including
providing and fixing of hinges, pivots, including priming coat of approved steel
primer, but excluding the cost of other fittings, complete all as per approved
design, (sectional weight of only steel members shall be measured for payment).
Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block
10.11.1 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate Kg 200.00 131.05 26,210.00
20 mm nominal size) @22 Kg/Sqm
Providing and fixing M.S. grills of required pattern in frames of windows etc.
103 9.48 with M.S. flats, square or round bars etc. including priming coat with approved
steel primer all complete.
9.48.2 Fixed to openings /wooden frames with rawl plugs screws etc. Kg 576.00 238.35 1,37,289.60
Providing and fixing T-iron frames for doors, windows and ventilators of mild
104 10.13 steel Tee-sections, joints mitred and welded, including fixing of necessary butt
hinges and screws and applying a priming coat of approved steel primer.
Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block
10.13.1 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate Kg 500.00 141.70 70,850.00
20 mm nominal size).
Providing and fixing oxidised M.S. casement stays (straight peg type) with
necessary screws etc. complete. (Copper oxidized as per IS : 1378).
9.68.1 300 mm weighing not less than 330 grams Nos 20.00 67.40 1,348.00
9.68.2 250 mm weighing not less than 280 grams Nos 30.00 61.05 1,831.50
Providing & fixing glass panes with putty and glazing clips in steel doors,
windows, clerestory windows, all complete with :
10.30.1 4.0 mm thick glass panes (weight not less than 10 kg/ sqm) Sqm 98.44 1,390.15 1,36,846.37
Providing and fixing PVC rigid foam sheet 1 mm thick on existing door shutters
(bathroom and W.C. doors) using synthetic rubber based adhesive.
108 13.50 Applying priming coat:
With ready mixed aluminum primer of approved brand and manufacture on resinous wood
Painting with synthetic enamel paint of approved brand and manufacture of
required colour to give an even shade :
Two or more coats on new work over an under coat of suitable shade with
ordinary paint of approved brand and manufacture
Providing and fixing fly proof galvanized M.S. wire gauge to windows
and clerestory windows using wire gauge with average width of aperture
1.4 mm in both directions with wire of dia 0.63 mm all complete.
9,51,1 With 2nd class teak wood beading 62X19 mm Sqm 500.00 1,308.35 6,54,175.00
Digitally signed by JAYA
Special repair work at JNV Dhenkanal (Odisha)
Minor Repair Work in School Building,Girls & Boys Dormitory at JNV, Dhenknal , ODISHA
Sl No Item Description Units Total Qty Rate (in Rs.) Amount (in Rs.)
F. Repairs to Flooring
Demolishing cement concrete manually/ by mechanical means including
110 15.2 disposal of material within 50 metres lead as per direction of Engineer - in
15.2.2 Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix) Cum 100.00 1,503.60 1,50,360.00
Providing and laying in position cement concrete of specified grade excluding
the cost of centering and shuttering - All work up to plinth level :
1:5:10 (1 cement : 5 coarse sand (zone-III) derived from natural sources : 10 graded
stone aggregate 40 mm nominal size derived from natural sources
Providing and laying in position cement concrete of specified grade excluding
the cost of centering and shuttering - All work up to plinth level :
1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded
stone aggregate 20 mm nominal size derived from natural sources)
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed
with grey cement slurry mixed with pigment to match the shade of the slab,
including rubbing and polishing complete with base of cement mortar 1 : 4 (1
cement : 4 coarse sand) :
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid
on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and
jointed with grey cement slurry mixed with pigment to match the shade of the
slabs, including rubbing and polishing complete.
Providing and laying Vitrified tiles in different sizes (thickness to be specified
by manufacturer), with water absorption less than 0.08 % and conforming to
I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps,
over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing
with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white
cement & matching pigments etc. complete.
Marble stone flooring with 18 mm thick marble stone, as per sample of marble
approved by Engineer-in-charge, over 20 mm (average) thick base of cement
mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cement slurry,
including rubbing and polishing complete with :
11.23.5 Udaipur green marble Sqm 250.00 2,428.60 6,07,150.00
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
117 11.3 aggregate) finished with a floating coat of neat cement, including cement slurry,
but excluding the cost of nosing of steps etc. complete.
11.3.1 40 mm thick with 20 mm nominal size stone aggregate Mtr 30.00 614.20 18,426.00
Repairs to Flooring Works Total : 61,56,606.69 -
Total (Schedule + Non-
Digitally signed by JAYA
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
PMC_GCC_2026 with Amendment02.pdf
Tender Document
SCC.pdf
Tender Document
Technical Specification.pdf
Tender Document
Milestone.pdf
Tender Document
BOQ.pdf
Tender Document
LIST OF APPROVED MAKES.pdf
Tender Document
Technical Circular.pdf
Tender Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].