Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.7 CrAccepted-AOC | ₹37.7 Cr | L1 | Accepted-AOC L1 bidder and awarded value is inclusive of GST |
| 2 | L2₹38.6 CrRejected-Finance | ₹38.6 Cr | L2 | Rejected-Finance L2 Bidder and quoted amount is inclusive of GST |
| 3 | L3₹38.7 CrRejected-Finance | ₹38.7 Cr | L3 | Rejected-Finance L3 Bidder and quoted amount is inclusive of GST |
| 4 | L4₹42.4 CrRejected-Finance 7TH FLOOR KALPATARU SYNERGY OPP GRAND HYATT SANTACRUZ EAST MUMBAI 400055 MAHARASHTRA INDIA | MUMBAI | MUMBAI | MAHARASHTRA | 400055 | ₹42.4 Cr | L4 | Rejected-Finance L4 Bidder and quoted amount is inclusive of GST |
Tender Value
Refer Docs
EMD Value
₹61 L
Closing Date
19 Jan 2023, 12:00 pmClosed
Chief General Manager PP and D
Conference Hall The MD AEGCL 1st Floor Bijulee Bhawan Paltan Bazar Guwahati01
TURNKEY CONSTRUCTION OF 2X50 MVA, 132/33KV GIS (GAS INSULATED SUBSTATION) AT EXISTING 220/132KV AMINGAON GIS (Retender)
2022_AEGCL_28111_1
AEGCL_132kV_AMINGAON_GISRETEN
Open Tender
Electrical Works
730 days
Amingaon Pacharia
Please refer Tender Documents
8 documents required · 8 mandatory
₹1,000
₹61 L
Yes
16 Aug 2023
8 Dec 2022
20 Jan 2023
9 Dec 2022
19 Jan 2023
20 Dec 2022
9 Dec 2022 - 29 Dec 2022
Amount
Supply of 132kV GIS Equipments( Supply A)
145kV, 3150A, 40kA for 4 second, SF6 gas-insulated metal enclosed Transformer bay module each set comprising of One (1) number 3-phase, 3150A, SF6 insulated circuit breaker complete with operating mechanism; Three (3) numbers 1-phase, 5-core, multi ratio,600-300/1-1-1-1-1A current transformers; Three (3) numbers 3-phase, 3150A, group operated isolators/disconnectors, complete with manual and motor driven operating mechanisms; One (1) number 3-phase, group operated safety grounding switches, complete with manual and motor driven operating mechanisms; Gas monitoring devices, barriers, pressure switches, UHF PD Sensors, support structure etc. as required; Local Bay control cubicle.(Stand Alone or Integrated)
Three phase, 3150A, 40kA for 4 second, SF6 gas-insulated metal enclosed bus bar of 145kV, each set comprising of Bus bars enclosures running from the existing Bus bar Module to interconnect each of the Transformer circuit breaker bay modules in Double Bus bar configuration; Gas monitoring devices, barriers, pressure switches, UHF PD Sensors, support structure etc. as required
145kV, 3150A, 40 kA for 4 sec, 3- phase SF6 to air bushings along with termination module & support structure for outdoor connections to connect GIS with 145kV side of Power transformer.
145kV, 3150A, 40kA for 4 second, 3-Ph encapsulated, SF6 Gas Insulated Bus Duct (GIB) outside GIS hall including Bus Duct support structure and associated accessories along with jointing elements
Erection Hardware for 145kV GIS Termination arrangement for Transformer bay Modules
Supply of outdoor bay equipments (Supply B)
Transformer
50 MVA, 132/33 kV, 3-Ph, YNyn0, Z =12.5 %, ONAN/ONAF with copper wound Power Transformer with OLTC(+5% to -15% in steps of 1.25%) , RTCC panel including all cabling, insulating oil for the transformer plus 10% spare oil, supplied with Bushing mounted NCT on HV & LV side & complete with all fittings and accessories to meet the technical specification including cost of all routine test including loading and unloading at site.The Transformer shall be suitable for 4" Aluminium Tubular Conductor termination on HV and LV side.
Online DGA
Online Insulating oil drying system
Lightning Arrester
120 kV, 10 kA, Metal Oxide type, heavy duty, station class 3, Lightning Arrestor complete with Pipe Structures, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
30 kV,10 kA, Metal Oxide type, heavy duty, station class Lightning Arrestor complete with Pipe Structures, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
Supply of 33kV XLPE Cable and Termination Kit
1000 sqmm, 33kV, 1-Core, XLPE Armoured Cu cable alongwith related accessories
33kV Cable Termination Kit (both indoor and outdoor) along with its accessories.
33kV Support Structure for Outdoor Cable Termination Kit
LT Power Cable (1.1kV grade)
(ii) 4C, 16 mm2
(iii) 3½ C, 35 mm2
(iv) 3½ C, 70 mm2
(vi) Cable Supports and fittings
LT Control Cable
(ii) 7C, 1.5 mm2
(iii) 12C, 1.5 mm2
(iv) 19C, 1.5 mm2
Earthing
Main Earthing Conductor 40mm dia MS Rod
Earthing Conductor: 40mm dia MS Rod For Riser From The Burial Earth Mat To Equipment,Structure Etc)
Earthing Conductor: 75X12mm GI Flat For Equipment and Structure Earthing
Earthing Conductor: 50X6 mm GI(HDG) Flat For Riser For Console Box,Lt Panels,Dc Panels,Marshalling Boxes, Cable Trenches Etc)
Earthing Device & Associated Accessories (50 mm Heavy Duty GI Perforated Pipe 3 Mtrs Long For Treated Earth Pit)
Earthing Device & Associated Accessories 40Mm Ms Rod 3 Mtrs Long For Non Treated Earth Pit)
Separate Earthing For 145 Kv GIS Modules
Separate Earthing For 145 Kv GIS Building
Separate Earthing For 36 Kv Indoor AIS Equipment
Separate Earthing For 36 Kv Indoor AIS Building
Other Earthing Accessories
Fire Protection System for Transformer
NIFPS
N2 Fire Prevention and extinguishing System for transformer with complete accessories and related Civil and Electrical works.
HVW spray system, Hydrant System and complete U/G and O/G Piping and accessories etc and associated Civil Works for fire protection system for 2 nos 50 MVA 132/33kV Transformer
HVWS System for 50 MVA ICT
Portable/Wheel/ Trolley mounted Fire Extinguishers
22.5 Kg capacity FE CO2 type, Trolley Mounted
25 Kg Capacity FE DCP type, Trolley Mounted
DCP 10 Kg Capacity, Wall mounted
FE CO2 6.5 Kg capacity, Wall mounted
DCP 5 Kg Capacity, Wall mounted
Foam Type 9 liter Capacity, Wall mounted
Water CO2 9 liter, Wall mounted
Fire Buckets (12 Nos. with stand in one set)
Supply of indoor floor mounted, SIMPLEX type control and relay panels, with mimic & annunciation panel for 132kV system as per specification comprising of the C & R panels and shall be complete with Numerical Relays and SAMAST Compliant ABT meters as per the Technical specifications & shall be compatible for SCADA/SAS.
132kV Panels
Transformer Protection Panel
Substation Automation System
Complete Sub Station Automation System for 132/33kV GSS Transformer Bays including Hardware and Software for the substation and remote control stations alongwith associated equipments for the transformer bay
Integration with the existing SAS system
Conductor / IPS Al Tube
4" IPS Al Tube
Lightning protection
Lightning Mast (LM)- 40m
Illumination system for Outdoor Lighting (Switchyard and Street lighting)
Lighting Panel
Lighting Panel Type ACP-2
Sub lighting panel type SLP
lighting Fixtures and Receptacles including junction box, lighting wires and flexible conduit (if required) from junction box to lighting fixture, mounting arrangement and other accessories/ materials etc as required for complete installation and commissioning of lighting fixture
Lighting Fixture Type SF1
Lighting Fixture Type SF2
Lighting Fixture Type SF4
Mandatory Spare Parts
For 132/33KV,50MVA Transformers
145kV H.V. Bushing with metal parts and Gaskets
HV side neutral bushing
36KV LV bushing
36kV Neutral Bushing with metal parts and gaskets
Local and remote winding temperature indicators with alarm and trip contacts and maximum reading pointer
Oil temperature indictor with alarm and trip contacts and maximum reading pointer
Pressure relief device for main tank
Pressure relief device for OLTC
Silica Gel/ Maintenance free breather assembly (one of each type) for Conservator and OLTC
Magnetic oil level gauge with low oil level alarm contacts
Oil Flow indicator with contacts
Coller Pump with Motor
Cooler fan with motor.
Buchholz relay.
Tap position Indicator (Local and remote)
Oil Sampling Bottle
Oil Surge Relay
Complete set of gasket (complete set for one transformer)
Set of valves (complete set for one transformer)
For 132KV Transformer Control and Relay Panel
Differential relay
Master Trip relay
Trip Circuit Supervision relay
Testing Kit for Transformers
Automatic Transformer Oil BDV Testing Kit
Stainless Steel Oil sampling bottle (One Litre Capacity)
Syringes for sampling oil (50ml capacity)
Supply of 33kV Equipments and Panels (Supply C)
33kV,3 Phase, 13 Unit Panel (8 Line Bays, 2 Transformer incomer Bays, 1 Bus Sectionalizer Bay and 2 PT Bay ) Indoor Drawn out type switchgear as per specification (Single bus with sectionalizer)
30 kV,10 kA, Metal Oxide type, heavy duty, station class Lightning Arrestor complete with Pipe Structure, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
Outdoor type 36 kV, 1250 A, 3-Ph gang operated, Double Break centre Post rotating outdoor type motor operated Disconnector (Isolator) with solid core Post Insulator, Pipe Structures, Clamps and Connectors
With one earth switch
Supply of 33kV XLPE Cable and Termination Kit
300 sqmm, 33kV, 1-Core, XLPE Armoured Cu cable alongwith related accessories
33kV Cable Termination Kit (both indoor and outdoor) along with its accessories and related structure for outdoor type.
33kV Support Structure for Outdoor Cable Termination Kit
LT Power Cable (1.1kV grade)
(ii) 4C, 16 mm2
(iii) 3½ C, 35 mm2
(iv) 3½ C, 70 mm2
LT Control Cable
(ii) 7C, 1.5 mm2
(iii) 12C, 1.5 mm2
(iv) 19C, 1.5 mm2
Supply of Indoor floor mounted, SIMPLEX type control and relay panels, with mimic & annunciation panel with SAMAST Compliant ABT Meters for 33kV system as per specification
33 kV Panels
33KV Line Protection & Control Panel with LBB
33KV Transformer I/C Protection & Control Panel on 33 k V side of Power Transformer
33KV Protection & Control Panel for Bus Section
Substation Automation System and Integration with existing SAS
Complete Sub Station Automation System for 132/33kV GSS including Hardware and Software for the substation and remote control stations alongwith associated equipments for the 33kV Line Bays, Transformer Bays, Bus Sectionaliser Bays, Bus PT etc. including integration of existing SAS
Conductor
ACSR Panther
Bay Steel Structures except equipment mounting structures
COLUMNS
Column Type ‘C5’
Column Type ‘C6’
BEAMS
Beam Type ‘B5’
Insulator and hardwares
33 kV, 90kN Tension String insulators and hardwares suitable for Single Panther conductors
33 kV, 70kN Suspension String insulators and hardwares suitable for Single Panther conductors
Illumination System
Indoor Illumination system for the 33kV Indoor Switchgear Room
Lightning protection (lightning masts, lightning spikes, shield wires, down conductors etc.)
Description of Work / Item(s)
Amount
Supply of 132kV GIS Equipments( F&I A)
145kV,3150A, 40kA for 4 second, SF6 gas-insulated metal enclosed Transformer bay module each set comprising of One (1) number 3-phase, 3150A, SF6 insulated circuit breaker complete with operating mechanism; Three (3) numbers 1-phase, 5-core, multi ratio,600-300/1-1-1-1-1A current transformers; Three (3) numbers 3-phase, 3150A, group operated isolators/disconnectors, complete with manual and motor driven operating mechanisms; One (1) number 3-phase, group operated safety grounding switches, complete with manual and motor driven operating mechanisms; Gas monitoring devices, barriers, pressure switches, UHF PD Sensors, support structure etc. as required; Local Bay control cubicle.(Stand Alone or Integrated)
Three phase, 3150A, 40kA for 4 second, SF6 gas-insulated metal enclosed bus bar of 145kV, each set comprising of Bus bars enclosures running from the existing Bus bar Module to interconnect each of the Transformer circuit breaker bay modules in Double Bus bar configuration; Gas monitoring devices, barriers, pressure switches, UHF PD Sensors, support structure etc. as required
145kV, 3150A, 40 kA for 4 sec, 3- phase SF6 to air bushings along with termination module & support structure for outdoor connections to connect GIS with 145kV side of Power transformer.
145kV, 3150A, 40kA for 4 second, 3-Ph encapsulated, SF6 Gas Insulated Bus Duct (GIB) outside GIS hall including Bus Duct support structure and associated accessories along with jointing elements
Erection Hardware for 145kV GIS Termination arrangement for Transformer bay Modules
Supply of outdoor bay equipments (F&I B)
Transformer
50 MVA, 132/33 kV, 3-Ph, YNyn0, Z =12.5 %, ONAN/ONAF with copper wound Power Transformer with OLTC(+5% to -15% in steps of 1.25%) , RTCC panel including all cabling, insulating oil for the transformer plus 10% spare oil, supplied with Bushing mounted NCT on HV & LV side & complete with all fittings and accessories to meet the technical specification including cost of all routine test including loading and unloading at site.The Transformer shall be suitable for 4" Aluminium Tubular Conductor termination on HV and LV side.
Online DGA
Online Insulating oil drying system
Lightning Arrester
120 kV, 10 kA, Metal Oxide type, heavy duty, station class 3, Lightning Arrestor complete with Pipe Structures, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
30 kV,10 kA, Metal Oxide type, heavy duty, station class Lightning Arrestor complete with Pipe Structures, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
Supply of 33kV XLPE Cable and Termination Kit
1000 sqmm, 33kV, 1-Core, XLPE Armoured Cu cable alongwith related accessories
33kV Cable Termination Kit (both indoor and outdoor) along with its accessories.
33kV Support Structure for Outdoor Cable Termination Kit
LT Power Cable (1.1kV grade)
(ii) 4C, 16 mm2
(iii) 3½ C, 35 mm2
(iv) 3½ C, 70 mm2
(vi) Cable Supports and fittings
LT Control Cable
(ii) 7C, 1.5 mm2
(iii) 12C, 1.5 mm2
(iv) 19C, 1.5 mm2
Earthing
Main Earthing Conductor 40mm dia MS Rod
Earthing Conductor: 40mm dia MS Rod For Riser From The Burial Earth Mat To Equipment,Structure Etc)
Earthing Conductor: 75X12mm GI Flat For Equipment and Structure Earthing
Earthing Conductor: 50X6 mm GI(HDG) Flat For Riser For Console Box,Lt Panels,Dc Panels,Marshalling Boxes, Cable Trenches Etc)
Earthing Device & Associated Accessories (50 mm Heavy Duty GI Perforated Pipe 3 Mtrs Long For Treated Earth Pit)
Earthing Device & Associated Accessories 40Mm Ms Rod 3 Mtrs Long For Non Treated Earth Pit)
Separate Earthing For 145 Kv GIS Modules
Separate Earthing For 145 Kv GIS Building
Separate Earthing For 36 Kv Indoor AIS Equipment
Separate Earthing For 36 Kv Indoor AIS Building
Other Earthing Accessories
Fire Protection System for Transformer
NIFPS
N2 Fire Prevention and extinguishing System for transformer with complete accessories and related Civil and Electrical works.
HVW spray system, Hydrant System and complete U/G and O/G Piping and accessories etc and associated Civil Works for fire protection system for 2 nos 50 MVA 132/33kV Transformer
HVWS System for 50 MVA ICT
Portable/Wheel/ Trolley mounted Fire Extinguishers
22.5 Kg capacity FE CO2 type, Trolley Mounted
25 Kg Capacity FE DCP type, Trolley Mounted
DCP 10 Kg Capacity, Wall mounted
FE CO2 6.5 Kg capacity, Wall mounted
DCP 5 Kg Capacity, Wall mounted
Foam Type 9 liter Capacity, Wall mounted
Water CO2 9 liter, Wall mounted
Fire Buckets (12 Nos. with stand in one set)
Supply of Indoor floor mounted, SIMPLEX type Control and Relay Panels, with mimic & annunciation panel for 132kV system as per specification comprising of the C & R Panels and shall be complete with Numerical Relays and SAMAST Compliant ABT Meters as per the Technical specifications & shall be compatible for SCADA/ SAS .
132kV Panels
Transformer Protection Panel
Substation Automation System
Complete Sub Station Automation System for 132/33kV GSS Transformer Bays including Hardware and Software for the substation and remote control stations alongwith associated equipments for the transformer bay
Integration with the existing SAS system
Conductor / IPS Al Tube
4" IPS Al Tube
Lightning protection
Lightning Mast (LM)- 40m
Illumination system for Outdoor Lighting (Switchyard and Street lighting)
Lighting Panel
Lighting Panel Type ACP-2
Sub lighting panel type SLP
lighting Fixtures and Receptacles including junction box, lighting wires and flexible conduit (if required) from junction box to lighting fixture, mounting arrangement and other accessories/ materials etc as required for complete installation and commissioning of lighting fixture
Lighting Fixture Type SF1
Lighting Fixture Type SF2
Lighting Fixture Type SF4
Mandatory Spare Parts
For 132/33KV,50MVA Transformers
145kV H.V. Bushing with metal parts and Gaskets
HV side neutral bushing
36KV LV bushing
36kV Neutral Bushing with metal parts and gaskets
Local and remote winding temperature indicators with alarm and trip contacts and maximum reading pointer
Oil temperature indictor with alarm and trip contacts and maximum reading pointer
Pressure relief device for main tank
Pressure relief device for OLTC
Silica Gel/ Maintenance free breather assembly (one of each type) for Conservator and OLTC
Magnetic oil level gauge with low oil level alarm contacts
Oil Flow indicator with contacts
Coller Pump with Motor
Cooler fan with motor.
Buchholz relay.
Tap position Indicator (Local and remote)
Oil Sampling Bottle
Oil Surge Relay
Complete set of gasket (complete set for one transformer)
Set of valves (complete set for one transformer)
For 132KV Transformer Control and Relay Panel
Differential relay
Master Trip relay
Trip Circuit Supervision relay
Testing Kit for Transformers
Automatic Transformer Oil BDV Testing Kit
Stainless Steel Oil sampling bottle (One Litre Capacity)
Syringes for sampling oil (50ml capacity)
Supply of 33kV Equipments and Panels (F&I C)
33kV,3 Phase, 13 Unit Panel (8 Line Bays, 2 Transformer incomer Bays, 1 Bus Sectionalizer Bay and 2 PT Bay ) Indoor Drawn out type switchgear as per specification (Single bus with sectionalizer)
30 kV,10 kA, Metal Oxide type, heavy duty, station class Lightning Arrestor complete with Pipe Structure, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
Outdoor type 36 kV, 1250 A, 3-Ph gang operated, Double Break centre Post rotating outdoor type motor operated Disconnector (Isolator) with solid core Post Insulator, Pipe Structures, Clamps and Connectors
With one earth switch
Supply of 33kV XLPE Cable and Termination Kit
300 sqmm, 33kV, 1-Core, XLPE Armoured Cu cable alongwith related accessories
33kV Cable Termination Kit (both indoor and outdoor) along with its accessories and related structure for outdoor type.
33kV Support Structure for Outdoor Cable Termination Kit
LT Power Cable (1.1kV grade)
(ii) 4C, 16 mm2
(iii) 3½ C, 35 mm2
(iv) 3½ C, 70 mm2
LT Control Cable
(ii) 7C, 1.5 mm2
(iii) 12C, 1.5 mm2
(iv) 19C, 1.5 mm2
Supply of Indoor floor mounted, SIMPLEX type control and relay panels, with mimic & annunciation panel with SAMAST Compliant ABT Meters for 33kV system as per specification
33 kV Panels
33KV Line Protection & Control Panel with LBB
33KV Transformer I/C Protection & Control Panel on 33 k V side of Power Transformer
33KV Protection & Control Panel for Bus Section
Substation Automation System and Integration with existing SAS
Complete Sub Station Automation System for 132/33kV GSS including Hardware and Software for the substation and remote control stations alongwith associated equipments for the 33kV Line Bays, Transformer Bays, Bus Sectionaliser Bays, Bus PT etc. including integration of existing SAS
Conductor
ACSR Panther
Bay Steel Structures except equipment mounting structures
COLUMNS
Column Type ‘C5’
Column Type ‘C6’
BEAMS
Beam Type ‘B5’
Insulator and hardwares
33 kV, 90kN Tension String insulators and hardwares suitable for Single Panther conductors
33 kV, 70kN Suspension String insulators and hardwares suitable for Single Panther conductors
Illumination System
Indoor Illumination system for the 33kV Indoor Switchgear Room
Lightning protection (lightning masts, lightning spikes, shield wires, down conductors etc.)
Description of Work / Item(s)
Amount
Foundation,Erection, Testing & Commissioning of 132kV GIS Equipments( Erection A)
145kV, 3150A, 40kA for 4 second, SF6 gas-insulated metal enclosed Transformer bay module each set comprising of One (1) number 3-phase, 3150A, SF6 insulated circuit breaker complete with operating mechanism; Three (3) numbers 1-phase, 5-core, multi ratio,600-300/1-1-1-1-1A current transformers; Three (3) numbers 3-phase, 3150A, group operated isolators/disconnectors, complete with manual and motor driven operating mechanisms; One (1) number 3-phase, group operated safety grounding switches, complete with manual and motor driven operating mechanisms;Gas monitoring devices, barriers, pressure switches, UHF PD Sensors, support structure etc. as required; Local Bay control cubicle.(Stand Alone or Integrated)
Three phase, 3150A, 40kA for 4 second, SF6 gas-insulated metal enclosed bus bar of 145kV, each set comprising of Bus bars enclosures running from the existing Bus bar Module to interconnect each of the Transformer circuit breaker bay modules in Double Bus bar configuration; Gas monitoring devices, barriers, pressure switches, UHF PD Sensors, support structure etc. as required
145kV, 3150A, 40 kA for 4 sec, 3- phase SF6 to air bushings along with termination module & support structure for outdoor connections to connect GIS with 145kV side of Power transformer.
145kV, 3150A, 40kA for 4 second, 3-Ph encapsulated, SF6 Gas Insulated Bus Duct (GIB) outside GIS hall including Bus Duct support structure and associated accessories along with jointing elements
Erection Hardware for 145kV GIS Termination arrangement for Transformer bay Modules
Foundation,Erection, Testing & Commissioning of outdoor bay equipments (Erection B)
Transformer
50 MVA, 132/33 kV, 3-Ph, YNyn0, Z =12.5 %, ONAN/ONAF with copper wound Power Transformer with OLTC(+5% to -15% in steps of 1.25%) , RTCC panel including all cabling, insulating oil for the transformer plus 10% spare oil, supplied with Bushing mounted NCT on HV & LV side & complete with all fittings and accessories to meet the technical specification including cost of all routine test including loading and unloading at site.The Transformer shall be suitable for 4" Aluminium Tubular Conductor termination on HV and LV side.
Online DGA
Online Insulating oil drying system
Lightning Arrester
120 kV, 10 kA, Metal Oxide type, heavy duty, station class 3, Lightning Arrestor complete with Pipe Structures, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
30 kV,10 kA, Metal Oxide type, heavy duty, station class Lightning Arrestor complete with Pipe Structures, Surge Counter, Hardware fittings and Clamps and Connectors as per specification
Erection of 33kV XLPE Cable and Termination Kit
Laying of 1000 sqmm, 33kV, 1-Core, XLPE Armoured Cu cable alongwith related accessories in cable trenches and cable terminations including supply of cable end sealing boxes, construction of cable trenches etc
33kV Cable Termination Kit (both indoor and outdoor) along with its accessories and related structure for outdoor type.
33kV Support Structure for Outdoor Cable Termination Kit
Earthing
Main Earthing Conductor 40mm dia MS Rod
Earthing Conductor: 40mm dia MS Rod For Riser From The Burial Earth Mat To Equipment,Structure Etc)
Earthing Conductor: 75X12mm GI Flat For Equipment and Structure Earthing
Earthing Conductor: 50X6 mm GI(HDG) Flat For Riser For Console Box,Lt Panels,Dc Panels,Marshalling Boxes, Cable Trenches Etc)
Earthing Device & Associated Accessories (50 mm Heavy Duty GI Perforated Pipe 3 Mtrs Long For Treated Earth Pit)
Earthing Device & Associated Accessories 40Mm Ms Rod 3 Mtrs Long For Non Treated Earth Pit)
Soil Resistivity Test And Soil Treatment As And When Required
Separate Earthing For 145 Kv GIS Modules
Separate Earthing For 145 Kv GIS Building
Separate Earthing For 36 Kv Indoor AIS Equipment
Separate Earthing For 36 Kv Indoor AIS Building
Other Earthing Accessories
Fire Protection System for Transformer
NIFPS
N2 Fire Prevention and extinguishing System for transformer with complete accessories and related Civil and Electrical works.
HVW spray system, Hydrant System and complete U/G and O/G Piping and accessories etc and associated Civil Works for fire protection system for 2 nos 50 MVA 132/33kV Transformer
HVWS System for 50 MVA ICT
Portable/Wheel/ Trolley mounted Fire Extinguishers
22.5 Kg capacity FE CO2 type, Trolley Mounted
25 Kg Capacity FE DCP type, Trolley Mounted
DCP 10 Kg Capacity, Wall mounted
FE CO2 6.5 Kg capacity, Wall mounted
DCP 5 Kg Capacity, Wall mounted
Foam Type 9 liter Capacity, Wall mounted
Water CO2 9 liter, Wall mounted
Fire Buckets (12 Nos. with stand in one set)
Erection of Indoor floor mounted, SIMPLEX type Control and Relay Panels, with mimic & annunciation panel for 132kV system as per specification comprising of the C & R Panels and shall be complete with Numerical Relays and SAMAST Compliant ABT Meters as per the Technical specifications & shall be compatible for SCADA/ SAS .
132kV Panels
Transformer Protection Panel
Substation Automation System
Complete Sub Station Automation System for 132/33kV GSS Transformer Bays including Hardware and Software for the substation and remote control stations alongwith associated equipments for the transformer bay
Integration with the existing SAS system
Conductor / IPS Al Tube
4" IPS Al Tube
Lightning protection
Lightning Mast (LM)- 40m
Erection of mounting structures as required including construction of foundations and supply of all foundation materials.
132kV Equipments
Lightning Arrester (1 Phase)
33kV Equipments
Lightning Arrester (1 Phase)
Illumination system for Outdoor Lighting (Switchyard and Street lighting)
Lighting Panel
Lighting Panel Type ACP-2
Sub lighting panel type SLP
lighting Fixtures and Receptacles including junction box, lighting wires and flexible conduit (if required) from junction box to lighting fixture, mounting arrangement and other accessories/ materials etc as required for complete installation and commissioning of lighting fixture
Lighting Fixture Type SF1
Lighting Fixture Type SF2
Lighting Fixture Type SF4
Foundation,Erection, Testing & Commissioning of 33kV Equipments and Panels(Erection C)
33kV,3 Phase, 13 Unit Panel (8 Line Bays, 2 Transformer incomer Bays, 1 Bus Sectionalizer Bay and 2 PT Bay ) Indoor Drawn out type switchgear as per specification (Single bus with sectionalizer)
30 kV,10 kA, Metal Oxide type, heavy duty, station class Lightning Arrestor complete with Surge Counter & copper connecting lead
Outdoor type 36 kV, 1250 A, 3-Ph gang operated, outdoor type, Double Break centre Post rotating outdoor type motor operated Disconnector (Isolator) with solid core Post Insulator.
With one earth switch
Supply of 33kV XLPE Cable and Termination Kit
300 sqmm, 33kV, 1-Core, XLPE Armoured Cu cable alongwith related accessories
33kV Cable Termination Kit (both indoor and outdoor) along with its accessories and related structure for outdoor type.
33kV Support Structure for Outdoor Cable Termination Kit
Erection of Control, Relay & Protection Panel(Simplex Type) with mimic & annunciation panel with ABT Meters for 33kV system as per specification
33 kV Panels
33KV Line Protection & Control Panel
33KV Transformer I/C Protection & Control Panel on 33 k V side of Power Transformer
33KV Protection & Control Panel for Bus Section
Substation Automation System and Integration with existing SAS
Complete Sub Station Automation System for 132/33kV GSS including Hardware and Software for the substation and remote control stations alongwith associated equipments for the 33kV Line Bays, Transformer Bays, Bus Sectionaliser Bays, Bus PT etc. including integration of existing SAS
Bay Steel Structures except equipment mounting structures
COLUMNS
Column Type ‘C5’
Column Type ‘C6’
Construction of foundations for lattice steel columns including supply of all foundation materials and labour
BEAMS
Beam Type ‘B5’
Erection of Foundation Bolts (including nuts, checknut and washers for lattice and pipe structures)
Erection of Fasteners (nuts, bolts and washers) including step bolts for lattice and pipe structures
Erection of mounting structures as required for Lightning Arrester including construction of foundations and supply of all foundation materials.
33kV Equipments
Isolator
Lightning Arrester (1 Phase)
Illumination System
Indoor Illumination system for the 33kV Indoor Switchgear Room
Lightning protection (lightning masts, lightning spikes, shield wires, down conductors etc.)
Description of Work / Item(s)
Amount
Site development, PCC and Gravelling work
Clearing and grubbing road land including uprooting wild vegetation, grass, bushes, shrubs, saplings and trees of girth upto 300 mm, removal of stumps of such trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned, upto a lead of 1000 m including removal and disposal of top organic soil not exceeding 150 mm in thickness as per Technical Specification Clause 201. (i) By Manual Means. (b) In area of thorny jungle.
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.(profile measurement to be taken and 12.5% deduction for shrinkage to be made from total quantity) etc. complete as directed and specified.
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 100 mm nominal dia Pipes
Providing and fixing PTMT grating of approved quality and colour. Circular type 100 mm nominal dia
Supplying and laying 100 mm thick machine crushed 25 mm stone aggregates in layers.
Cost of Haulage excluding loading and unloading. Surface road. 25-5=20KM @ Rs.16.00 Cum/KM=20X16=320
Trenches work
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M25 grade with minimum cement content of 330 kg /cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter.
Boundary / Retaining wall
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.
All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum
All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Coursed rubble masonry (first sort) with hard stone in foundation and plinth with : Cement mortar 1:6 (1 cement : 6 coarse sand)
Tower foundations
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum
Equipment foundations
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
50 MVA Power Transformer foundation-2 Nos
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Fire Protection wall- 1 Nos
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil.
Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M10 grade with minimum cement content of 220 kg /cum
Brick on edge flooring with bricks of class designation 7.5 on a bed of 12 mm cement mortar, including filling the joints with same mortar, with common burnt clay non modular bricks: 1:6 (1cement : 6 coarse sand)
5.33 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; including the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.
All works upto plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum
All works above plinth level upto floor V level Concrete of M25 grade with minimum cement content of 330 kg /cum
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand)
15 mm cement plaster on the rough side of single or half brick wall of mix : (1 cement: 6 fine sand)
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : Water thinnable cement
Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm)
VCB Building
Design and Construction of VCB Building ( Ht=6.00 meter ) with all finishes, Sanitary System,Plumbing,Electrification,AIR Conditioning etc as per the drawing ,specification and direction of Engineer In Charge .Rate shall include supply of all material and labour.
PCC Road
Brick on edge flooring with bricks of class designation 7.5 on a bed of 12 mm cement mortar, including filling the joints with same mortar, with common burnt clay non modular bricks: 1:6 (1cement : 6 coarse sand)
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Mega Electricals
Kanohar Electricals Limited
Kalpataru Power Transmission Limited
Shyama Power India Limited
Mega Electricals
Kalpataru Power Transmission Limited
Kanohar Electricals Limited
Shyama Power India Limited
Kalpataru Power Transmission Limited
Mega Electricals
Kanohar Electricals Limited
Kalpataru Power Transmission Limited
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid