Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-AOC LOWER KAFFER KALIMPONG | KALIMPONG | ₹3.4 L | L1 | Accepted-AOC BELOW |
| 2 | L2₹3.5 LRejected-Finance | ₹3.5 L | L2 | Rejected-Finance ABOVE |
| 3 | L3₹3.5 LRejected-Finance PEDONG KALIMPONG 734311 | KALIMPONG | WEST BENGAL | 734311 | ₹3.5 L | L3 | Rejected-Finance ABOVE |
Tender Value
₹3.4 L
EMD Value
₹6,814
Closing Date
26 Feb 2026, 6:00 pmClosed
Executive Engineer, KEED, GTA.
Office of the Executive Engineer KEED (Power Department), P.H.E. Complex, 9th Mile, Kalimpong.
Electrical works for Construction of Model Ayush OPD (SITC of Electrical works and SITC of AC Machine and Power backup at SHD Samthar PHC, Kalimpong, GTA.
2026_GTA_1009210_1
10/NIeT/EE/KEED/KPG/GTA/25-26
Open Tender
Electrical Work/ Equipment
180 days
Kalimpong
As per NIeT
5 documents required · 5 mandatory
₹750
₹6,814
Yes
20 May 2026
18 Feb 2026
2 Mar 2026
18 Feb 2026
26 Feb 2026
18 Feb 2026
Distn.wiring in 22/0.3(1.5sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in19 mm bore,3mm thick polythen pipe complete with all accessories embedded in wall to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate flushed in wall incl.mending good damages to original finish. 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC
i) Average run 6 mtr
iii) Average run 9 mtr
Distn. wiring in 22/0.3(1.5sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in19mm bore,3mm thick polythen pipe complete with all accessories embedded in wall to 240V 6A 5 pin plug point incl. S&F 240V 6A 3 pin Modular type plug socket & Modular type switch(Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed inwall incl. mending good damages to original finish. 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC
i) On Board
ii) Average Run 1.5 Mtr
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required
i) 2x x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
ii) 2x36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC [Power & 15A Board]
iii) 2x56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC [A.C. Point]
iv) 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC [HTPN DB to SPN DB]
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 25mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
v) 4 x 84/0.3 (6 sqmm) + 2 x 56/0.3 (4 sqmm) ECC [2 KVA INVERTER SUB MAIN]
Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles.
19 mm dia 3 mm thick polythene pipe with 1x14 SWG GI earth continuity wire
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approved by EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [CPU Board & Othres]
Supply & Fixing 240 V, 3 nos. 16 A, 3 pin Modular type plug socket with 3 nos. 16A Modular type switch (Brand approved by EIC), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.[Separate 16A Plug Point & AC]
Supply & Fixing 240 V, 25A Modular type socket, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C-Curve) and 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [AC Board] [LABORATORY & BIO-CHEM LAB]
Supplying & Fixing two way CI Round box with cover concealed in ceiling/wall
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph ,N & E) fixed on bakelite/ Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works
6 Module
8 Module
2 Row 12 Module
6A Modular type Switch
10A Modular type 2 way Switch
Blank Plate for modular box
Indicator Modular type
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Legrand / Havells / Siemens/L&T).
(2+12 Way) Enclosure (DHDPSNODRW12)
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Legrand / Havells / Siemens/L&T) .
Single pole 6-32A MCB [NDB 1,2,3 EDB 1, EDB 2]
Double Pole 40A MCB Isolator [EDB 2 I/C]
Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991)
a) 4 bars, 415 V, 63 A
Supply & Fixing Socket type fan regulator (Step type) (Brand approved by EIC) on existing sheet metal switch board with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc.
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991)
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessaryconnection as required by 2x1.5 sqmm flexible copper wire.
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter:
Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long)
For Al : 30 cm Exhaust fan (12")
Supply & delivery of Sweep:- 48" (1200mm) AC ceiling fan, 50-70 Watts, Speed:->=350 RPM, Air delivery:->=220 CMM, make: (Orient PSPO NEWBREEZE or SUMMERCOOL / equivalent of EPC or USHA STRIKER PLUS or CROMPTON [Approved by EIC]
Supply & delivery of Sweep:-36" (900mm) AC ceiling fan, 50-70 Watts, Speed:->=380 RPM, Air delivery:->=145 CMM, make: (Orient PSPO NEWBREEZE or SUMMERCOOL / equivalent of EPC or USHA or CROMPTON or HAVELLS [Approved by EIC]
Supply & delivery of heavy duty Exhaust Fan of Sweep:-12" (300mm), 240 volt, 50 Hz, AC , 50-60 Watts, Speed >900 RPM, Air delivery >=1145 CMM suitable for . [Make - Orient(Model:Power Flow)/EPC/Havells/Crompton Greaves] [Approved by EIC]
Supply and delivery of Wall fan 400mm Sweep Plastic blade
Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting
Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
For 4 core upto 50 sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
3½ core 50 sqmm cable
Supplying and Delivery at site 1.1 KV. Grade LT power cable, XLPE insulated, cores laid up, PVC inner sheathed aluminium armoured conductor of the following specificaion:- (make: Polycab/Gloster/Havells) 50 sqmm 4 core (A2XWY/A2XFY) [METER PANEL TO AYUSH SUB-MAIN PANEL ]
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 x 19/8 stranded GI (Hot Dip) wire (4 Mts. long), 25 mm dia x 150 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (Hot Dip) wire by crimping sockets/ thimbles and S & F 40 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. Solid GI wire
No. 6 SWG
Supply & delivery of single 4ft LED tube light fitting incl. 4ft LED tube, 1200 mm, Efficacy>= 100 lm/W, THD<10%, complete with all accessories. (Mas LEDtube 1200mm) [Philips: TMC 501 P 1xT-LED 22W P3241] or equivalent of Havells, Crompton etc. [Approved by EIC]
Supply & Delivery at site 12 watt LED Inverter Bulb, Efficacy>=90 lm/W, Base Cap:-B22 [Make-Crompton] or equivalent of Havells, Philips etc. [Approved by EIC]
Supply & Delivery of Square Downlight 24 Watt (Make-Havells, Philips or approved by EIC)
Supplying & Fixing Out door type CFL luminaire (Havells makeLHRC4185099) with deep drawn aluminium housing anodised inside & clear acrylic cover and accessories incl. for 85 watts CFL lamp incl. S&F 32mm dia GI pipe bracket, clamp, nut & bolts etc.
Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener
Fixing only bulk head ceiling fitting on wall /ceiling by screws etc.
Fixing only lamp
Fixing only bulk head ceiling fitting on wall /ceiling by screws etc.
Supply and Delivery of 1 Ton Split type Room Air Conditioner having following specification. Cooling Capacity (Kcal/Hr):- 6000 Kcal/Hr (2 TR) ISEER Rating:- 3 Star/2018-2019 as per BEE/BIS IS Compliance:- IS 1391 Refrigerant:- R32/R410A Compressor:- Rotary/Scroll Evaporator & Condenser Coil : Copper Operating Outdoor Temperature = 50°C and above Power Supply:- 240V,50 Hz (Tolerance as per applicable standard) [Make: Mitsubishi Electric/Hitachi/O-General/Blue Star/Havells] [Location:- Kalimpong]
Installation, Testing & Commissioning of Indoor & Outdoor unit with necessary fixing on wall ( Indoor unit & outdoor unit ) as per direction of EIC by providing of 40x40x5 mm MS angle iron frame with necessary anchoring facilty on one side for necessary support on outer wall / making pedestal by angle & flat with necessaery welding each other etc. & Making hole for providing holding with outdoor unit by proper gauge Gl nut bolt & washer with necessary painting by synthetic enamel paint two coat of one after another over one coat of RO primer or Providing of ISI marked bracket provide on wall by necessary providing of 100 mm MS / Gi Fastner arrangwement not less than 6 ( six ) no for each unit with making hole on wall and making connection of refrigeration pipe, power cable, drain pipe etc as per direction of the EIC.
S&F of following items for complete installation and commissioning of above AC machines including supply and fixing of Refrigerant pipe with insulation (nitrile rubber) tube of minimum thickness 9 mm (Make:- Armaflex/Accoflex) (dia as required at site) including wrapping insulation and copper wire with GKB Gold wrapping tape & 3 core PVC insulated FRLSZH grade copper cable (Make:-Havells/Polycab/R.R.Kabel]
Supply & Fixing of PVC drain pipe 1" dia (make approved by EIC)
Supply and Delivery of 6X5=30 sqft Glow Sign Board of 3D Channel Letter (make approved by EIC) @ 1200 per sqft
Supplying and Installation of 2 kva Inverter with 150AH Tall Tubular Battery Combo (Make:- Microtek, Exide, Luminous)
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
Tendernotice_2.pdf
PDF • 0.42 MB
BOQ_2477866.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid