Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹12.4 LAdmitted-Finance | -7.01% | ₹12.4 L | L1 | Admitted-Finance |
| 2 | L2₹12.9 LAdmitted-Finance | -3.25% | ₹12.9 L | L2 | Admitted-Finance |
| 3 | L3₹13.0 LAdmitted-Finance | -2.51% | ₹13.0 L | L3 | Admitted-Finance |
| 4 | L4₹13.6 LAdmitted-Finance | +2.00% | ₹13.6 L | L4 | Admitted-Finance |
| 5 | Rejected-Technical A 86 MANISH MARG NEMI NAGAR VAISHALI NAGAR JAIPUR JAIPUR JAIPUR RAJASTHAN 302021 | JAIPUR | RAJASTHAN | 302021 | - | - | - | Rejected-Technical Shortfall document not submitted |
Tender Value
₹15.8 L
EMD Value
₹31,580
Closing Date
11 May 2026, 11:00 amClosed
SE CIVIL JAIPUR
Chambal Power House hawa sadak sodala jaipur
SITC of air conditioner units at 220 KV GSS Goner.
2026_RRVPN_555976_1
RVPN/SE/CIVIL/RURAL/JPR/NIT02
Open Tender
Civil Works
120 days
Goner Jaipur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
Accounts Officer T and C RRVPNL Jaipur Rural
₹31,580
Yes
29 May 2026
4 May 2026
12 May 2026
4 May 2026
11 May 2026
4 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1 | Supply , Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 2.0 TR ISEER not less then 4.6. (E- 22.24.8) | 20 | Each | 54,917 | ₹10,98,340 | BI01010001010000000000000515BI0100001113 |
| 2 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 20 mm (E-22.40.1) | 90 | meter | 131 | ₹11,790 | BI01010001010000000000000515BI0100001118 |
| 3 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 5 kVA (E-22.41.3) | 20 | Each | 3,570 | ₹71,400 | BI01010001010000000000000515BI0100001122 |
| 4 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.2.5 Sq.mm 3 core flat / Round(E-4.7.2) | 90 | meter | 133 | ₹11,970 | BI01010001010000000000000515BI0100001123 |
| 5 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia 100 mm dia per running inch length (E-22.42.2) | 20 | per inch | 133 | ₹2,660 | BI01010001010000000000000515BI0100001124 |
| 6 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . (E-22.45) | 20 | Each | 542 | ₹10,840 | BI01010001010000000000000515BI0100001125 |
| 7 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR Single pole MCB (With B/C curve tripping Characteristics) 6 A to 32 A rating (E-6.1.1.2) | 40 | Each | 169 | ₹6,760 | BI01010001010000000000000515BI0100001126 |
| 8 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 3 pole MCCB With Thermal Magnetic release up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting (E-9.3.1.1) | 1 | Each | 1,506 | ₹1,506 | BI01010001010000000000000515BI0100001127 |
| 9 | P&F metal clad / Plastic industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted (without MCB) including making connections, testing etc.as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 20 amp, 2 pin + scrapping Earth, 1 Module (E-6.13.1) | 20 | Each | 1,458 | ₹29,160 | BI01010001010000000000000515BI0100001128 |
| 10 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (E-4.1.14) | 110 | r. Mtr | 142 | ₹15,620 | BI01010001010000000000000515BI0100001129 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.22 MB
Tendernotice_2.pdf
PDF • 10.31 MB
Tendernotice_3.pdf
PDF • 1.14 MB
Tendernotice_4.pdf
PDF • 4.45 MB
BOQ_990190.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid