Loading…
Loading…
Tender ID
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.2 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹21.2 L+₹2.0 L (10.4%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bidder |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
30 May 2024, 6:00 pmClosed
CWE Dhar Road Udhampur
HQ CWE Dhar Road Udhampur C/o 56 APO
PROVN OF CERTAIN E/M WORKS AT BHALRA MIL STN UNDER AGE (I) BHALRA
2024_MES_651374_1
8275/CWE/DR- /2024-25/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE(I) Bhalra
Please refer tender documents
5 documents required · 5 mandatory
₹500
AGE (I) Bhalra
₹50,000
2 Sept 2024
27 Apr 2024
6 Jun 2024
27 Apr 2024
30 May 2024
11 May 2024
Amount
Material and labour for PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundation filling, basement and mass concrete for poles all as specified directed by Engineer-in-Charge.
Material and labour for Aluminium strip 25x3.15 mm with saddles and fixing screws etc for roof conductors and down conductors above ground all as specified and directed by Engineer-in-Charge.
Material and labour for Earthing complete with galvanized iron steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion.
Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 25 x 4 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and as directed.
Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Chemical earthing with copper earth plate 90x60cmx5mm & copper earth strip 32x6mm complete all as specifiied and directed by the Engineer-in-Charge.
Supply and fixing cast iron earth pit cover inplace of old damage PCC earth pit cover with suitable frame work complete all asspecified and directed by Engineer-in-Charge.
Supply and fixing GI earth plate of 600mm x 600mm x 6 mm inplace of old damaged earth plate complete all asspecified and directed by Engineer-in-Charge.
Supply and laying of charcoal for repair of existing earthing complete all as specified and directed by Engineer-in-Charge.
Supply and laying of common salt for repair of existing earthing complete all as specified and directed by Engineer-in-Charge.
Material and labour for Galvanised Iron earthing strip 32 x 6 mm from earth test point to electrical equipment including taking down old unserviceable earthing strip complete all as specified and directed by Engineer-in-Charge.
Maintenance and complete overhauling of 11 KV,3 phase, 630 Amps - 400 Amps, VCB including disassembling of operating mechanism parts, well cleaning with petrol & CRC-226 including reassembling, panel board, main bus bar, de-carbonizing all joints bus bar, CTs, PTs, spouts metal parts and making VCB perfect operating in manual and electric mode including all routine and preventive maintenance complete and replacing unserviceable parts and components complete, all as specified and directed by Engineer-in-Charge. Make of VCB :- ABB & BECCO Note :- Spare parts will be measured and paid seperately as supply only under respective items as given here-in-after. The labour charges deemed to be included in the unit rate quoted for this item.
Supply only holding catch assembly compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only push button Bracket assembly compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only charged / discharged indicator assembly compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only big and small gear assembly compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only closing spring assembly compatiable with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only triping spring assembly compatible with KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only trip shaft assembly with spring and trip strips compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only close shaft assembly with spring and close strips compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only TNC switch compatiblewith existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only trip catch assembly with all linkage compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only over current/Earth fault relay Numerical 3 Pole,OC/EF Protection Relay complete for 11 KV VCB, all as specified and directed by Engineer-in-Charge. Model :- ADR 131A Make :- ASHIDA, aux. 24-230 VAC/DC, CT:1A/5A
Supply only trip Coil 110 V, DC compatible with existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only control fuses rating 3A to 8Amp HRC type complete for 11 KV VCB, all as specified and directed by Engineer-in-Charge. Make : RBCO/GE/L&T
Supply only indication lamps comparising CB ON, CB OFF, Spring charge, trip cuircuit indicators etc.Capacity 3 V DC complete for 11 KV VCB, all as specified and directed by Engineer-in-Charge. Note : Colour code as per existing (R,Y,B,G,W). Make : Siemens/ Kaycee/L&T.
Supply only isolating contact assembly upto 800 Amp compatiblewith existing 11 KV VCB, all as specified and directed by Engineer-in-Charge.
Supply only CT unit 100/50/5A, 15 VA 50 Hz suitable for existing 11 KV VCB. Make : L&T, Schenider, CG, Kirloskar & ABB.
Supply only master trip relay for 11 KV VCB complete, all as specified and directed by Engineer-in-Charge.
Supply only auxilary relay compatible with existing 11 KV VCB complete, all as specified and directed by Engineer-in-Charge.
XLPE copper cable 2.5 sqmm 4 core complete, all as specified and directed by Engineer-in-Charge.
XLPE copper cable 2.5 sqmm 8 core complete, all as specified and directed by Engineer-in-Charge.
Supply only Ferrules 0 to 9 suitable for 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Supply only Ferrules A to Z suitable for 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Supply only ammeter suitable for existing 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Supply only volt meter suitable for existing 11 KV VCB complete all as specified and directed by Engineer-in-Charge.
Supply only Spring charging motor compatible with existing 11 KV VCB/outdoor breaker switch all as specified and directed by Engineer-in-Charge. Make : GEC / Crompton
Material and Labour for disconnecting electrical connection, removing of defective 33 KV Vaccum Circuit Breaker conforming to IS-13118/ IEC:56 of 36 KV, 1250 Amps, 3 Phase, 50 Hzs having breaking capacity of 25 KA, Shunt trip 110 volts DC alongwith repair of its mechanism at site with cleaning of all contacts, bushes, terminals, spring charging mechanism, greasing of all moving parts, checking of function & physical servicibility of CT, PT, Protection relays, tripping system with coils, spring charging, breaker operating mechanism and reasserbling of breaker complete as specified and directed by Engineer-in-Charge. Note :- Spare parts will be measured and paid seperately as supply only under respective items as given here-in-after. The labour charges deemed to be included in the unit rate quoted for this item.
Supply only Over Current and Earth Fault relays operating voltage of 36 volts for 33 KV VCB complete all as directed by Engineer-in-Charge.
Supply only master Tripping Relay operation voltage of 36 volts complete for 33 KV VCB all as directed by Engineer-in-Charge.
Supply only Spring charging motor compatible with existing 33 KV VCB/outdoor breaker switch all asspecified and directed by Engineer-in-Charge. Make : GEC / Crompton
Supply only Tripping and Closing coils complete for 33 KV all as directed by Engineer-in-Charge.
Supply only TNC Switch complete for 33 KV all as directed by Engineer-in-Charge.
Supply only ammeter suitable for existing 33 KV VCB complete all as specified and directed by Engineer-in-Charge.
Supply only volt meter suitable for existing 33 KV VCB complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of batteries(cell) of 2 volts of capacity 100 AH suitable for battery bank including initial Dry battery complete as per specification including necessary cell connectors, nuts, bolts and washers etc and copper control cable for DC supply complete, all as specified & directed by Engineer-in-Charge. Make : Exide / Amron.
Material and labour for disconnecting electrical connection, removing of defective 3.15 MVA transformer at site including disconnecting and rewinding of 33/11 KV, Three Phase, 4 wire, 50 Hz vector group DYn 11 transformer with paper insulated copper winding wire as per original data on HV (Delta connection) and LV (Star connection) & tapping brought on HV side for tap charger to change (±) 2.5%, 5%, 7.5% by means of manually operated off load tap changing gear complete rewinding of HV on three limbs providing insulation material like spares, wooden blocks, cotton tape etc and re-conditioning three limbs complete ovening, replacement of cock sheet packing, vent diafragm replacement of LT terminal plate, breather, filling of new transformer oil for top up with existing oil after proper filtration upto level of 45 KV at 2.5mm gap dielectric strength and testing of transformer at site after connecting electrical connection in full load , complete all as specified & directed by Engineer-in-Charge. Note : (a) The repair to the Transformer shall be done at site and the contractor shall make all the necessary arrangements required at site. (b) Spare parts will be measured and paid seperately as supply only under respective items as given here-in-after. The labour charges deemed to be included in the unit rate quoted for this item. Note : Supply only following Items / Spares required for 3.15 MVA transformer :-
Supply only gasket suitable for 3.15 MVA transformer complete all as directed by Engineer-in-Charge.
Supply only Digital Voltmeter for 33 KV complete all as directed by Engineer-in-Charge.
Supply only Digital Amp Meter for 33 KV complete all as directed by Engineer-in-Charge.
Supply only 33 KV Buchholz Relay model GOR-3 complete all as directed by Engineer-in-Charge.
HT coil/ LT coil of suitable gauge of paper insulated copper winding wire of transformer.
LT Bush with rod of brass complete cork washer with nuts, bolts and washers of brass of requisite size suitale for 3.15 MVA transformer.
HT Bush with rod of brass complete cork washer with nuts, bolts and washers of brass of requisite size suitale for 3.15 MVA transformer.
LT terminal plate for outgoing connections for 3.15 MVA transformer.
Breather for transformer of capacity 3.15 MVA.
Supply, filling and top up with new Transformer Oil of dielectric strength more than 50 KV at 2.5mm gap confirming to IS : 335-1993 complete all as specified and as directed by Engineer-in-Charge. Make : APAR Oils / Savita
Dehydration of transformer oil by using filtration plant of suitable capacity and removing the moisture / dust till obtaining the oil dielectric strength 45 KV at 2.5mm gap and above for various transformer / voltage stabilizer of any size located at different substations, complete all as specified & directed by Engineer-in-Charge.
Draining out the old engine oil from DG set, cleaning of deposits and rectifing leakages, if any, by means of welding, brazing and cleaning of oil tank and Supply and filling of new Engine oil complete all as specified and directed by Engineer-in-Charge.
Material and labour for taking down radiator from DG Set of any type /make of capcity 20 to 50KVA from base mounting , cleaning /descaling by using of air compressor and cleaning with suitable stain removal detergent along with chemical etc and rectifing water leakage by means of welding / brazing, after cleaning , descaling and rectifing of leakage etc. including renewal of all connecting parts i.e radiator hose pipe with clamps , bolts, nuts washers , rubber bush packing materal etc and re-assembling the radiatorand fixing with DG set properly in original position, checking the alignment, making proper hose connecting, testing for smooth operation complete all as directed by Engineer-in-Charge. Note :- 1. The cost of renewed parts is deemed to be included in unit rate quoted by contractor. No extra cost shall be paid to the contractor for the same.
All as per Item No. 19 here-in-before but DG Set of capacity 100 KVA to 320 KVA.
Material and labour for taking out of injector of DG Set of any type/make of capacity 20 KVA to 45 KVA disconnection and opening of fuel injector assembly, carrying complete overhauling / servicing fuel injector system, including renewal of injector kit, calibration of injector, checking of pressure complete for each injector and re-assembling the same in original positon by making proper fuel connnection and testing for smooth operation complete all as directed by Engineer-in-Charge. Note : Renewal of parts to be measured & paid under respective items as given here-in-after separately.
Supply only Needle valve.
Supply only Nozzle holder.
All as per Item No. 21 here-in-before but DG Set of capacity 100 KVA.
Supply only Needle valve.
Supply only Nozzle holder.
All as per Item No. 21 here-in-before but DG Set of capacity 320 KVA.
Supply only Needle valve.
Supply only Nozzle holder.
Supply and fixing high pressure fuelline sutable for DG Set of capacity 20 KVA to 50 KVA.
Supply and fixing high pressure fuelline sutable for DG Set of capacity 100 KVA.
Supply and fixing high pressure fuelline sutable for DG Set of capacity 320 KVA.
Opening /taking out of fuel injection pump (FIP) of DG Set of any type/make of capacity 20 KVA to 45 KVA, disconnecting of fuel injector line, carrying complete overhauling / servicing of injecor pump, calibration of fuel pump as per manufacturer instruction , assembling of the same with DG Set properly in original position, checking the allignment, making proper fuel connection including renewal of unserviceable/defective minor parts like seal, 'O' ring, gaskit fuel pump, gear, technometer, bushing, technometer cover, fuel pump, gear housing, fuel pump gear etc and testing for smooth operation complete all as directed by Engineer-in-Charge, after renewal of following major parts if found defected/unserviceable. Note : Supply only major items should be measured & paid under respective items given here-in-after seperately.
Supply only Plunger.
Supply only Control rack.
All as per Item No. 27 here-in-before but DG Set of capacity 100 KVA.
Supply only Plunger.
Supply only Plunger Barel sleeve.
All as per Item No. 27 here-in-before but of DG Set of capacity 320 KVA.
Supply only Plunger.
Supply only Control rack.
Supply and fixing, testing and commissioning in replacement of self starter 12V DC suitable for 30 to 100 KVA DG set complete all as specified and directed by Engineer-in-Charge.
Supply and fixing, testing and commissioning in replacement of self starter 24 V DC suitable for 320 KVA to 500 KVA DG set complete all as specified and directed by Engineer-in-Charge.
Supply & laying of Synthetic rubber insulated mats 2.5mm thick for voltage upto 1100 V for electrical purpose as per IS 15652-2006 suitable for electrical shock safety of size 2m x 1m, complete all as directed by Engineer-in-Charge. Make : Jyoti/Jaipuria.
Taking down old unserviceable fuel feed pump and supply and fixing new fuel feed pump for fuel injection pump complete assy for various capacity of DG Sets.
Supply and fixing (in repairs) of fuel shut down soleneoied valve kit including taking out old valve assy and making all connection testing for smooth operation in any type DG Set complete all as specified and directed by Engineer-in-Charge.
Material and labour for 'B' check kit of DG Set of capacity 20 KVA to 45 KVA.
Material and labour for 'B' check kit of DG Set of capacity 100 KVA.
Material and labour for 'B' check kit of DG Set of capacity 320 KVA.
Supply and fixing (in repairs) element air cleaner for DG Set of capacity 20 KVA to 50 KVA.
Supply and fixing (in repairs) element air cleaner for DG Set of capacity 100 KVA.
Supply and fixing (in repairs) element air cleaner for DG set of capacity 320 KVA.
Supply and fixing (in repairs) Radiator cap suitable for DG set of any type /make and capacity complete all as directed by Engineer-in-Charge.
Supply and fixing (in repairs), V belt of size A-48 suitable for DG Set 20 KVA to 50 KVA capacity complete all as specified and directed by Engineer-in-Charge.
All as per Item No. 42 but of size AX60/A49 suitable for 100 KVA capacity complete all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs), V belt of size AX39 suitable for DG Set 320 KVA capacity complete all as specified and directed by Engineer-in-Charge.
Material and labour for top up of concentrated form coolent in radiator of DG Set of any type/Make and capacity, complete all as specified and directed by Engineer-in-Charge. Make : Bosch, feelit guard & equalient. Note : Measurement shall be done only in concentrate form of coolant.
Supply and fixing (in repairs) Fuel hose flexible with matalic tape from fuel tank to filter, filter to FIP including allied nut bolt washer and coupling for DG set 20 KVA to 50 KVA with and including taking out old hose and making all connection testing for smooth operation all as directed by Engineer-in-Charge.
All as per Item No. 46 here-in-before but for DG Set of capacity 100 KVA.
All as per Item No. 46 here-in-before but for DG Set of capacity 320 KVA.
Supply and fixing (in repairs) of radiator hose pipe suitable both inlet and outlet of 20 KVA to 50 KVA DG Set with including taking out old hose and making all connection, testing for smooth operation complete all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) of radiator hose pipe suitable both inlet and outlet of 100 KVA DG Set with including taking out old hose and making all connection, testing for smooth operation complete all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) of radiator hose pipe suitable both inlet and outlet of 320 KVA DG Set with including taking out old hose and making all connection, testing for smooth operation complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of 12V 180 AH Battery tubular of specified and directed by Engineer-in-Charge. Make : Exide/Amron/Tata or equalent make.
Supply and fixing (in repair) of 12V 150 AH Battery tubular of specified make.
Supply and fixing in repair of battery terminals made of brass , suitable for battery of any type /make and capacity, complete all as directed.
Supply and fixing in repairs of PVC insulated multi stranded copper conductor single core unsheathed cable of size 70 sqmm, 1100 volts grade for battery lead Red and Black colour and all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) thermostat with new thermostat alongwith complete assembly for DG set connection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) RPM CABLE of any type/make of DG set complete all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) Water Temp Meter of any type and all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) OIL PRESSURE GUAGE of any type and all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) OIL TEMP METER of any type and all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) High Cylinder Temperature (HCT) Switch of any type and size of DG Set and all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) Low lube oil pressure (LLOP) Switch of any type and size of DG Set and all as specified and directed by Engineer-in-Charge.
Material and labour for taking down of existing fuel from fuel tank by any means, removing of sludge and sediments deposited inside the fuel tank by repeatedly washing by using of chemical & detergent with air compressor including rectifing of leakage if found and refixing the same in position as per direction of engineer in charge by testing all as specified and directed by Engineer-in-Charge. cap 320 KVA DG Sets.
Material and labour for taking down of existing fuel from fuel tank by any means, removing of sludge and sediments deposited inside the fuel tank by repeatedly washing by using of chemical & detergent with air compressor including rectifing of leakage if found and refixing the same in position as per direction of engineer in charge by testing all as specified and directed. cap 100 KVA DG Sets.
Material and labour for taking down of existing fuel from fuel tank by any means, removing of sludge and sediments deposited inside the fuel tank by repeatedly washing by using of chemical & detergent with air compressor including rectifing of leakage if found and refixing the same in position as per direction of Engineer-in-Charge by testing all as specified and directed. cap 20 to 40 KVA DG Sets.
Opening and taking out of cylinder head 320 KVA capcity DG Set Renewal of inlet and exhaust valve, valve guide seats and lapping of valve machining job, pressure testing including renewal of unserviceable parts, reassembling complete testing as required.
All as per Item No. 66 here-in-before but 100 KVA capacity DG Set.
All as per Item No. 66 here-in-before but 20 KVA to 50 KVA capacity DG Set.
Renewal of anti viberation mounting pad B series of any type or cpacity complete all as directed by Engineer-in-Charge.
Supply and filling distilled water in sealed packing for DG 12 volts battery.
Supply and fixing in replacement of battery charging sets 12V DC automatic type, fixed in DG set / panel with transformer and rectifier etc including rewiring of faulty control complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of battery charging sets 24V DC automatic type, fixed in DG set / panel with transformer and rectifier etc including rewiring of faulty control complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs of Automatic voltage Regulator (AVR) suitable for DG Set of 20 KVA to 45 KVA capacity with and including taking out old AVR and making all connection testing for smooth operation complete all as specified and directed by Engineer-in-Charge. Model No. Tavr-20(k).
Supply and fixing in repairs of Automatic voltage Regulator (AVR) suitable for DG Set of 100 KVA capacity with and including taking out old AVR and making all connection testing for smooth operation complete all as specified and directed by Engineer-in-Charge. Model No. Tavr-20(k).
All as per Item No. 74 here in before but for DG Set of capacity 320 KVA, Model No. AVRIVER-2.
Supply and fixing (in repairs) rotating diods assembly suitable for DG set of capacity 40 KVA to 320 KVA with and including taking out old diods and making all connection testing for smooth operation complete all as specified and directed by Engineer-in-Charge.
Material and labour for opening / taking out of turbo charger of DG Set of 30 KVA to 100 KVA capacity, disconnection of air supply connection pipe etc complete overhauling servicing of turbo charger renewal of turbo charger repair kit including calibration /testing of turbo charger system complete and re assembling the same fitted with DG set properly in original position checking the alignment making proper all connection testing for smooth operation complete all as directed by Engineer-in-Charge.
Material and labour for opening /taking out of turbo charger of DG Set of 320 KVA capacity, disconnection of air supply connection pipe etc complete overhauling servicing of turbo charger renewal of turbo charger repair kit including calibration / testing of turbo charger system complete and re assembling the same fitted with DG set properly in original position checking the alignment making proper all connection testing for smooth operation complete all as directed by Engineer-in-Charge.
Renewal of Exhaust Muffler of DG Set any type any cap and all as specified and directed by Engineer-in-Charge.
Renewal of Expension bellow for exhaust of DG Set any type any cap and all as specified and directed by Engineer-in-Charge.
Material and labour for carrying out complete overhauling /servicing of DG Set panel, AMF Panel, control panel including checking and rewiring faulty electrical circuit using 1.5 sqmm FRLS copper conductor making all concections to CTs, push button, digital volt meter, digital amp meter and renewal of LED indicator and testing for smooth operation of any cap and all as directed by Engineer-in-Charge.
Taking down of old unserviceable exhaust fan fitted in DG set conopy and all as specified and supply and fixing in replacement of suitable size of existing size and capcity all as specified and directed by Engineer-in-Charge.
Dismantling AC alternator assembly of any capacities including taking out of worn out windings of Rotor and stator incl rewinding the coils with suitable guage of super enamelled winding wire of copper, renewal of insulation materials, heat varnishing, connecting leads and terminal plates all as required to make serviceable of the DG and including reassembling the same after necessary testing all as directed. The item rate includes shifting of altternatos from location to workshop and back to the installation complete all as directed by Engineer-in-Charge. Note : Supply only winding coils of super enameled copper shall be measured & paid for separately under relevant item given here-in-after.
Supply only copper winding for Item No. 83 above as per existing guage.
Supply and fixing (in repairs) Radiator water pump assy 100 to 320 KVA capacity complete all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) fuel cap suitable lock & key type of 30 to 320 KVA DG sets all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs fuel shut down brass solionid valve all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs electronic controller circuit board for engine governorr suitable for 100 to 320 KVA DG Set all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) MCCB, 3 pole, 125 Amps, Icu=25KA, 415 volts, 50 Hz, AC, with adjustable thermal and magnetic release duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repairs) MCCB, 3 pole, 100 Amps, Icu=25KA, 415 volts, 50 Hz, AC, with fixed thermal magnetic release duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed by Engineer-in-Charge.
Supplying, fixing and testing (in repairs) 63 Amps, 415V, 4 pole on-load changeover switch with sheet metal enclosure, side handle operated, 50 Hz, fixed to walls / panels with suitable size clamps, nuts, bolts and washers complete all as specified and directed including making connections and testing complete all as specified and directed by Engineer-in-Charge.
Supplying, fixing and testing (in repairs) 100 Amps, 415V, 4 pole off load changeover switch with sheet metal enclosure, side handle operated, 50 Hz, fixed to walls/ panels with suitable size clamps, nuts, bolts and washers complete all as specified and directed including making connections and testing complete all as specified and directed by Engineer-in-Charge.
Supplying, fixing and testing (in repairs) 200 Amps, 415V, 4 pole on- load changeover switch with sheet metal enclosure, side handle operated, 50 Hz, fixed to walls / panels with suitable size clamps, nuts, bolts and washers complete all as specified and directed including making connections and testing complete all as specified and directed by Engineer-in-Charge.
Supply and fixing (in repair) DC alternator after removal of for 12V DC from the DG Set of capacity 30 KVA to 100 KVA and renewal of minor parts like bush, o ring assembly, bush set, sealing kit,including assembling and re fixing at site complete all as specified and directed by Engineer-in-Charge after renewal of following major parts if found defected/unserviceable. Note : Supply only following parts shall lbe measured & paid for seperately under respective items given here-in-after.
Stator
Rotor
Exicitor
Rectifier plate with diod assembly
Slip ring voltage regulator
Supply and fixing (in repair) DC alternator after removal of for 12V DC from the DG Set of capacity 320 KVA and renewal of minor parts like bush, o ring assembly , bush set, sealing kit,including assembling and re fixing at site complete all as specified and directed by Engineer-in-Charge after renewal of following major parts if found defected / unserviceable. Note : Following items measured & Paid seperately.
Stator
Rotor
Exicitor
Rectifier plate with diod assembly
Slip ring voltage regulator
Supply and fixing of EMS 555/KG 934/ GC 1211 orother make/model suitable for any DG set of capacity 30 KVA to 300 KVA all as specified and directed by Engineer-in-Charge. Note : (i) The cost of transportation (to and from) for all kind of necessary eqpt /T&P shall be arranged /brought by contractor to complete the job at site or at E/M yard and no extra cost shall be paid to the contractor to this effect. (ii) If any complaint which inform to the contaractor by AGE or JE through telephone or verbal direction and the same will not attend by the contractor with in one day a penality of Rs 1000/- per day will be impossed.
darshan kumar gandhi
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .