GE E/M RR HOSP DELHI CANTT-10
GE E/M RR HOSP DELHI CANTT-10
GE/H/T-38 / 2026-27 SPL REPAIR TO OLD AND DAMAGED EARTHING OF VARIOUS BLDG AND ALLIED WORKS AT AHRR UNDER GE E/M R AND R HOSP DELHI CANTT-10
2026_MES_779853_1
GE/H/T-38/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE E/M RR HOSP DELHI CANTT-10
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE E/M RR HOSP DELHI CANTT-10
₹86,708
Yes
21 Jul 2026
21 Jul 2026
13 Aug 2026
21 Jul 2026
11 Aug 2026
4 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and fixing of 8 mm solid round Aluminium conductor manufactured from EC Grade Aluminium (Min Purity 99.5%) specifically designed for use as an air termination conductor, down conductor, and mesh conductor in external lightning protection system. The conductor shall be free from kinks, surface defects and mechanical damage. It shall be suitable for bending and fixing on standard lightning protection fixings without cracking all as per IEC 62561-2 and IEC 62305 including taking down GI strip of size 25X3 mm and air termination rods of size 12mm dia and 300 mm long all as specified and directed by Engr in charge. | 6,200 | RM | - | - |
| - | Supply and fixing UV stabilised PVC Holder with fasteners suitable for securing 8 mm aluminium conductor on Concrete, masonry, metal sheets, parapet walls and rooftop structures including all required bolts, nuts, washers and base plugs. It shall be designed for use in outdoor exposed environment and temperature variations and non metallic to avoid galvanic corrosion and ensure electrical isolation from the structure. It shall securely fix and support the conductor on rooftops, walls, parapets, and structures while maintaining proper routing and separation distance all as specified and as directed. | 6,200 | Each | - | - |
| - | M&L for cross connector made up of high quality Aluminium alloy used to join two conductors at right angles for creating a grid or bonding in the lightning protection work and to prevent galvanic corrosion. It shall electrically connect intersecting conductors and form lightning protection meshes or bonding networks,it shall have low electrical resistance and excellent corrosion resistance all as specified and as directed. | 120 | Each | - | - |
| - | M&L for expansion piece made up of Aluminium for 8 mm aluminium conductor allowing thermal expansion and contraction of long conductor runs preventing thermal stresses on conductors and breaking, stress or damage all as specified and as directed | 240 | Each | - | - |
| - | Maintenance free chemical earthing comprising of suitable Nos of earthing with specifications given:
(a) Copper bonded to MS earth rod of min size 17.2mm dia x 3 mtr long, ISI marked and IED 62561-2:2018 certified.
(b) Fixing of 8 mm Aluminium conductor to the main earth electrode by suitable means.
(c) Use of excel electrofill plus compound (IEC 62561 - 7: 2018 certified) mixed with soil having adequate moisture retention copability to a depth of approx one metre from the bottom the pit. (Approx-40 kg).
(d) Addition of carbon based RoHS & TCLP- certified electrofill compound (high conductivity), mixed with soil and water to form a slurry and filled upto 35 percent of the pit depth above the base compund layer (Approx-40 kg).
e) Add gravel at the top of the portion for easy passage of water and removal of air bubbles at the time of filling of electrofill plus excel compound is necessary for easy dissipation of fault current.
(f) Fixing of PVC earth pit chamber of size 24 x 24 cm with M8 SS 304- grade nut and bolts all as specified.
(g) FRP earthing display board 254x 380mm made out of plastic material showing information related to type of earthing, earthing result, due data of plastic hollow pipe of 20mm dia. Note- Cost of earthing and excavation incl in rate quoted. | 10 | Each Job | - | - |
| - | M & L in replacement of single pointed Franklin air termination copper bonded aluminium rod 17.3 mm dia 2 m long on roof surface for lightning interception on low height areas and connecting with the Aluminium earth conductor grid of lightning protection system complete with base, mounting brackets and conductor connection clamp all as directed and specified. | 7 | Each | - | - |
| - | M & L in replacement of Hot Dipped Galvanized steel mast of 5 m height complete with air terminal (Conventional spike of min 0.3 m height), base plate, anchor bolts and connection accessories providing high level lightning interception point increasing the protection radius on taller structures and connecting with the Aluminium earth conductor grid of lightning protection system complete all as directed and specified. | 3 | Each | - | - |
| - | M&L for test link/ test clamp made up of Aluminium/Copper bonded alloy, it shall be manufactured from high quality copper alloy or brass with excellent corrosion resistance and electrical conductivity, it shall comply with relevant standards (such as IEC 62561-1, BS EN 50164-1) for earthing and lightning protection complete with all fittings for 8 mm Aluminium conductor all as specified and as directed | 10 | Each | - | - |
| - | M &L in replacement of plate earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground vertically (in earth pit not less than 2.25m below normal ground level) with the top edge of the earth plate at a depth not less than 1.5m below normal ground level, the earth electrode surrounded by adequate quantity of clear coal dust and salt to a packed thickness of 15cm on all sides and incl galvanized iron strip 32 x 6 mm bolted (with nuts, bolts & check nuts) and revetted to earth plate at one end and connected to metallic bodies of equipments etc and also including 20 mm bore GI pipe medium grade from bottom of earth plate to ground level for watering complete with earth pit in PCC 1:2:4 type B-O using 12mm graded crushed stone aggregate and RCC cover, funnel, wire mesh including necessary excavation & earth work, etc as shown on electrical plate No 3 of SSR Part I complete all as specified and directed. Note :- PCC chamber shall be constructed at least 1.0 metre away from the earth pit and pipe for watering shall be provided in slanting manner. | 14 | Each Job | - | - |
| - | M & L in replacement of earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of size 32 mm x 6 mm galvanised iron strip complete all as specified and directed. | 180 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
T38Tender.pdf
Tender Documents • 1.14 MB
BOQ_873491.xls
BOQ • 0.33 MB
SOCT38.pdf
Additional Documents • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].