Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance LANE NO 4 FIRDOUSABAD BATAMALOO SRINAGAR SRINAGAR SRINAGAR JAMMU KASHMIR 190009 | SRINAGAR | JAMMU AND KASHMIR | 190009 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹70.5 L
EMD Value
₹3.5 L
Closing Date
25 Jan 2024, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, Jal shakti(PHE) MRD, Sgr
Executive Engineer, Jal shakti(PHE) MRD, Sgr
SITC of electro-mechanical works at WSS Chinar Colony Kawoosa
2024_PHE_242978_1
PHE/MRD/TS/142 of 01/2024
Open Tender
Miscellaneous Works
Item Rate
50 days
Srinagar
Please refer Tender documents.
2 documents required · 2 mandatory
₹100
Yes
Executive Engineer JSD PHE Mech Rural Division Sgr
₹3.5 L
Yes
27 Jan 2024
15 Jan 2024
25 Jan 2024
15 Jan 2024
25 Jan 2024
15 Jan 2024
Amount
Stage Ist (Raw Water) Part (A) - Mechanical
Supply, Installation, Testing & Commissioning of Non-Clog open well Submersible Pumping equipment as per IS 5600 at Raw water Stage. (Rest Technical Specifications as per Annexure )
Pipe line (as per IS: 1239) Providing/laying/Fitting of 150 mm Class (C) GI flanged rising main (Rest Technical Specifications as per Annexure )
Fabrication and fitting of delivery flanged piping arrangement with wash out manifold fabricated out of 150 mm pipe (10mtr) , P/F of G.I Y-Junction as per site requirement, P/F of G.I. 150mm dia. flanged bends (7 nos.) and Flanged Tee (1nos) made out of 150 mm dia. G.I. pipe class “c” as per specifications mentioned above. The job includes P/F of sluice valve 150 mm dia. VAG/ SIGMA/Talis or any other reputed make-01no The flange thickness shall be 22 mm and as per IS – 6392. Job includes P/F of M20 flange bolts / nuts chrome plated for connecting the pumping unit with the delivery Manifold.
Providing, Fitting, Testing and Commissioning of 150 mm Nominal Diameter, Ductile Iron, Gate Valve of rating PN 16. The valve shall be resilient seated, with internal stem thread, face-to-face length, flange dimensions according to DIN EN 1092-2. Material of Construction: Body parts of ductile cast iron, with flat bottom, wedge fully rubber lined with EPDM, with wedge draining, stem made of stainless steel min. 13 % Cr, maintenance-free spindle seal. Corrosion protection: Inside and outside epoxy coating, blue, RAL 5005 according to GSK. The job includes providing and fitting of 02 No. M.S Flanges perfectly adaptable to the inbuilt flanges of the valve, which shall be fitted with delivery mains of the pumping unit. Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work. Make:-VAG/SIGMA/Talis or any other reputed make.
Providing, Fitting, Testing and Commissioning of 150 mm Nominal Diameter, Ductile Iron, Non Return Valve of rating PN 16. The valve shall have body and bonnet of ductile iron, with drainage plug disk of ductile iron, fully covered with rubber (EPDM) approval identical seal on both sides, with integrated rubber joint protected against overload, body seat of cast iron, bolts and nuts of stainless steel (A2), Corrosion protection: Inside and outside epoxy coating, blue, RAL 5005 according to GSK. The job includes providing and fitting of 02 No. M.S Flanges perfectly adaptable to the inbuilt flanges of the valve, which shall be fitted with delivery mains of the pumping unit. Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work Make:-VAG/SIGMA/Talis or any other reputed make
Over Head Gantry Fabrication / Erection of Channel iron column to act as support for resting of monorail crane (Rest Technical Specifications as per Annexure )
Providing, installation and testing of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features Gears: - The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears. Load Chain: - The load chain is to be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation. Load chain wheel: - the load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specifications of C.P Block are given below : Make = Indeff/pull lift /Globe or any other Reputed make Capacity = 2 ton (P) No. Of load chain falls = 2 or above Min. Height of lift = 6 M Manufacturers’ test certificate to be appended.
Part B Electrical
Fabrication, Providing and fitting of Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories (Rest Technical Specifications as per Annexure )
Providing, fitting, testing and commissioning of 30 KVA voltage controllers for stage 1st (Rest Technical Specifications as per Annexure )
Providing, fitting, testing and commissioning of 50 mm 2 XLPE Armoured Al. Cable of 1.1 KV grade conforming to IS: 7089 part 1st with following characteristics: Conductor Nominal area : 5 0 mm2 Min. Number of wires : 3 ½ Nominal thickness Insulation : 1.00 mm Outer sheath : 1.24mm Make : L&T or any other equivalent make
Supply & Installation of 1000 Kva Microtek /Luminous or any other reputed make inverter along with 12 volt 180 AH Exide/Luminous or any other reputed make battery complete with leads terminals & thimbles. The job also includes all the charges on account of carriage, wiring and arrangement of skilled labour for installation of inverter.
Providing and Fitting of 3-core multi-stranded copper cable, PVC insulated, internal intermediate sheathed of 16mmSq.Submersible flat cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) – 1964 of Havells/Finolex/L&T/ KEI or any other reputed make for submersible pumping equipment & for inter connections of electrical gadgets from starter to pumping units (For both stage 1 and stage 2 pumping units). The job also includes termination of ends of cable with suitable rating of Cu. thimbles duly taped. Note:- The test certificates of the cable from the OEM shall be produced at the time of supply of material
Supply, Installation, Testing & Commissioning 16mm Sq. Single Core flexible copper power cable, suitable for LV 1.1KV/650V grade, XLPE Insulated, cores laid up, PVC inner sheathed, Un-armoured for connecting Control panels and Voltage Stabilizers together (For both stage 1 and stage 2 voltage stabilizers and panel). Confirming to IS7098- Part 1, 1988. Acceptable makes for the cable are Havells/Finolex/L&T/ KEI/POLYCAB or any other reputed make. The job is inclusive of Providing & fixing of copper thimbles (not less than 40 No’s) (make Dowels) for the cable as per site requirement duly crimped with the cable termination ends by crimping tool and 150mm Nylon Cable ties (150 No’s). The cable is used to connect various electric gadgets. Note:- The test certificates of the cable from the OEM shall be produced at the time of supply of material
Providing/Fitting of 150 mm width Steel perforated cable trays along with duct ,bends for accommodating interconnection cable
Stage 2nd Filter Water Part A- Mechanical
Supply, Installation, Testing & Commissioning of Open Well Submersible Pumping Equipments as per IS : 14220 suitable with following specifications:- (For OHT) (Rest Technical Specifications as per Annexure )
Pipe line (as per IS: 1239) Providing/laying/Fitting of 150 mm Class (C) GI flanged rising main Nominal Bore: 150.00 mm Outside Dia: 166.50 mm Wall thickness: 5.40 mm with tolerance permissible as per relevant IS Code Pipe Ends Plain Flanges (as per IS 6392/1971 Table:17) Nominal Size: 150.00 mm Flange Dia: 285.00 mm Flange Thickness: 22.00 mm Raised Face Thickness: 3.00 mm Raised Face Dia: 212.00 mm Bolting: M20 No of Holes: 8 Dia. of Hole: 20 mm The pipe shall be flanged after every 6 mtr segment.
Fabrication and fitting of delivery flanged piping arrangement with wash out manifold fabricated out of 150 mm pipe (10mtr) , P/F of G.I Y-Junction as per site requirement, P/F of G.I. 150mm dia. flanged bends (7 nos.) and Flanged Tee (1nos) made out of 150 mm dia. G.I. pipe class “B” as per specifications mentioned above. The job includes P/F of sluice valve 150 mm dia. VAG/AVK/SIGMA/Talis or any other reputed make-01no The flange thickness shall be 22 mm and as per IS – 6392. Job includes P/F of M20 flange bolts / nuts chrome plated for connecting the pumping unit with the delivery Manifold.
Contol Valves(Sluice Valves) Providing, Fitting of 150 mm, PN 1.6/16, Ductile Iron double flanged, soft seated glandless gate/ sluice valve. Body and bonnent of ductile cast iron, wedge with fully vulcanized EPDM rubber(Approved for drinking water) and NBR seal. Gate /Sluice valve shall be compatible for buried application and shall be safe to install in both horizontal and vertical positions It shall have electrostatic epoxy coating inside and outside approved for drinking water the valve shall be supplied along with hand wheel. The job includes providing and fitting of 02 No. M.S Flanges perfectly adaptable to the inbuilt flanges of the valve, which shall be fitted with delivery mains of the pumping unit. Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work. Make :VAG/ SIGMA FLOW/Talis or any other reputed make
Control Valves(Non-Return Valves) Providing, Fitting of 150 mm,PN 1.6/16, Ductile Iron double flanged, Slanted seat swing check valve(NRV). Body of ductile cast iron with fully encapsulated vulcanized EPDM rubber(Approved for drinking water) . NRV shall be compatible for buried application and shall be safe to install in both horizontal and vertical positions It shall have electrostatic epoxy coating inside and outside approved for drinking water. The job includes providing and fitting of 02 No. M.S Flanges perfectly adaptable to the inbuilt flanges of the valve, which shall be fitted with delivery mains of the pumping unit. Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work. Make :VAG/ SIGMA FLOW/Talis or any other reputed make.
Providing, fitting of MS clamps capable of holding 200 mm dia. GI-C-class Pipe. The clamp shall be fabricated out of 18 mm thick MS plate with adequate flange length and flanges bored with 5/8” holes and provided with suitable size nuts and bolts
Over Head Gantry for stage 2nd.(Near Clear water Sump) Fabrication / Erection of Channel iron column to act as support for resting of monorail crane as per following details:- Vertical Posts = ISMC 150 No. of vertical posts = 02 Nos. Vertical channel section each post = 02 Nos. vertical post bracing = ISMC 100 Sole / Matching plates = 500x300x12 thk Height of vertical posts = 4.5 M size of vertical post concrete blocks = 600x600x1200(Depth) Concrete grade = M20 welding Electrode = Overcord SS of Adore/ESAB/L&T Monorail Section = ISMB 200 length of monorail = 5M Steel Detail : i. ISMC 150 4.5Mx2x2 = 18 M @ 16.4kg/m = 295 kg ii ISMC 100 0.25Mx8x2x2 = 8 M @ 9.2kg/m = 73.60 kg iii Plate 0.500x0.300x8 (12mmthk) = 1.20 M²(12thk) = 112.80 kg iv Monorail ISMB 200 5 M @ 25.4 kg/M = 127 kgs v Bolts/Nuts (L.S) = 20 kgs Total = 647kg= 650 Kgs
Providing, installation and testing of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features Gears: - The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears. Load Chain: - The load chain is to be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation. Load chain wheel: - the load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specifications of C.P Block are given below : Make = Indeff/ Reputed make Capacity = 2 ton (P) No. Of load chain falls = 2 or above Min. Height of lift = 6 M Manufacturers’ test certificate to be appended.
The job includes complete painting of the Gantry structures, two in number by applying first two coats of metal primer & then two coats of synthetic enamel paint of desired shade so as to make the structure rust proof and to look aesthetically better.
Fabrication, Providing and fitting of Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories (Rest Technical Specifications as per Annexure )
Providing, fitting, testing and commissioning of 50 KVA voltage controllers for stage 1st. as per specifications below: Type of voltage controller: Manually operated copper wound, 3phase, AC power supply multi step. Type of Regulator : double plate type with electrolytic copper contacts. Input voltage : 156-415 volts. Output voltage : 400 + 10% volts. Frequency : 50+ 3 C/S. Windings : Electrolytic grade copper of adequate section, vacuum impregnated and oven dried. Insulation : Fiber glass insulations to tested parameters. Efficiency : 98 % Cooling : Naturally, Oil cooled Temp. Rise (Max) : 30°C above ambient Mounting : on uni-directional wheels. Correction rate : 30 volts per step Wave form distortion : virtually nil Duty cycle : 100% continuous. Enclosure : MS sheet enclosure in pressed CGR sheet powder coated with radiators. Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations. Load : Three phase induction motor load. Load Amperes (continuous) Load Amperes for 2-hour : 78Amperes on worst combination of voltage and frequency. Overload in 24-hours operation: 10% above continuous Ampere rating. Note: The voltage Controller shall be accepted with manufacturers duly stamped test certificate and shall have name plate with specifications, name of manufacturer and name of Water Supply Scheme
Providing, fitting, testing and commissioning of 70 mm 2 XLPE Armoured Al. Cable of 1.1 KV grade conforming to IS: 7089 part 1st with following characteristics: Conductor Nominal area : 70 mm2 Min. Number of wires : 3 ½ Nominal thickness Insulation : 1.00 mm Outer sheath : 1.24mm Make : L&T
Part (B) High mast luminaries/Electrification
Providing, Fitting & erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom diameter (A/F)- 150mm, Top diameter (A/F)- 90mm wide, thickness 4mm with 70 Microns Zinc coating with inside arrangement for providing of power connection with following items. • 1 No. Terminal connector 60 Ampere. • Required size Lugs duly Crimped. • Cement concreting of required size not less than 2’x2’x4’ in ratio of 1:2:4. • Required length of PVC copper flexible multi strand wire 1.5mm2/mtr. Filling to terminal conductor. • Mounting clamps for fixing of flood lights made with pole of MS & GI pipe of required size including cost of Nuts & Bolts. • Mounting arrangements for fixing of LED lights with pole. Earthing in GI Electrode.PVC pipe HDF of required size & length for inlet & out for cable in connection block
Providing installation testing and commissioning of area lighting 120 Watt LED (Street Light Type) Input: 90-240 V 50 Hz Power Factor: >0.9 Colour Temperature: 4K - 6.5K Beam Angle: 120˚ - 170˚ Lumens: >12000 Operating Temperature: -20˚C to 60˚C The LED shall have pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68. The LED shall be properly fitted on the arm of the pole and connected to the copper wire as provided in item no A Makes: any reputed make
Providing Laying and connection of 2Cx10 mm² XLPE Aluminum Armoured Cable from the connector of high mast pole to the stabilizer. The job includes underground laying of cable through 2” dia. HDPE heavy duty pipe, including, bends etc as per requirement and directions of the site in charge. Make: Havel’s/ Gloster/Polycab or any other reputed make.
1. Providing/Fitting of lighting and fan points in 1.5 mm multi strand single core cable (Havells) make carried through 1 dia.PVC pipe junction box, bends, clips and fitted with 6-Amp piano type SSK switch on Hylum plate (12 nos). 2. Providing/Fitting of Havells or any other reputed make ceiling/table fan complete in all respects (02Jobs) 3. Providing/Fitting of heating points in 2.5 mm multi strand single core cable (Havells) make fitted with 16-Amp socket switch cabin on Hylum plate.( 04 nos.) 4. Providing / Fitting of 16mm2 Aluminum armoured cable from main panel board to distribution board (20 mtr) 5. Providing /Fitting of 3-pin, 6 Amp plug points complete in all respects. (4 Nos.) 6. Providing /Fitting of Angle holder with 100 watt lamps complete in all respects.( 12 Jobs) 7. Providing /Fitting of 16 ways main distribution board of QVF Havells make with 6 Amp MCB-12 nos., 16 Amp-4 nos. for heating points, and 36 AMP MCB (mains) Havells or any other reputed make.( C. Job)
Providing of tool kit comprising of Flat Spanner 14-27 No (07 Pieces), Ring spanner set 14-27 No (07 pieces), 10” screw Driver,Hammer-1.5 Kg, H/D Plier,24” pipe ranch ,The tools shall be of Taparia /Ambika or any other reputed make Provided in canvas bag. The Job also Includes Providing of Chargeable lantern of Andslite make 02 nos, 06 no PVC chairs Prima /Cello make along with PVC Table, 15 ltrs. Bucket & mug, 8 Kg gas cylinder along with Burner/stove, 3 Ltrs. pressure cookers, 3 ltrs. Rice Cooker ,5 no steel plates & glasses,10 mm Thermo cool for operators quarter having size of 12’x14’,bedding/Exel matting for the operators quarter of 12x14 size ,02 no.blankets,02 no pillows, 02 no quilts/ Razie, 2 no mattress,
Providing and Fabrication of 6’-6” x 6’-0” size MS angle Iron Framed worker’s sleeping bed made out of ISA 50 mm x 50 mm x 6 mm. The job shall include four no of legs 1’-6’’ long made out of equal iron ISA 50 mm x 50 mm x 6 mm with braces of MS flats 50mm x 4 mm, 2 no(1’-0” Long) for each leg and for central support,3 no’s (6’-0”long each) to be welded precisely with Advani electrodes as per requirement.
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -
Composition: Rubber (synthetic mats for electrical purpose)
Thickness:-2.5mm.Size:-1Mwide.
Part C- Electrical Substation
Creation of pope mounted , outdoor type 100 KVA Electric Sub Station by way of S/I/T/C of 11/0.433 KVA , 3 Phase Distribution Transformer with Bimetallic Terminal connectors Energy level -2 Aluminum wound 100 KVA Specifications conforming to IS : 1180 (Part 1) 2014 with latest amendments(1 NOHT/LT Transformer as stand by) Type of cooling: ONAN. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved. The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica Jel crystals, conservator with oil level indicator, explosion vet and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment. The testing and commissioning shall be completed only after obtaining above certificate
Providing and fitting G.I Channel Flat of Various sizes including clamps
Supply, Installation, Testing and commissioning of Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT post double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings , operating handle and 2 length of 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs.
Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation.
Supply, Installation, Testing and commissioning of 11KV polymeric composite disc insulator12 KV, min falling load 45 KN, lighting impulse 75 KV positive& 80 kV negative, creepage distance 320mm
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type.
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative , creepage distance 320 mm.
Supply, installation, erection of 9 mtrs long ST- 410 (sp-33). The job further includes drilling of holes for installation of various accessories .wherever required.
Providing and fitting of ACSR as per IS 398 (part-2) 1996 0.05" ACSR (Galvanized steel reinforced.)
Earthing of ST poles by way of P/F of GI rod 20mm 3mtr long through GI strip.
P/F of Galvanized nuts bolts of various sizes as per site requirement.
Earth work in excavation by manual means in trenches for foundation , drains ,pipes , cables (not exceeding 1.5 m in width ) and for shafts , wells , cesspits and the like not exceeding 10 sqm on plan , including dressing of sides and reaming of bottom lift up to 1.5 m , including getting out excavated earth and disposal of surplus excavated earth as directed. all kinds of soil
Providing and laying of soling stone including manual compaction
Concrete cement bottoming 1:2:4 mix as per REC standards , 0.5 Cum /pole
Providing and fitting of D- clamps
Providing and Fitting of heavy duty11 KVA link set near tapping point.
Providing and fitting of Galvanized stay set with 50 X 8 mm Stay Clamp , Guy insulator (2no.), Anchor plate (200X200X6mm) , nuts and bolts , 2 N0- turn buckle , 1.8 m long , 16 mm diameter solid G.I stay rod & 7/3.15 mm dia. G.I stranded wire complete.
Painting of poles Red oxide
Painting of poles Aluminum paint
Providing and fitting of LT Distribution box for 100 KVA H.T transformer With MCCB For incomer and 100 Amp SFU for outgoing circuits .
Providing, Installation of earthing station comprising of company fabricated earthing electrodes as per IS: 3043. The job includes Auguring of bore of required dia. / depth for installation of electrode along with black fill compound mixed with soil and all other items required thereof for achieving the best result The job includes connecting of electric gadgets, DG set through GI stripe making of surface structure in brick / cement concrete material as per drawing annexure. Safe earthing electrode size 80 mm dia. length - 2000mm Blackfill - 30 Kg Model / make - JMV-392, Ashlok, Recons or any other reputed make
Providing and fitting of sign boards on sheet metal with proper frame work with blue back ground & written in white. As per requirements. a. 3 ft. x 1.5 ft – 01 No. Board shall be Written with 1.Name of Water Supply Scheme------Chinar Colony Narbal 2. Year of Commissioning--------. 3.Capacity--- b. 4 ft. x 3 ft. – 01 No.(Machinery data Board written with equipments & specifications such as, I, Pumping Unit (Submersible) 2,Discharge----- 3,Head----------- 4, Capacity of Voltage Stabilizer. 5,capacity of HT transformer----
Part D- Standby Power Arrangement (DG Set)
Providing, Installation, Fitting, Testing and Commissioning of 82.5 KVA Water Cooled D.G Set confirming to (CPCB-IV NORM ) (Rest Technical Specifications as per Annexure )
FAVOURITE ELECTRICALS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .