| Sl No | Description | Qty | Unit | FAVOURITE ELECTRICALS L1 |
|---|---|---|---|---|
| 1.00Heat Pump Supply , installation , testing & commissioning of Micro Processor Controlled air cooled Heat pump delivering actual capacity as per the following parameters duly installed at site. Heat pumps shall be reversible air cooled Scroll type, with environment friendly refrigerant R-410a. Heat pump Shall have minimum 2 Compressors with independent circuits. The overall support frame and bottom plate of the unit Shall be made of galvanized steel sheet whose outer surface has to be painted, with high strength and strong anti-corrosion ability. The unit shall be equipped with compressor and refrigeration components as standard protective panels to protect the unit and effectively block noise transmission. It shall have silent operation and the sound level should not exceed 70 dB at 1 meter from the unit. The compressor motor should adopt suction cooling and there should be no directly contact with lubricating oil. Evaporator used must be high quality shell and tube/platetype heat exchanger. The close-cell thermal insulation material should be attached on the exchanger to prevent condensation on the external surface. The electric heater inside the exchanger shall be provided to avoid freezing in extreme environment. Unit must be capable to manage defrost cycles as per the prevailing environmental conditions.The air-side heat exchanger shall be finned tube type with U/H-shaped design to increase the effective area of heat exchange and have a high heat transfer effect. Copper tubes must be internally threaded, which also increases heat exchange area and refrigerant disturbance to improve heat transfer. Refrigerant cycle must have Electronic Expansion valve, to precisely control the gas flow to optimize the evaporator's performance. EEV must adjust the system based on the superheat degree of suction gas for reliable running."Heat Pump mjust be provided with Intelligent microprocessor with human-machine interface screen able to manage unit efficiently, to network and communicate well, protection - when under alarm and alarm management functions. Multi-language menu, shortcut key, graphic unit status. Average compressor running time to extend unit working life." R-410a ( Refrigerant) Heating Mode: 80 kW Heating Capacity Hot Water In - 45 C Hot Water Out - 50 C Ambient - (-)minus 7 C Fouling Factor - 0.0180 COP at above conditions - 1.6 Cooling mode: 130 kW - Cooling Capacity Chilled Water In - 12 C Chilled Water Out - 7 C Ambient - 35 C Fouling Factor - 0.0180 COP at above conditions - 3.2 The job includes butterfly valves ( 2 no) , rubber expansion joints ( 2 no), balancing valves ( 1 no), dial type pressure gauge (2 no), dail type thermometer ( 2 no) , ball valves ( 2 no) and air vents of necessary sizes as recommended by OEM | ||||
| 1.01 | Heating Mode: 80 kW Heating Capacity ,Cooling mode: 130 kW - Cooling Capacity | 4 | Nos | 21,50,000 ₹86,00,000 Lowest |
| 2.00Providing, installation, testing and commissioning of following insulated pumps suitable for 415 Volts connected with T.E.F.C. induction motor, M.S.channel, base plate 3-phase electric supply complete with vibration isolators, isolating valve on suction and discharge, non return valve on discharge, pressure gauges and dial type thermometer with syphon and stop cock on suction and discharge. The pump shall have mechanical seal. | ||||
| 2.01 | Hot Water Primary Pumps alongwith providing and fitting of butterfly valves (2 n0.), y strainer (1 no) , check value (1 no) , dial pressure gauge ( 2 no) , dial type thermometer (1 no) .
Pump :
Flow - 8.0 L.P.S.
Head - 10 Mtrs
H.P. - 5.0 H.P. | 4 | Nos | 1,92,000 ₹7,68,000 Lowest |
| 2.02 | Hot Water Secondary Pump with VFD Panel. alongwith providing and fitting of butterfly valves (2 n0.), y strainer (1 no) , check value (1 no) , dial pressure gauge ( 2 no) , dial type thermometer (1 no) .
Pump:
Flow - 15 L.P.S.
Head - 30 mtrs
H.P. - As per OEM (1W+1 Standby) | 2 | Nos | 71,000 ₹1,42,000 Lowest |
| 3.00Double Skin Air Handiling Units. Supply, Installation, testing and commissioning of Floor Mounted/ Ceiling Suspended Hot/ chilled water factory built Air Handling Units Double skin type with 40 mm thick panels consisting of G.I casing of thickness 0.6 mm outside layer and 0.6 mm inside layer with zinc coating and polyurethene foam (PUF) insulation having density of 42 kg/m3, complete with backward curved Plug type direct driven fan withVFD suitable for static pressure as detailed below, Hot/ chilled water cooling coil with aluminium finned copper tubes. Filter section having 50 mm thick MERV-8 pre filters, TEFC, IE-3 motor suitable for 415+10% volts, 50 Hz, 3 phase AC supply, drain connections with stainless steel drain pan (18 Ga) with PUF insulation, fire retardent canvas connection and necessary vibration isolation arrangement to avoid any vibration alongwith etc. complete as per specifications and drawings. AHU shall be Eurovent certified. the All Valves accessories should be insulated. The job includes providing and fitting of butterfly valves (2 n0.), y strainer (1 no) , two way value (1 no) , dial pressure gauge ( 2 no), drain cocks (2 no) and dial type thermometer (2 no). | ||||
| 3.01 | 7500 CFM, 90 mmwg ESP,4/6 row deep (Horizontal Floor Mounted) | 2 | Nos | 7,20,000 ₹14,40,000 Lowest |
| 3.02 | 2500 CFM, 90 mmwg ESP, 4/6 row deep (Vertical Floor Mounted) | 2 | Nos | 4,50,000 ₹9,00,000 Lowest |
| 4.00 | SITC of Chilled water ductable unit of following capacities along with ball valves (2 no), Y- strainer (1 no) and two way valve (1 no)-
6 TR | 2 | Nos | 50,000 ₹1,00,000 Lowest |
| 5.00Providing, fixing, testing and commissioning Hot Water MS Heavy Class Pipe with all necessary fittings, i.e. bends, tees, ecentric reducer, Unions, flanges, supports/ anchors as required including cutting holes in walls, ceiling and floor making good the same, final connections to equipments complete as per drawings and specifications. the pipes shall be insulated with 25mm thick EPDM/Nitrile/ closed cell polyethylene /rock wool and finished with Alluminium sheet 28 G. | ||||
Tender Value
₹2.1 Cr
EMD Value
₹4.3 L
Closing Date
1 Dec 2025, 4:00 pmClosed
Executive Engineer RnB Mech. Central KmR
Executive Engineer RnB Mech. Central KmR, PMGSY Building Rajbagh
HVAC (Reversible Chiller) at Tagore Hall Srinagar
2025_PWDJK_295192_1
RnB/MDCK/NIT/19
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
60 days
Tagore Hall Srinagar
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,500
Ex. Engineer RnB Central KmR Mech.
₹4.3 L
9 Dec 2025
14 Nov 2025
2 Dec 2025
15 Nov 2025
1 Dec 2025
15 Nov 2025
Amount
Heat Pump Supply , installation , testing & commissioning of Micro Processor Controlled air cooled Heat pump delivering actual capacity as per the following parameters duly installed at site. Heat pumps shall be reversible air cooled Scroll type, with environment friendly refrigerant R-410a. Heat pump Shall have minimum 2 Compressors with independent circuits. The overall support frame and bottom plate of the unit Shall be made of galvanized steel sheet whose outer surface has to be painted, with high strength and strong anti-corrosion ability. The unit shall be equipped with compressor and refrigeration components as standard protective panels to protect the unit and effectively block noise transmission. It shall have silent operation and the sound level should not exceed 70 dB at 1 meter from the unit. The compressor motor should adopt suction cooling and there should be no directly contact with lubricating oil. Evaporator used must be high quality shell and tube/platetype heat exchanger. The close-cell thermal insulation material should be attached on the exchanger to prevent condensation on the external surface. The electric heater inside the exchanger shall be provided to avoid freezing in extreme environment. Unit must be capable to manage defrost cycles as per the prevailing environmental conditions.The air-side heat exchanger shall be finned tube type with U/H-shaped design to increase the effective area of heat exchange and have a high heat transfer effect. Copper tubes must be internally threaded, which also increases heat exchange area and refrigerant disturbance to improve heat transfer. Refrigerant cycle must have Electronic Expansion valve, to precisely control the gas flow to optimize the evaporator's performance. EEV must adjust the system based on the superheat degree of suction gas for reliable running."Heat Pump mjust be provided with Intelligent microprocessor with human-machine interface screen able to manage unit efficiently, to network and communicate well, protection - when under alarm and alarm management functions. Multi-language menu, shortcut key, graphic unit status. Average compressor running time to extend unit working life." R-410a ( Refrigerant) Heating Mode: 80 kW Heating Capacity Hot Water In - 45 C Hot Water Out - 50 C Ambient - (-)minus 7 C Fouling Factor - 0.0180 COP at above conditions - 1.6 Cooling mode: 130 kW - Cooling Capacity Chilled Water In - 12 C Chilled Water Out - 7 C Ambient - 35 C Fouling Factor - 0.0180 COP at above conditions - 3.2 The job includes butterfly valves ( 2 no) , rubber expansion joints ( 2 no), balancing valves ( 1 no), dial type pressure gauge (2 no), dail type thermometer ( 2 no) , ball valves ( 2 no) and air vents of necessary sizes as recommended by OEM
Heating Mode: 80 kW Heating Capacity ,Cooling mode: 130 kW - Cooling Capacity
Providing, installation, testing and commissioning of following insulated pumps suitable for 415 Volts connected with T.E.F.C. induction motor, M.S.channel, base plate 3-phase electric supply complete with vibration isolators, isolating valve on suction and discharge, non return valve on discharge, pressure gauges and dial type thermometer with syphon and stop cock on suction and discharge. The pump shall have mechanical seal.
Hot Water Primary Pumps alongwith providing and fitting of butterfly valves (2 n0.), y strainer (1 no) , check value (1 no) , dial pressure gauge ( 2 no) , dial type thermometer (1 no) . Pump : Flow - 8.0 L.P.S. Head - 10 Mtrs H.P. - 5.0 H.P.
Hot Water Secondary Pump with VFD Panel. alongwith providing and fitting of butterfly valves (2 n0.), y strainer (1 no) , check value (1 no) , dial pressure gauge ( 2 no) , dial type thermometer (1 no) . Pump: Flow - 15 L.P.S. Head - 30 mtrs H.P. - As per OEM (1W+1 Standby)
Double Skin Air Handiling Units. Supply, Installation, testing and commissioning of Floor Mounted/ Ceiling Suspended Hot/ chilled water factory built Air Handling Units Double skin type with 40 mm thick panels consisting of G.I casing of thickness 0.6 mm outside layer and 0.6 mm inside layer with zinc coating and polyurethene foam (PUF) insulation having density of 42 kg/m3, complete with backward curved Plug type direct driven fan withVFD suitable for static pressure as detailed below, Hot/ chilled water cooling coil with aluminium finned copper tubes. Filter section having 50 mm thick MERV-8 pre filters, TEFC, IE-3 motor suitable for 415+10% volts, 50 Hz, 3 phase AC supply, drain connections with stainless steel drain pan (18 Ga) with PUF insulation, fire retardent canvas connection and necessary vibration isolation arrangement to avoid any vibration alongwith etc. complete as per specifications and drawings. AHU shall be Eurovent certified. the All Valves accessories should be insulated. The job includes providing and fitting of butterfly valves (2 n0.), y strainer (1 no) , two way value (1 no) , dial pressure gauge ( 2 no), drain cocks (2 no) and dial type thermometer (2 no).
7500 CFM, 90 mmwg ESP,4/6 row deep (Horizontal Floor Mounted)
2500 CFM, 90 mmwg ESP, 4/6 row deep (Vertical Floor Mounted)
SITC of Chilled water ductable unit of following capacities along with ball valves (2 no), Y- strainer (1 no) and two way valve (1 no)- 6 TR
Providing, fixing, testing and commissioning Hot Water MS Heavy Class Pipe with all necessary fittings, i.e. bends, tees, ecentric reducer, Unions, flanges, supports/ anchors as required including cutting holes in walls, ceiling and floor making good the same, final connections to equipments complete as per drawings and specifications. the pipes shall be insulated with 25mm thick EPDM/Nitrile/ closed cell polyethylene /rock wool and finished with Alluminium sheet 28 G.
125 mm dia
100 mm Dia.
80 mm dia
65 mm dia
50 mm dia
40 mm dia
32 mm dia
25 mm dia
SITC of Hi Wall units having static pressure as per OEM, complete OEM , of required cooling coil , suitable prefilter, along with ball valves (2 no), y strainer (1 no) and two way valve (1 no).
SITC of chilled Water FCU unit of following capacities with static pressure as per OEM, complete motor, of required cooling coil , suitable prefilter, insulated drain tray, along with ball valves (2 no), y strainer (1 no) and two way valve (1 no).
Supply, Installation and Testing of Site fabricated GSS rectangular ducting complete with vanes, splitters,gaskets hanging arrangement including fully threaded GI rods ,Hangers & Supports complete with end fixing as approved clients/consultants in accordance with the approved shop drawings and specifications. Quoted price shall be inclusive of necessary lifting & shifting charges towards installation of supply air ducts outside or within building wherever required.
Supply, installation, testing and commissioning of 500 litres capacity Pressurerised expansion tank complete with Pressure reducing valve,Pressure releif valve and pressurerization pump (2cmh and 25mWC. PN 10 )etc. The tank shall be duly insulatated as per the specifications. (1 W+1standby pump)
Supply, installation, testing and commissioning of Microbubbleair & Dirt Seperator with accessories the Air Seperator Connection dia shoud be up to 125 mm.
Supply and installation of following sizes of perforated GI cable tray made cut of 2 mm thick GI sheet, suspended from the ceiling or fixed on wall/column etc complete with suspenders, runners and fixing hard ware etc. as required.
50 mm x 150mm x 50 mm
50 mm x 50 mm x 50 mm
Dismantling of Existing System Like Chillers, Hot water pump, circulation pump, piping accessories, AHUs ect.
Supply and Installation of Linear Grill/ Diffuser
Supply and installation of Duct Dampers as per site requirement.
Supply and Installation of Jet Nozzle as per Site requirement
Supply & Installation of Duct Thermal Insulation Nitrile Rubber Insulation or Oxide Acetate Foam Insulation 13 mm Thick on various ducts complete with all accessories and finishes as per specifications Nitrile Rubber Insulation 13 mm
SITC of Duct Acoustic Insulation with Open-cell elastomeric foam based on synthetic rubber Insulation of Density 140 to 180 Kg/cum. in various ducts complete with all accessories & finishes as per specifications and any other item required to make the system complete. Thickness of Insulation in mm as indicated below:
15 mm Thick
Supply, laying, testing and commissioning of 1100 Volt grade PVC insulated aluminium conductor XLPE armoured cables including the cost of providing required gap between adjacent cables (minimum one cable dia.) and including the cost of providing identification tags, cable trays, stays, hangers etc. complete as per specification, as required.
2 Nos x 3.5C x 35 sq.mm
3.5C x 10 sq.mm
3C x 6 sq.mm
3C x 4 sq.mm
Supplying, receiving, storing, laying, effecting proper connections, testing and commissioning of the following sizes of 1.1 KV grade PVC insulated XLPE Aluminium conductor armoured stranded control cable complete as required and as per specifications.
2 Nos x 3.5C x 35 sq.mm
3.5C x 10 sq.mm
3C x 6 sq.mm
3C x 4 sq.mm
Supply, installation, testing and commissioning of following sizes of G.I. strip/wire clamped to walls, cable trays, bus ducts, cables in recess or surface etc for equipment/ System / Lightning protection earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps etc. and other fixing hardware material as required for proper installation.
25 x 3 mm strip
8 SWG wire
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Document
0.74 MB
BOQ
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .