Executive Engineer (Mech) SKIMS Soura
Executive Engineer (Mech) SKIMS Soura
Supply Installation Testing and Commissioning of Hot and Cold with Inverter Technology based high wall mounted split type AC Units for Department of Microbilogy,Immunology,Molecular Medicine Lab. and Sample Reception Lab.of SKIMS Soura
2019_SKIMS_84481_1
NIT NO. 32 OF 2019-20 Dated. 22.10.2019
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
30 days
SKIMS Soura
Please refer Tender documents.
6 documents required · 6 mandatory
₹200
Yes
Director Finance SKIMS
₹9,200
Yes
Executive Engineer (Mech) SKIMS Soura
15 Jan 2020
24 Oct 2019
9 Nov 2019
24 Oct 2019
7 Nov 2019
24 Oct 2019
25 Oct 2019
Amount
Supply, installation, testing and commissioning of high wall mounted split air conditioning unit with inverter technology each complete with outdoor unit and indoor unit comprising of compressor, condenser coil, fan and evaporator coil, blower, filter etc. Including providing and fixing of copper refrigerant piping of suitable dia, insulated with nitrile rubber of recommended thickness, interconnecting of copper conductor power cables 03 core 4mm2 between the indoor and outdoor unit through minimum 5KVA voltage stabilizer with voltage digital display should be supplied input:130-300v, output;220v + 5%, 50Hz and metal enclosure plug and socket with MCB (DP) of 20A 3pin + SC related accessories for mounting of outdoor unit. The job also includes pressure testing, vacuum testing and charging of refrigerant for rated performance of air conditioning machine. Specification: a. Cooling capacity: 7.1 (2.3-8.5)KW Rated (Min-Max) b. Heating capacity: 8.2 (2.3-10)KW Rated (Min-Max) c. EER:>10.25 d. Power supply: Single Ø, 220 + 5%, 50Hz
Supply, installation, testing and commissioning of high wall mounted split air conditioning unit with inverter technology each complete with outdoor unit and indoor unit comprising of compressor, condenser coil, fan and evaporator coil, blower, filter etc. Including providing and fixing of copper refrigerant piping of suitable dia, insulated with nitrile rubber of recommended thickness, interconnecting of copper conductor power cables 03 core 2.5mm2 between the indoor and outdoor unit through minimum 4KVA voltage stabilizer with voltage digital display should be supplied input:130-300v, output;220v + 5%, 50Hz and metal enclosure plug and socket with MCB (DP) of 16A 3pin + SC Flexible condensate pipe of 3mt. length and related accessories for mounting of outdoor unit. The job also includes pressure testing, vacuum testing and charging of refrigerant for rated performance of air conditioning machine. Specification: a. Cooling capacity: 3.5 (1.2-3.8)KW Rated (Min-Max) b. Heating capacity: 4.0 (1.2-5.0)KW Rated (Min-Max) c. EER: >11.25 d. Power supply: Single Ø, 220v + 5%, 50Hz
M/S NEW EDGE CONSTRUCTIONS
MEHRAJ GROUP OF CONSTRUCTION ENGINEERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .